DVRTSB Bay Window Fireplace
Troubleshooting the Gas Control System
SIT NOVA 820 Millivolt Valve
NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.
WARNING: Before doing any gas control service work, remove glass front.
Symptom | Possible Causes | Corrective Action |
1. Spark ignitor will not light | A. Defective or misaligned | Using a match, light pilot. If pilot lights, turn off |
| electrode at pilot. | pilot and push the red button again. If pilot will not |
|
| light - check gap at electrode and |
|
| 1/8” to have a strong spark. |
| B. Defective ignitor (Push Button) | Push Piezo Ignitor Button. Check for spark at |
|
| electrode and pilot. If no spark to pilot, and elec |
|
| trode wire is properly connected, replace ignitor. |
2. Pilot will not stay lit after | A. Defective pilot generator | Check pilot flame. Must impinge on thermo |
carefully following lighting | (thermocouple), remote wall | couple/thermopile. Note: this pilot burner assem |
instructions. | switch. | bly utilizes |
|
| The thermocouple operates the main valve |
|
| operation (On and Off). Clean and or adjust pilot for |
|
| maximum flame impingement on thermopile and |
|
| thermocouple. |
| B. Defective automatic valve | Turn valve knob to “Pilot”. Maintain flow to pilot; |
|
| milivolt meter should read greater than 10 mV. If |
|
| the reading is okay and the pilot does not stay on, |
|
| replace the gas valve. Note: An interrupter block |
|
| (not supplied) must be used to conduct this test. |
3. Pilot burning, no gas to | A. Wall switch or wires defective | Check wall switch and wires for proper connec |
main burner |
| tions. Jumper wire accross terminals at wall |
|
| switch, if burner comes on, replace defective wall |
|
| switch. If okay, jumper wires across wall switch |
|
| wires at valve, if burner comes on, wires are faulty |
|
| or connections are bad. |
| B. Thermopile may not be | 1. Be sure wire connections from thermopile at |
| generating sufficient | gas valve terminals are tight and thermopile is fully |
| millivoltage. | inserted into pilot bracket. |
|
| 2. One of the wall switch wires may be grounded. |
|
| Remove wall switch wires from valveterminals if |
|
| pilot now stays lit, trace wall switch wiring for |
|
| ground. May be grounded to fireplace or gas |
|
| supply. |
|
| 3. Check thermopile with millivolt meter. Take |
|
| reading at thermopile terminals of gas valve. |
|
| Should read |
|
| while holding valve knob depressed in pilot |
|
| position and wall switch “Off”. Replace faulty |
|
| thermopile if reading is below specified minimum |
| C. Plugged burner orifice. | Check burner orifices for debris and remove. |
| D. Defective automatic valve | Turn valve knob to “On”, place wall switch to “On” |
| operator. | millivolt meter should read greater than 100 mV. If |
|
| the reading is okay and the burner does not come on, |
|
| replace the gas valve. |
4. Frequent pilot outage | A. Pilot flame may be too low | Clean and/or adjust pilot flame for maximum flame |
problem. | or blowing (high) causing the | impingement on thermopile and thermocouple. |
| pilot safety to drop out. |
|
| B. Possible blockage of the vent | Check the vent terminal for blockage (recycling the |
| terminal. | flue gases) |
|
|
|
10003848 | 25 |