Regency L676S-NG1 installation manual Pilot Adjustment, High Elevation, GAS Line Installation

Page 28

INSTALLATION

INSTALLATION

 

 

L676S-NG1 SYSTEM DATA

Note: To properly check gas pressure, both

 

inlet and manifold pressures should

Min. Supply Pressure

5" WC (1.25 kpa)

 

be checked using the valve pressure

Low Setting Man.

1.6" WC (0.39 kpa)

 

ports on the valve.

 

 

Pressure

 

1) Make sure the valve is in the "OFF"

Max. Manifold

3.5" WC (0.87 kpa)

 

position.

Pressure

 

2) Loosen the "IN" and/or "OUT" pressure tap(s),

Orifice Size

#37 DMS

 

turning counterclockwise with a

Minimum Input

19,500 Btu/h

 

 

1/8" wide flat screwdriver.

 

(5.71 kW)

 

 

Maximum Input

29,000 Btu/h

3)

Attach manometer to "IN" and/or "OUT"

 

pressure tap(s) using a 5/16" ID hose.

 

(8.49 kW)

 

L676S-LP1 SYSTEM DATA

4)

Light the pilot and turn the valve to "ON"

Min. Supply Pressure

12" WC (2.98 kpa)

 

position.

 

 

Low Setting Man.

6.4" WC (1.59 kpa)

5)

The pressure check should be carried out

Pressure

 

 

with the unit burning and the setting should

Max. Manifold

10" WC (2.49 kpa)

 

be within the limits specified on the safety

Pressure

 

 

label.

Orifice Size

#53 DMS

6) When finished reading manometer, turn off the

Minimum Input

21,000 Btu/h

PILOT ADJUSTMENT

gas valve, disconnect the hose and tighten the

 

(6.15 kW)

 

screw (clockwise) with a 1/8" flat screwdriver.

Maxiumm Input

26,000 Btu/h

 

Note: Screw should be snug, but do not

 

over tighten.

 

(7.61 kW)

 

 

 

 

HIGH ELEVATION

This unit is approved in Canada for altitude 0 to 4500 ft. (CAN1 2.17-M91).

GAS LINE

INSTALLATION

Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA B149 installation code.

For USA installations follow local codes and/ or the current National Fuel Gas Code, ANSI Z223.1.

When using copper or flex connectors use only approved fittings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and flex connectors are usually considered to meet this requirement.

IMPORTANT: Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.

Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).

Note: If you have an incorrect flame pattern, contact your Regency® dealer for further instructions.

Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.

The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.

SIT 820 VALVE DESCRIPTION

1)Gas on/off knob

2)Manual High/Low Adjustment

3)Pilot Adjustment

4)Thermocouple Connection - option

5)Outlet Pressure Tap

6)Inlet Pressure Tap

7)Pilot Outlet

8)Main Gas Outlet

9)Alternative TC Connection Point

28

Regency® L676S Direct Vent Gas Fireplace

Image 28
Contents L676 Sunrise Gas Fireplace Manufactured Mobile Home Requirements Information for MOBILE/MANUFACTURED Homes After First SaleTable of Contents Safety Label Copy of Safety DecalSerial No. / No de serie Factory Equipped For Altitude 0-4500ft -1372mRequirements For the State of Massachusetts onlyUnit Dimensions Installation General Safety InformationInstallation Checklist Important Message Save These InstructionsManufactured Mobile Home Additional Requirements Heat Release KITFinished Floor Locating Your GAS FireplaceClearances Mantel Clearances Mantel LEG ClearancesInstalled. See Diagram 3 for details FramingImportant Header must be metal stud. All other framing may FramingNon-combustible FinishingMaterial + 3/8 + 3/4Finishing Template Unit Assembly Prior to InstallationVenting Introduction No adjustment required Vent Restrictor PositionVent Restrictor Plate Latch Latch Location HingeDoorMinimum Clearance Requirements Exterior Vent Termination RequirementsCanada1 Venting Arrangements Horizontal Termination FlexRigid Pipe Venting Systems Basic Horizontal & Vertical Terminations8 Rigid Pipe Cross Reference Chart Installation Vent Restrictor On Set Allowable Horizontal TerminationsVertical Vent Restrictor On Set Option + H1 Option + V1 H + H1Option + H1 V + V1 With these options, max. totalAllowable Vertical Terminations Unit Installation with Horizontal Termination Unit Installation With Vertical Termination This allows for small adjustmentsDiagram Minimum VentUnit Installation Astrocap XLPilot Adjustment GAS Line InstallationGAS Pipe Pressure Testing High ElevationAeration Adjustment Wiring DiagramMinimum Air Shutter Opening OptionalConversion KIT #526-969 from NG to LP LP Conversion Kit Contains Qty DescriptionLeaks Panel Installation Stainless Steel Panels Black Enamel PanelsFirebox base Slots on fl oor of fi rebox baseLeft panel Holes on bottom PanelUse this hole on panel clip Spread the supplied Glass Crystals or optional Ceramic Spa Faceplate & Door Frame Installation Adjustment for fi nishing materialsLevel adjustment Location of mounting bracketsOperating Instructions For Your Safety Read Before Lighting Normal Operating Sounds GAS AppliancesCopy of Lighting Plate Instructions Lighting InstructionsMaintenance DC Spark BOX Battery Replacement DC Spark BOX ReplacementDC Spark Box Wires DC Spark Box LocationDoor Hinge with door removed Valve Tray ReplacementSlots for back panel Disconnect 2 wires DC Spark Box Electrode WireLocation of Screws Disconnect 2 generator wires Valve Tray OutParts List Main AssemblyHeat Wave Kit Release Kit Burner Assembly Regency L676S Direct Vent Gas Fireplace Regency L676S Direct Vent Gas Fireplace Warranty ConditionsInstaller Please complete the following information