Waterford Appliances E65-LP1, E65-NG1 GAS Pipe Pressure Testing, Valve Description

Page 25

INSTALLATION

GAS PIPE

PRESSURE TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.

The manifold pressure is controlled by a regu- lator built into the gas control, and should be checked at the pressure test point.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

1)Make sure the valve is in the "OFF" position.

2)Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a 1/8" wide flat screwdriver.

3)Attach manometer to "IN" and/or "OUT" pres- sure tap(s) using a 5/16" ID hose.

4)Light the pilot and turn the valve to "ON" position. Read manometer.

5)The pressure check should be carried out with the unit burning and the setting should be within the limits specified on the safety label.

6)When finished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" flat screwdriver. Note: Screw should be snug, but do not over tighten

Valve Description

1)Gas cock knob

2)Manual high/low adjustment

3)Pilot Adjustment

4)Thermocouple Connection

5)Main Operator

6)Outlet Pressure Tap (Manifold Pressure)

7)Inlet Pressure Tap (Supply Pressure)

8)Pilot Outlet

9)Main Gas Outlet

10)Flange Securing Screw Holes

11)Alternative TC Connection Point

12)Thermoelectric Unit

13)Additional Valve Mounting Hole

CONVERSION KIT FROM NATURAL GAS TO PROPANE

Model #261-969

for Emerald Gas Stoves and Gas Inserts using SIT 820 NOVA Gas Valve

THIS CONVERSION MUST BE DONE BY A

QUALIFIED GAS

FITTER IF IN DOUBT DO NOT DO THIS

CONVERSION !!

Conversion Kit Contains:

Qty.

Part # Description

1910-018 SIT Conversion Kit-50% Turndown LP

1

910-037

LP Injector (Pilot Orifice)

1

904-641

Burner Orifice #50

1908-175 E63/E65 Decal "Converted to Propane"

1908-528 Red "PROPANE" label

1908-780 Instruction Sheet

1)Shut off the gas supply.

2)Open the valve door and remove the control panel.

3)Open the front door. Open the right side door and there is a cutout in the heat shield through which can be seen a wing nut threaded on to a stud attached to the front door. Loosen this nut by turning it counter- clockwise.

4)Carefully remove the logs, embers and rockwool.

5)Remove burner. See diagram below.

Note: Use a magnetic type screwdriver if possible.

Pilot assembly is now accessible

for steps 6) to 11).

Waterford E65-1 Emerald Direct Vent Freestanding Gas Stove

25

Image 25
Contents Models E65-NG1 Natural Gas Emerald Direct Vent Freestanding Gas StoveWaterford Unit SpecificationsTo the New Owner Table of Contents Copy of Safety Label for E65-NG1 Natural Gas Stove Safety LabelCopy of Safety Label for E65-LP1 Propane Stove Specifications InstallationSave These Instructions Information for MobileInstallation Checklist General Safety InformationClearances to Combustibles Manufactured Mobile Home Additional Requirements Locating Your Optional FAN Installation Emerald GAS StoveCombustion and Ventilation AIR Introduction Precautions InstallationSafety Precautions for the Installer Ance adapterExterior Vent Terminal Locations 4DT-AJB Rigid Pipe Venting Components ListHorizontal Venting Rigid Pipe Venting Horizontal TerminationsVenting Arrangements Examples Offset to Vertical Terminations Straight Vertical TerminationsVent Restrictor #1 Required Parts Vertical Termination with CO-LINEAR Flex SystemDescription Alternate Approved CapsMinimum components for a Horizontal Installa- tion Miniumum Horizontal Termination InstallationsDV Stove Horizontal Vent KIT Optional ComponentsInstallation DURA-VENT Termination KIT Planning Your Dura-Vent InstallationAlternate Horizontal Termination Caps Minimum components for a Dura-Vent Horizontal InstallationMinimum components for a Dura-Vent Vertical Termination Dura-Vent Basic Horizontal Kit #Below Grade Snorkel Installation DURA-VENT Horizontal InstallationsSnorkel Terminations # 942 over the vent pipe DURA-VENT Vertical TerminationCathedral Ceilings Offset ChartRound Support RDS Square Support SQS Support Extensions Round Rdse or Square Sqse Prior to installation and connectionGeneral Converting a Factory Built Metal ChimneyConverting a Masonry Chimney High Elevation Aeration AdjustmentGAS Connection With 38,000 BTUConversion KIT from Natural GAS to Propane GAS Pipe Pressure TestingValve Description Natural Gas Conversion Kit 260-920 Contains Reduction KIT to Lower BTU Rating for E65-1 GAS StovePropane Conversion Kit 260-922 Contains Optional Door Grill Installation LOG InstallationDoor Grill Kit Contains Optional Wall Thermostat Optional Remote ControlFinal Check Lighting Procedure Wiring Diagram E65-NG1 & E65-LP1Operating Instructions Operating InstructionsFirst Fire Shutdown ProcedureCopy of the Lighting Plate instructions Adjusting Flame Height MaintenanceMaintenance Instructions Automatic Convection FAN OperationLOG Replacement General Vent MaintenanceGlass Replacement FAN MaintenanceTo remove valve from valve assembly, continue Installing Valve AssemblyRemoving Valve To remove fanMain Assembly Parts ListBurner & LOG Assembly Waterford E65-1 Emerald Direct Vent Freestanding Gas Stove Waterford E65-1 Emerald Direct Vent Freestanding Gas Stove Page Conditions WarrantyRegister your Waterford online at