CURBS & WEIGHTS DIMENSIONS - 580J*04-07 (cont.)

580J

C

B

C08599

Fig. 2 - Dimensions 580J 04-07

D

A

 

 

C08337

 

Fig. 3 - Service Clearance

 

 

 

 

LOC

DIMENSION

CONDITION

 

48--- in (1219 mm)

Unit disconnect is mounted on panel

A

18--- in (457 mm)

No disconnect, convenience outlet option

18--- in (457 mm)

Recommended service clearance

 

 

12--- in (305 mm)

Minimum clearance

 

 

 

 

42--- in (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall)

B

36--- in (914 mm)

Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)

 

Special

Check for sources of flue products within 10--- ft of unit fresh air intake hood

 

 

 

C

36--- in (914 mm)

Side condensate drain is used

18--- in (457 mm)

Minimum clearance

 

 

 

 

 

48--- in (1219 mm)

No flue discharge accessory installed, surface is combustible material

D

42--- in (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)

36--- in (914 mm)

Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)

 

 

Special

Check for adjacent units or building fresh air intakes within 10--- ft of this unit’s flue outlet

 

 

 

18

Image 18
Contents Product Data Table of Contents Certified to ISOFeatures and Benefits Intake/Exhaust Options Voltage Factory Installed OptionsUnit Type Packaging Cooling TonsEconomizers FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesCondenser Protection Economizer SensorsFactory Options AND/OR Accessories Economizer dry-bulb or enthalpyFactory Options AND/OR Accessories Motormaster Head Pressure ControllerUnit Ahri Cooling Rating TableNOM NET Cooling Seer EER Ieer StagesUnits Heating Rating Table Natural GAS & PropaneAL/SS Heat Exchanger Temp Rise Thermal Afue EfficiencySound Performance Table Stages WeightedHeating Rating Table LOW NOx1 Unit CoolingMinimum Maximum Airflow Ratings Natural GAS & Propane Cooling Heating MinimumMinimum Maximum Physical Data TonsNatural Gas, Propane Heat Heat Anticipator Setting Amps580J*04 580J*05 580J*06 580J*07 Gas Connection Low NOx Gas Heat8.5 Tons 10 12.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D12.5 Tons 580J*08 580J*09 580J*12 580J*14 Gas ConnectionCurbs & Weights Dimensions 580J*04-07 Dimensions 580JCurbs & Weights Dimensions 580J*04-07 Dimension ConditionRoof Curb Details Curbs & Weights Dimensions 580J*08-12 Curbs & Weights Dimensions 580J*08-12 580JCurbs & Weights Dimensions 580J*08-14 Curbs & Weights Dimensions 580J Dimensions 580J-14Curbs & Weights Dimensions 580J 14 Options & Accessory Weights Option / Accessory WeightsApplication Data Min operating ambient temp coolingApplication Data Sizing a rooftopSelection Procedure with 580J*07A EXAMPLE1 Rtpf Ambient TemperatureCooling Capacities SHCEdb 900 1200 15001050 1200 1350 Ewb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 1800 580J*07A 105 115EAT db 21002100 2400 2700 2100 2400 2700 1750 2000580J*08A 105 115 580J*08D 105 115 Rtpf & Novation EA db2250/0.05 3000/0.07 3750/0.09 Condenser Edb Cooling Capacities 2-STAGE Cooling Rtpf only TonsTemp F AIR ENT 2250 3000 3750580J*09A 105 115 580J*09D 105 115 2550/0.04 3400/0.05 4250/0.07 Condenser Edb 2550 3400 4250580J*12A 105 115 580J*12D 105 115 Rtpf & Novation Cooling Capacities 2-STAGE Cooling Rtpf only 3000/0.04 4000/0.06 5000/0.07 Condenser Edb3000 4000 5000 580J*14D 105 115 Rtpf & Novation CONDENSEREdb 3750/0.02 5000/0.06 6250/0.05 Condenser EdbTemp Fair ENT 3750 5000 6250Static Pressure Adders Factory Options and/or Accessories 12.5 TonsTons FAN Performance 580J*04CFM RPM BHP FAN Performance Medium Static Option High Static Option1201 580J*051177 1213 1268 13211493 15061486 580J*06 Medium Static Option Field---Supplied Drive11482 1696 1752 17191713 1736580J*07 580J*08 580J*09 580J*12 579580J*14 Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboECONOMIZER, Barometric Relief and PE Performance 2000 1000580J*05A Stage Cooling Electrical Information580J*04A Stage Cooling 580J*06A Stage Cooling580J*08A Stage Cooling Tons Electrical Information580J*07A Stage Cooling 580J*08D Stage Cooling Tons580J*09A Stage Cooling Tons 580J*09D Stage Cooling Tons580J*12A Stage Cooling 580J*12D Stage Cooling 580J*14D Stage Cooling TonsRLA LRA MCA/MOCP Determination no C.O. or Unpwrd C.O Unit Combustion Power NOM IFM FAN Motor Exhaust No P.EUnbalanced 3-Phase Supply Voltage MCA Mocp MCA/MOCP Determination W/ Pwrd C.OPwrd C.O Mocp FLA LRACont. MCA/MOCP Determination W/ Pwrd C.O Typical Wiring Diagrams Stage Cooling Typical Power DiagramTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Sequence of Operation CoolingHeating Sequence of Operation Optional Perfect Humidity Dehumidification SystemSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 23 07 16 Hvac Equipment Insulation Guide Specifications 580J*04-14Gas Heat/Electric Cooling Packaged Rooftop 23 09 13 Instrumentation and Control Devices for Hvac23 40 13 Panel Air Filters 23 09 33 Electric and Electronic Control System for Hvac23 09 93 Sequence of Operations for Hvac Controls 23 81 19 Self-Contained Air Conditioners580J 580J 580J 580J 580J 580J Catalog No. PDS580J