Heat & Glo LifeStyle 550TRSI-AUF Vent Clearances and Framing, Combustible Wall Penetration

Page 38

8 Vent Clearances and Framing

A. Pipe Clearances to Combustibles

B. Wall Penetration Framing

 

 

WARNING! Risk of Fire! Maintain air space clearance to

Combustible Wall Penetration

 

 

vent. DO NOT pack insulation or other combustibles:

Whenever a combustible wall is penetrated, you must

 

 

 

 

Between ceiling firestops

 

frame a hole for the wall shield firestop(s). The wall shield

Between wall shield firestops

firestop maintains minimum clearances and prevents cold

• Around vent system

 

air infiltration.

 

 

 

 

 

Failure to keep insulation or other material away from

• The opening must be framed on all four sides using the

vent pipe may cause over heating and fire.

same size framing materials as those used in the wall

 

 

 

 

construction.

 

 

 

 

 

 

 

 

 

• DVP pipe - A wall shield firestop is required on one side

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

only on interior walls. If your local inspector requires a

DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184

wall shield firestop on both sides, then both wall shield

 

mm) thick.

 

 

• If wall thickness is less than 4 in. the existing heat shields must be field trimmed. If

firestops

must

have

a heat

shield

(refer

to Section

 

wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.

16.B.) attached to them.

 

 

 

SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to

 

 

 

 

194 mm thick).

 

 

• SLP pipe - A wall shield firestop must be placed on each

• If wall thickness is less than 4-3/8 the existing heat shields must be field trimmed.

 

If wall thickness is greater than 7-5/8 in. a DVP-HSM-B will be required.

side of an interior wall. A minimum 1-1/2 inch (38 mm)

 

 

 

 

overlap of attached heat shields must be maintained.

 

 

(DVP-SLP Pipe Shown)

• See Section 10.H. for information for regarding the in-

 

 

 

 

stallation of a horizontal termination cap.

 

 

 

Heat

3 in. (76 mm)

Non-Combustible Wall Penetration

 

 

 

3 in. (76 mm)

Shield

top clearance *

If the hole being penetrated is surrounded by noncom-

 

top clearance

 

Heat

 

 

 

Shield

bustible materials such as concrete, a hole with diameter

 

 

 

 

 

 

 

 

 

 

1 in. (25 mm)

 

 

one inch greater than the pipe is acceptable.

 

clearance around

 

 

Whenever a non-combustible wall is penetrated, the wall

vertical sections

 

 

 

 

 

1 in. (25 mm)

shield firestop is only required on one side and no heat

 

 

Wall

clearance

shield is necessary.

 

 

 

 

 

 

Shield

bottom & sides

 

 

 

 

 

 

Firestop

 

 

 

 

 

 

 

 

 

 

WALL

Note: A 6 in. (152 mm) section of straight flue must

 

 

 

be attached to the fireplace before a 90° elbow.

 

 

 

 

 

 

Heat

3 in. (76 mm)

 

 

 

 

 

 

 

 

 

Shield

top clearance *

 

 

 

 

 

 

 

 

 

 

Heat

 

 

 

 

 

 

 

 

 

 

Shield

 

 

 

 

 

 

 

 

 

Wall

1 in. (25 mm)

 

 

 

 

 

 

 

 

 

clearance

 

 

 

 

 

 

 

 

 

Shield

bottom & sides

 

 

 

 

C

 

 

 

 

Firestop

 

10 in.

 

10 in.

 

 

 

 

 

 

 

 

D

 

 

 

 

 

WALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* When using SLP or SL-D pipe, minimum clearances from the vent pipe to combus-

 

10 in.

 

12 in.

 

 

 

 

tible materials at inside wall firestops are: Top: 2-1/2 in. (64 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bottom: 1/2 in. (13 mm)

 

 

 

 

 

 

 

 

 

 

Sides: 1 in. (25 mm)

 

 

 

 

 

 

 

Figure 8.1 Horizontal Venting Clearances To Combustible

A*

B*

 

 

 

 

 

 

Materials

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A*

B*

C

D

 

 

 

 

550TRSI-AUF

in.

40-3/4 24-3/8 39-3/4

23-3/8

 

 

 

 

550TRSILP-AUF

mm

1035

619

1010

593

 

 

 

 

* Shows center of vent framing hole for top or rear venting. The center of the

 

 

 

 

hole is 1 in. (25 mm) above the center of the horizontal vent pipe.

