Burnham 8H manual III. Gas Control System Assembly Knockdown Boilers

Page 15

III. Gas Control System Assembly (Knockdown Boilers)

A.24V Standing Pilot Control System

Install Gas Control System. All components are located in Combination Boiler Parts and Control Carton.

1.Install Gas Control Assembly on Manifold. See Figure 10. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.

2.Install pilot burner piping and controls. See Figure 10.

3.Connect Thermocouple Lead to Gas Valve.

4.Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.

a.Canada only - loop 4” nylon cable tie between junction box and transformer/control center.

b.Attach transformer/control center to junction box.

B.EI (Intermittent Ignition)

Install Gas Control System. All components are located in Combination Boiler Parts and Control Carton.

1.Install Gas Control Assembly on Manifold. See Figure 11. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.

2.Install pilot burner piping and controls.

a.Honeywell EI

i.USA - See Figure 12.

ii.Canada - See Figure 13.

3.Install Ignition Module.

a.Attach Ignition Control Mounting Bracket to Jacket Vestibule Panel using two (2) #8 x ½” sheet metal screws.

b.Attach Honeywell Ignition Module to Mounting Bracket using two (2) #8 x ½” sheet metal screws.

c.Connect pilot ground wire and ignitor/sensor lead(s) to ignition module. Refer to “Section VII: Electrical” for connection details.

4.Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box. See Figure 8.

a.Canada only - loop 4” nylon cable tie between junction box and transformer/control center.

b.Attach transformer/control center to junction box.

C.OP Control System

Install Gas Control System. All components are located in Combination Boiler Parts and Control Carton.

1.Install Gas Control Assembly on Manifold. See Figure 14. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.

2.Install pilot burner piping and controls. See Figure 14.

3.Connect Thermocouple Lead to Gas Valve.

4.Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.

a.Canada only - loop 4” nylon cable tie between junction box and transformer/control center.

b.Attach transformer/control center to junction box.

D.OP-CSD-1 Control System

Install Gas Control System. All components are located in Combination Boiler Parts and Control Carton.

1.Install Gas Control Assembly on Manifold. See Figure 15. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.

2.Mount pilot switch.

3.Install pilot burner piping and controls. See Figure 15.

4.Connect Thermocouple lead to pilot switch.

5.Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.

6.Attach transformer/control center to junction box.

E.EP Control System

Install Gas Control System. All components are located in Combination Boiler Parts and Control Carton.

1.Install Gas Control Assembly on Manifold. See Figure 16.

2.Install pilot burner piping and controls. See Figure 16.

3.Install Ignition Transformer.

a.Attach Ignition Transformer to Jacket Vestibule Panel using four (4) #8 x ½” lg. sheet metal screws.

b.Connect Ignition Lead from Pilot to Ignition Transformer.

4.Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.

a.Canada only - loop 4” nylon cable tie between junction box and transformer/control center.

b.Attach transformer/control center to junction box.

15

Image 15
Contents 81416021R3-6/10 Price $5.00 Series 8HImportant Information Read Carefully Page Table of Contents Dimensional Data Boiler Model Special Base Part Number Pre-InstallationPage Remove Crate II. Boiler AssemblyDo not use air to leak test boiler Installation of Special Base for Combustible FlooringGeneral Assembly Knockdown Boilers Flame Roll-out Switch Installation Install Jacket. See Figure Jacket Assembly EP/OP Control Installation III. Gas Control System Assembly Knockdown Boilers Page Schematic Gas Piping, 24V Standing Pilot, 806H & 807H Main Gas Piping, Intermittent Ignition EI Schematic Pilot Piping Honeywell EI, USA Page Schematic Gas Piping, OP Control System, 806H 810H Schematic Gas Piping, OP-CSD-1 Control System, 808H 810H Page Schematic Gas Piping, EP-CSD-1 Control System, 808H 810H IV. Water Trim and Piping Flow Rate, Temperature Rise, and Pressure DropDrain Piping Installation Page Page Gas Piping Rated InputConnect boiler gas valve to gas supply system Specific Gravity Correction Factors Equivalent Lengths of Standard Pipe Fittings & ValvesVI. Venting Blocked Vent Switch InstallationBoiler Equipped With Vent Damper. See Figure Vent Damper InstallationTypical Vent System If an Existing Boiler is RemovedVII. Electrical Install Boiler WiringHeat Anticipator Settings Sequence of Operation and Wiring Diagrams Page Page Page Page Page Page Wiring Diagram, Honeywell EI, USA, Continuous Circulation Wiring Diagram, Honeywell EI, USA, Intermittent Circulation Wiring Diagram, Honeywell EI, Canada, Continuous Circulation Page Page Page Page Page Page VIII. System Start-Up Lighting Instructions 24V Standing Pilot Operating Instructions EI Lighting Instructions OP Operating Instructions EP Boiler Operating Instructions To Shut Down Honeywell Q314 Pilot Flame 24V Standing Pilot Adjust gas input rate to boiler. Natural Gas Check LimitsInput Rate Combustion Chamber Burn-Off Adjust gas input rate to boiler. LP/PropaneClean Heating System Install Front Removable PanelClean Boiler Flueways. See Figure IX. ServiceAvoid Breathing Fiber Particulates and Dust Pilot Burner Location Boiler Flueway CleaningHoneywell EI Ignition Module Yellow LED Flame Codes OFF Honeywell EI Ignition Module Green LED Status CodesHoneywell EI Trouble Shooting Guide Repair Parts Heat Exchanger Assembly Canopy Base Assembly Manifold and Main Burners Description Size Quantity Description Quantity Gas Valve, Robertshaw 7000DERHC, Natural Gas, 1 NPT 81660151 Solenoid Gas Valve, Honeywell V8295A1024, ¾ NPT 81660235 Description Quantity Natural Gas Only Pilot Burner, Honeywell Q348A1002, Natural Gas Pilot Burner, Honeywell Q348A1010, LP Gas 8236081 Pipe Tee, 1/8 NPT, Malleable 806601005 Description Size Quantity Brass Compression Coupling, 1/4 OD Tube 8236008 Description Size Quantity Page Jacket Jacket Front Removable Panel Trim and Miscellaneous Controls Draft Hood and Automatic Vent Damper Service Record Service Record Service Record