Vermont Casting DVRTSB manual Below Grade Installation, Vertical Through-the-Roof Applications

Page 17

Below Grade Installation

When it is not possible to meet the required vent ter- minal clearances of 12” (305 mm) above grade level a starter kit is recommended. It allows installation depth of down to 7” (178 mm) below grade level. The 7” (178mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall.

If venting system is installed below ground, we recom- mend a window well with adequate and proper drain- age.

Ensure sidewall venting clearances are observed.

If installing a snorkel, a minimum 24” (610mm) vertical rise is necessary. The maximum horizontal run with the 24” (610mm) vertical pipe is 36” (914mm). The meas- urement is taken from the collar of the fireplace (or tran- sition elbow) to the face of the exterior wall. See Vent Chart (see ‘How to use the Vent Graph’) for extended horizontal runs if the vertical exceeds 24” (610mm).

1.Establish vent hole through the wall. (Fig. 23)

2.Remove soil to a depth of approximately 16” (406mm) below base of snorkel. Install drain pipe. Install window well (not supplied). Refill hole with 12” (305mm) of coarse gravel leaving a clearance of ap- proximately 4” (100mm) below snorkel. (Fig. 27)

3.Install vent system.

4.Ensure a watertight seal is made around the vent pipe coming through the wall.

5.Apply high temperature sealant caulking (supplied) around the 4” and 7” snorkel collars.

6.Slide the snorkel into the vent pipes and secure to the wall.

7.Level the soil so as to maintain a 4” (100mm) clear- ance below snorkel. (Fig. 27)

Zero Clearance

 

 

Sleeve if Required

 

 

Firestop

 

7DVSKS

7” Pipe

Screws

(Snorkel)

 

 

Minimum 4” Clearance

 

 

 

Ground

 

Window Well

24” (610mm)

Gravel

Drain

Minimum

 

Foundation Wall

 

• A minimum of 24” (610mm) vertical

 

pipe must be installed when using

 

the 7DVSKS/7TDVSKS kit.

 

• The 22” vertical rise (center to cen-

 

ter) of the snorkel may be included

FP1386

for calculation of max. horizontal

 

run.

Fig. 27 Below grade installation.

10003848

 

DVRTSB Bay Window Fireplace

Do not back fill around snorkel.

A clearance of at least 4” (100mm) must be maintained between the snorkel and the soil.

If the foundation

 

 

 

is recessed, use

 

 

 

recess brackets

 

 

 

(not supplied) for

 

 

Snorkel

securing lower

 

 

portion of the

Foundation

 

snorkel. Fasten

Recess

Wall

 

 

brackets to wall

Water-

 

Screws

 

 

first, then secure

 

 

tight Seal

 

to snorkel with self

Around

 

Sheet Metal

Pipe

 

drilling #8 x 1/2

 

Screws

 

 

 

 

 

sheetmetal screws.

 

 

CFM139

It will be necessary

Fig. 28

Snorkel installatin, recessed

to extend vent

foundation.

 

pipes out as far as

 

 

 

 

protruding wall face. (Fig. 28)

 

 

Vertical Through-the-Roof Applications

This Gas Fireplace has been approved for:

Vertical installations up to 40’ (12 m) in height. Up to a 10’ (3 m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows. (Fig. 29 & 30)

Up to two (2) 45° elbows may be used within the horizontal run. For each 45° elbow used on the horizontal level the maximum horizontal length must be reduced by 18” (457 mm).

Example: Maximum horizontal length

0

x

45° elbows =

10’ (3 m)

1

x

45° elbows =

8.5’ (2.6 m)

2

x

45° elbows =

7’ (2.1 m)

A minimum of an 8’ (2.4 m) vertical rise.

A maximum of two (2) sets of 45° elbow offsets can be used within these vertical installation. From 0 to a maximum of 8’ of vent pipe can be used between elbows. (Fig. 30)

7DVCS supports offsets. (Fig. 32) This application will require that you first determine the roof pitch and use the appropriate starter kit. (See Venting Components List)

The maximum angular variation allowed in the system is 270˚. (Fig. 30)

17

Image 17
Contents Homeowner’s Installation Operating Manual Table of Contents National Fuel Gas Code Ansi Z223.1/NFPA Installation & Operating InstructionsDvrtsb Top Vent Fireplace Dimensions Installed as Top VentFraming Dimensions Dvrtsb Rear Vent Fireplace Dimensions Installed as Rear VentClearance to Combustibles Locating Your FireplaceMantels HearthFinal Finishing Gas Line InstallationGas Specifications Gas Inlet and Manifold PressuresEB-1 Electrical Box Remote ON/OFF Switch InstallationAlternate Switch Location Remove flue cover and flue pipe Optional Top Vent ApplicationLocation of Vent Termination General Venting Information Termination LocationTermination location requirements Canadian Installations1 US Installations2Canadian Installations General Information for Connecting Vent PipesUSA Installations Twist Lock PipesRear Wall Vent Installation How to Use the Vent GraphRear Wall Vent Applications Example aZero clearance sleeve is only required for combustible walls Vertical Sidewall ApplicationsMaximum vent run with elbows Vertical Sidewall InstallationHorizontal length requirement Always install horizontal venting on a level planeVertical Through-the-Roof Applications Below Grade InstallationEnlarged ends of the vent section always face downward Vertical Through-The-Roof InstallationAttic Insulation Shield Upper Floor Twist Lock Venting Components Louvre Removal Glass InformationGlass/Frame Removal Side Glass FrameCeramic Refractory Installation Glass CleaningInstallation of Logs Clean the glass after the first two weeks of operationLava Rock & Ember Material Flame Characteristics Flame & Temperature AdjustmentCeramic Ember Rocks Pt. # RN/RP ModelsTo Turn Off Gas To Heater Lighting and Operating InstructionsTroubleshooting the Gas Control System Honeywell Millivolt Valve SIT top Convertible Pilot Fuel Conversion InstructionsPSE Pilot SIT 820 Nova Gas Control Valve FigBrass Trim Cleaning the Standing Pilot Control SystemBurner and Burner Compartment OFF DescriptionDvrtsb Dvrtsb Bay Window Fireplace Fan Kits ON/OFF and Temperature Remote ControlsModel Function/s Controlled Wall mounted thermostat controlDvrtsb Bay Window Fireplace Limited Lifetime Warranty Efficiency Ratings