 

 

 

 

Figure 8.2

Wall Penetration

 

 

 

38

 

 

Heat & Glo • 550TRSI-AUF, 550TRSILP-AUF2079-980 Rev. N • 5/12

 

 

 

 

 

 

 

 

 

Image 38
Contents What to do if you smell gas Models 550TRSI-AUF 550TRSILP-AUFRef No GSCS20163 Sans 15392008 AS45532008 Hot glass will cause burnsModels 550TRSI-AUF, 550TRSILP-AUF Congratulations Homeowner Reference InformationSans Novida Testing ServiceSans Compliance Table of Contents User GuideGas Information Appliance SetupTroubleshooting Electrical InformationAustralian Warranty Information Limited Lifetime WarrantyOther Rights This warranty is void if PerthListing and Code Approvals Your Fireplace Gas Fireplace SafetyOperating Instructions User Guide Fan Kit Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Clear SpaceLighting Instructions IPI Final inspection byNine Hour Safety Shutdown Feature Control Module OperationFrequently Asked Questions After Fireplace is LitMaintenance and Service Logs Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection FireboxGetting Started Typical Appliance SystemInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Any such action may cause a fire hazardFraming and Clearances Selecting Appliance LocationConstructing the Appliance Chase ClearancesMinimum Framing Dimensions Combustible Mantel Legs or Wall Projections Mantel and Wall ProjectionsCombustible Mantels Termination Locations Vent Termination Minimum ClearancesMIN. Clearance in. mm ClearanceVent Information and Diagrams Top Vent Horizontal Termination V1 Minimum H1 MaximumTop Vent Horizontal Termination Two Elbows Minimum + H 2 MaximumThree Elbows Min MaxTop Vent Vertical Termination Straight Up Vertical Flue SystemFlue System Approvals And Installations Flue Termination ApprovalsTop Vent Vertical Termination Two Elbows H1 Maximum V1 + V2 MinTop Vent Vertical Termination Three Elbows H1 + H2 V1 + V2 Minimum H1 + H2 MaximumH1 Minimum H1 Maximum Rear Vent Horizontal Termination No ElbowOne 45º Elbow Rear Vent Horizontal Termination Two Elbows H3H2V1 Minimum H1 + H2 Maximum Rear Vent Vertical Termination One Elbow Two ElbowsMinimum Maximum Minimum + H 2 + H Maximum Rear Vent Vertical Termination Three ElbowsMaximum Minimum + H 2 Maximum Combustible Wall Penetration Vent Clearances and FramingPipe Clearances to Combustibles Wall Penetration Framing Non-Combustible Wall PenetrationInstall the Ceiling Firestop Pipe DVP SLPFlat Ceiling Installation Install Attic Insulation ShieldInstalling the Optional Heat-Zone-240V Kit Vaulted Ceiling InstallationAppliance Preparation Top VentRear Vent Cut the metal retaining band and fold the sides outInstalling the Non-combustible Board Securing and Leveling the ApplianceAdjustments And Replacement Parts Components Removal For ServiceParts Replacement Install Trim and/or SurroundAssemble Vent Sections DVP Pipe Only Installing Vent Pipe DVP and SLP PipeAttach Vent to the Firebox Assembly Assemble Pipe SectionsAssemble Vent Sections SLP Pipe Only Assemble Slip SectionsSecure the Vent Sections Disassemble Vent SectionsInstall Support Brackets Install FirestopsFor Horizontal Terminations using the SLP-TRAP2 or DVP-TRAP2 Flue TerminationInstall Metal Roof Flashing Heat Shield Requirements for Horizontal TerminationAssemble and Install Storm Collar Install Vertical Termination CapGas Information Gas ConnectionGAS Access Optional Accessories Requirements Wiring RequirementsIntelliFire Plus Ignition System Wiring Optional Remote Control Receiver LocationBlower Fireplace Specific Information Kit ContentsInstallation Precautions IntroductionChanging Temperature Scale Installation of Remote Control HousingProgramming the RC300AU to the Control Module AUX300CE Module InstallationFan Installation Display Screen Idle When Remote is in on ModeStandby mode Function ButtonsAdjusting Flame Height About on ModeAbout OFF Mode Adjusting Fan SpeedSetting the Child Lock Adjusting ThermostatAdjusting Timer Power OutageFrequently Asked Questions/Troubleshooting Symptom Possible Cause Corrective Action816 940 FinishingFacing Material Clean the Appliance Appliance SetupRemove Fixed Glass Assembly AccessoriesLog Placement Instructions 3 4 5 6 7Heat & Glo 550TRSI-AUF, 550TRSILP-AUF 2079-980 Rev. N 5/12 Heat & Glo 550TRSI-AUF, 550TRSILP-AUF 2079-980 Rev. N 5/12 IntelliFire Plus Ignition System TroubleshootingSymptom Possible Cause Corrective Action Troubleshooting Location Inches Millimeters Appliance Dimension DiagramReference Materials Maintenance Tasks Inspect Maintenance TasksVent Components Diagrams DVP-AS2Horizontal Termination Cap Mm Heat Shield 15-1/8 384 mmEffective Length DVP-HRC-SS DVP-HRC-ZC-SS Elbow 165 mm165 mm 222 mm 235 mm 152 mm 168 mm 251 mmCathedral Ceiling Heat Shield 15-1/8 384 mmEffective HorizontalService Parts Log Set Assembly#19 Valve Assembly Beginning Manufacturing Date July Ending Manufacturing DateService Parts List Conversion KitsContact Information