Regency L676S-NG1 installation manual Clearances

Page 9

INSTALLATION

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:

A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

INSTALLATION

Caution Requirements

The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoff may NOT be

recessed into combustible construction.

Clearance to Combustibles from:

Back0" (0mm)

Side0" (0mm)

Floor0" (0mm)

Minimum Clearance from Top of Front Facing:

Mantel

min. 16-1/2"

(419mm)

Ceiling

52"

(813mm) from top of front facing

Side Wall to Unit:

14-3/4"* (375mm)

Horizontal Vent Clearances to Combustibles:

Top

3"

(76mm)

Side

2"

(51mm)

Bottom

2"

(51 mm)

Vertical Vent Clearances to Combustibles:

All Sides

2"

(51mm)

Alcove Clearances:

Min. Depth

36"

(914mm)

Min. Width*

84"

(2134mm)

Min. Height

84"

(2032mm)

(1321mm)

ceiling

 

52”

to

 

 

“NON-COMBUSTIBLE FACING”

 

 

(713mm)

14-3/4”

1/16”

(375mm)

 

 

-

 

28

 

3”

(76mm)

NOTE: Only materials such as, but not limited to durarock, wonderboard and concrete board may be put on the front face of this appliance. See specific requirements under "Framing and Finishing" section.

* Alcove side wall must have a minimum of 14-3/4" (375mm) clearance on one side.

IMPORTANT: One set of inner panels must be installed (see P 32). The operation of this unit without inner panels is prohibited.

WARNING

 

IMPORTANT

Fire hazard is an extreme risk

 

If converting this unit to LP, it is highly recommened

if these clearances (air space) to combustible materials

 

 

the conversion be done BEFORE the unit is slid into

are not adhered to. It is of greatest importance that this

 

 

position for ease of conversion. See "Conversion

fireplace and vent system be installed only in

 

accordance with these instructions.

 

from NG to LP" section for instructions.

 

 

 

 

 

 

Regency® L676S Direct Vent Gas Fireplace

9

Image 9
Contents L676 Sunrise Gas Fireplace Information for MOBILE/MANUFACTURED Homes After First Sale Manufactured Mobile Home RequirementsTable of Contents Copy of Safety Decal Safety LabelSerial No. / No de serie Factory Equipped For Altitude 0-4500ft -1372mFor the State of Massachusetts only Requirements Unit Dimensions General Safety Information InstallationInstallation Checklist Important Message Save These InstructionsHeat Release KIT Manufactured Mobile Home Additional RequirementsFinished Floor Locating Your GAS FireplaceClearances Mantel LEG Clearances Mantel ClearancesFraming Installed. See Diagram 3 for detailsImportant Header must be metal stud. All other framing may FramingFinishing Non-combustibleMaterial + 3/4 + 3/8Unit Assembly Prior to Installation Finishing TemplateVenting Introduction Vent Restrictor Position No adjustment requiredVent Restrictor Plate Latch Latch Location HingeDoorExterior Vent Termination Requirements Minimum Clearance RequirementsCanada1 Horizontal Termination Flex Venting ArrangementsBasic Horizontal & Vertical Terminations Rigid Pipe Venting Systems8 Rigid Pipe Cross Reference Chart Installation Allowable Horizontal Terminations Vent Restrictor On SetVertical Vent Restrictor On Set Option + V1 H + H1 Option + H1+ H1 V + V1 With these options, max. total OptionAllowable Vertical Terminations Unit Installation with Horizontal Termination This allows for small adjustments Unit Installation With Vertical TerminationDiagram Minimum VentAstrocap XL Unit InstallationGAS Line Installation Pilot AdjustmentGAS Pipe Pressure Testing High ElevationWiring Diagram Aeration AdjustmentMinimum Air Shutter Opening OptionalLP Conversion Kit Contains Qty Description Conversion KIT #526-969 from NG to LPLeaks Stainless Steel Panels Black Enamel Panels Panel InstallationFirebox base Slots on fl oor of fi rebox baseHoles on bottom Panel Left panelUse this hole on panel clip Spread the supplied Glass Crystals or optional Ceramic Spa Adjustment for fi nishing materials Faceplate & Door Frame InstallationLevel adjustment Location of mounting bracketsOperating Instructions Normal Operating Sounds GAS Appliances For Your Safety Read Before LightingCopy of Lighting Plate Instructions Lighting InstructionsMaintenance DC Spark BOX Replacement DC Spark BOX Battery ReplacementDC Spark Box Wires DC Spark Box LocationValve Tray Replacement Door Hinge with door removedSlots for back panel DC Spark Box Electrode Wire Disconnect 2 wiresLocation of Screws Disconnect 2 generator wires Valve Tray OutMain Assembly Parts ListHeat Wave Kit Release Kit Burner Assembly Regency L676S Direct Vent Gas Fireplace Regency L676S Direct Vent Gas Fireplace Conditions WarrantyInstaller Please complete the following information