Vermont Casting DVRTSB manual Troubleshooting the Gas Control System

Page 25

DVRTSB Bay Window Fireplace

Troubleshooting the Gas Control System

SIT NOVA 820 Millivolt Valve

NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.

WARNING: Before doing any gas control service work, remove glass front.

Symptom

Possible Causes

Corrective Action

1. Spark ignitor will not light

A. Defective or misaligned

Using a match, light pilot. If pilot lights, turn off

 

electrode at pilot.

pilot and push the red button again. If pilot will not

 

 

light - check gap at electrode and pilot-should be

 

 

1/8” to have a strong spark.

 

B. Defective ignitor (Push Button)

Push Piezo Ignitor Button. Check for spark at

 

 

electrode and pilot. If no spark to pilot, and elec

 

 

trode wire is properly connected, replace ignitor.

2. Pilot will not stay lit after

A. Defective pilot generator

Check pilot flame. Must impinge on thermo

carefully following lighting

(thermocouple), remote wall

couple/thermopile. Note: this pilot burner assem

instructions.

switch.

bly utilizes both-a thermocouple and a thermopile.

 

 

The thermocouple operates the main valve

 

 

operation (On and Off). Clean and or adjust pilot for

 

 

maximum flame impingement on thermopile and

 

 

thermocouple.

 

B. Defective automatic valve

Turn valve knob to “Pilot”. Maintain flow to pilot;

 

 

milivolt meter should read greater than 10 mV. If

 

 

the reading is okay and the pilot does not stay on,

 

 

replace the gas valve. Note: An interrupter block

 

 

(not supplied) must be used to conduct this test.

3. Pilot burning, no gas to

A. Wall switch or wires defective

Check wall switch and wires for proper connec

main burner

 

tions. Jumper wire accross terminals at wall

 

 

switch, if burner comes on, replace defective wall

 

 

switch. If okay, jumper wires across wall switch

 

 

wires at valve, if burner comes on, wires are faulty

 

 

or connections are bad.

 

B. Thermopile may not be

1. Be sure wire connections from thermopile at

 

generating sufficient

gas valve terminals are tight and thermopile is fully

 

millivoltage.

inserted into pilot bracket.

 

 

2. One of the wall switch wires may be grounded.

 

 

Remove wall switch wires from valveterminals if

 

 

pilot now stays lit, trace wall switch wiring for

 

 

ground. May be grounded to fireplace or gas

 

 

supply.

 

 

3. Check thermopile with millivolt meter. Take

 

 

reading at thermopile terminals of gas valve.

 

 

Should read 250-300 millivolts (minimum 150)

 

 

while holding valve knob depressed in pilot

 

 

position and wall switch “Off”. Replace faulty

 

 

thermopile if reading is below specified minimum

 

C. Plugged burner orifice.

Check burner orifices for debris and remove.

 

D. Defective automatic valve

Turn valve knob to “On”, place wall switch to “On”

 

operator.

millivolt meter should read greater than 100 mV. If

 

 

the reading is okay and the burner does not come on,

 

 

replace the gas valve.

4. Frequent pilot outage

A. Pilot flame may be too low

Clean and/or adjust pilot flame for maximum flame

problem.

or blowing (high) causing the

impingement on thermopile and thermocouple.

 

pilot safety to drop out.

 

 

B. Possible blockage of the vent

Check the vent terminal for blockage (recycling the

 

terminal.

flue gases)

 

 

 

10003848

25

Image 25
Contents Homeowner’s Installation Operating Manual Table of Contents National Fuel Gas Code Ansi Z223.1/NFPA Installation & Operating InstructionsFraming Dimensions Fireplace Dimensions Installed as Top VentDvrtsb Top Vent Dvrtsb Rear Vent Fireplace Dimensions Installed as Rear VentClearance to Combustibles Locating Your FireplaceMantels HearthFinal Finishing Gas Line InstallationGas Specifications Gas Inlet and Manifold PressuresAlternate Switch Location Remote ON/OFF Switch InstallationEB-1 Electrical Box Remove flue cover and flue pipe Optional Top Vent ApplicationLocation of Vent Termination General Venting Information Termination LocationTermination location requirements Canadian Installations1 US Installations2Canadian Installations General Information for Connecting Vent PipesUSA Installations Twist Lock PipesRear Wall Vent Installation How to Use the Vent GraphRear Wall Vent Applications Example aZero clearance sleeve is only required for combustible walls Vertical Sidewall ApplicationsMaximum vent run with elbows Vertical Sidewall InstallationHorizontal length requirement Always install horizontal venting on a level planeVertical Through-the-Roof Applications Below Grade InstallationEnlarged ends of the vent section always face downward Vertical Through-The-Roof InstallationAttic Insulation Shield Upper Floor Twist Lock Venting Components Louvre Removal Glass InformationGlass/Frame Removal Side Glass FrameCeramic Refractory Installation Glass CleaningInstallation of Logs Clean the glass after the first two weeks of operationLava Rock & Ember Material Flame Characteristics Flame & Temperature AdjustmentCeramic Ember Rocks Pt. # RN/RP ModelsTo Turn Off Gas To Heater Lighting and Operating InstructionsTroubleshooting the Gas Control System Honeywell Millivolt Valve SIT top Convertible Pilot Fuel Conversion InstructionsPSE Pilot SIT 820 Nova Gas Control Valve FigBurner and Burner Compartment Cleaning the Standing Pilot Control SystemBrass Trim OFF DescriptionDvrtsb Dvrtsb Bay Window Fireplace Fan Kits ON/OFF and Temperature Remote ControlsModel Function/s Controlled Wall mounted thermostat controlDvrtsb Bay Window Fireplace Limited Lifetime Warranty Efficiency Ratings