Vermont Casting DVRTSB manual Honeywell Millivolt Valve

Page 26

DVRTSB Bay Window Fireplace

 

Troubleshooting the Gas Control System

 

 

 

Honeywell Millivolt Valve

WARNING: Before doing any gas control service work, remove glass front.

START

CHECK

Gas Supply On

YES

NO

Supply Line Hooked Up

Shutoff Valve Open

Pilot Lights With Piezo Ignitor

YES

Pilot Stays Lit

YES

Pilot Lights Main Burner

YES

System OK

NO

NO

NO

Lockout Has Engaged. Wait 60 Seconds And Try Again.

For Spark At Electrode While Depressing Piezo

1/8" Gap To Pilot Hood Needed.

All Wiring Connections

Replace Piezo Ignitor

For Air In The Lines

Thermopile Needs A Min. 325mv. Adjust Pilot Flame Height.

All Wiring Connections

Replace Thermopile

Thermocouple Needs A Min. Of 14mv

Valve Is Turned On

Wall Switch Is Not Turned On. Watch For Grounded Wires!

Thermopile Needs A Min. 325mv.

Plugged Burner Orifice

Defective Valve. Turn To Pilot, Meter Should Read Greater Than 100mv. If Not, Replace.

26

10003848

Image 26
Contents Homeowner’s Installation Operating Manual Table of Contents Installation & Operating Instructions National Fuel Gas Code Ansi Z223.1/NFPADvrtsb Top Vent Fireplace Dimensions Installed as Top VentFraming Dimensions Fireplace Dimensions Installed as Rear Vent Dvrtsb Rear VentMantels Locating Your FireplaceClearance to Combustibles HearthGas Specifications Gas Line InstallationFinal Finishing Gas Inlet and Manifold PressuresEB-1 Electrical Box Remote ON/OFF Switch InstallationAlternate Switch Location Optional Top Vent Application Remove flue cover and flue pipeGeneral Venting Information Termination Location Location of Vent TerminationCanadian Installations1 US Installations2 Termination location requirementsUSA Installations General Information for Connecting Vent PipesCanadian Installations Twist Lock PipesRear Wall Vent Applications How to Use the Vent GraphRear Wall Vent Installation Example aVertical Sidewall Applications Zero clearance sleeve is only required for combustible wallsVertical Sidewall Installation Maximum vent run with elbowsAlways install horizontal venting on a level plane Horizontal length requirementBelow Grade Installation Vertical Through-the-Roof ApplicationsVertical Through-The-Roof Installation Enlarged ends of the vent section always face downwardAttic Insulation Shield Upper Floor Twist Lock Venting Components Glass/Frame Removal Glass InformationLouvre Removal Side Glass FrameInstallation of Logs Glass CleaningCeramic Refractory Installation Clean the glass after the first two weeks of operationCeramic Ember Rocks Pt. # Flame Characteristics Flame & Temperature AdjustmentLava Rock & Ember Material RN/RP ModelsLighting and Operating Instructions To Turn Off Gas To HeaterTroubleshooting the Gas Control System Honeywell Millivolt Valve PSE Pilot Fuel Conversion InstructionsSIT top Convertible Pilot SIT 820 Nova Gas Control Valve FigBrass Trim Cleaning the Standing Pilot Control SystemBurner and Burner Compartment Description OFFDvrtsb Dvrtsb Bay Window Fireplace Fan Kits Model Function/s Controlled Remote ControlsON/OFF and Temperature Wall mounted thermostat controlDvrtsb Bay Window Fireplace Limited Lifetime Warranty Efficiency Ratings