INSTALLATION
INSTALLATION |
|
| ||
| Note: To properly check gas pressure, both | |||
| inlet and manifold pressures should | |||
Min. Supply Pressure | 5" WC (1.25 kpa) |
| be checked using the valve pressure | |
Low Setting Man. | 1.6" WC (0.39 kpa) |
| ports on the valve. | |
|
| |||
Pressure |
| 1) Make sure the valve is in the "OFF" | ||
Max. Manifold | 3.5" WC (0.87 kpa) | |||
| position. | |||
Pressure |
| 2) Loosen the "IN" and/or "OUT" pressure tap(s), | ||
Orifice Size | #37 DMS | |||
| turning counterclockwise with a | |||
Minimum Input | 19,500 Btu/h |
| ||
| 1/8" wide flat screwdriver. | |||
| (5.71 kW) |
|
| |
Maximum Input | 29,000 Btu/h | 3) | Attach manometer to "IN" and/or "OUT" | |
| pressure tap(s) using a 5/16" ID hose. | |||
| (8.49 kW) |
| ||
| 4) | Light the pilot and turn the valve to "ON" | ||
Min. Supply Pressure | 12" WC (2.98 kpa) |
| position. | |
|
| |||
Low Setting Man. | 6.4" WC (1.59 kpa) | 5) | The pressure check should be carried out | |
Pressure |
|
| with the unit burning and the setting should | |
Max. Manifold | 10" WC (2.49 kpa) |
| be within the limits specified on the safety | |
Pressure |
|
| label. | |
Orifice Size | #53 DMS | 6) When finished reading manometer, turn off the | ||
Minimum Input | 21,000 Btu/h | PILOT ADJUSTMENT | gas valve, disconnect the hose and tighten the | |
| (6.15 kW) |
| screw (clockwise) with a 1/8" flat screwdriver. | |
Maxiumm Input | 26,000 Btu/h |
| Note: Screw should be snug, but do not | |
| over tighten. | |||
| (7.61 kW) |
| ||
|
|
|
HIGH ELEVATION
This unit is approved in Canada for altitude 0 to 4500 ft. (CAN1
GAS LINE
INSTALLATION
Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA B149 installation code.
For USA installations follow local codes and/ or the current National Fuel Gas Code, ANSI Z223.1.
When using copper or flex connectors use only approved fittings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and flex connectors are usually considered to meet this requirement.
IMPORTANT: Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.
Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).
Note: If you have an incorrect flame pattern, contact your Regency® dealer for further instructions.
Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual
The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.
SIT 820 VALVE DESCRIPTION
1)Gas on/off knob
2)Manual High/Low Adjustment
3)Pilot Adjustment
4)Thermocouple Connection - option
5)Outlet Pressure Tap
6)Inlet Pressure Tap
7)Pilot Outlet
8)Main Gas Outlet
9)Alternative TC Connection Point
28 | Regency® L676S Direct Vent Gas Fireplace |