Bryant 580J manual

Page 80

580J

2.Factory assembled, single-piece heating and cooling rooftop unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, and special features required prior to field start-up.

3.Unit shall use environmentally sound, Puron refrigerant.

4.Unit shall be installed in accordance with the manufacturer’s instructions.

5.Unit must be selected and installed in compliance with local, state, and federal codes.

23 81 19.13.B. Quality Assurance

1.Unit meets ASHRAE 90.1 minimum efficiency requirements.

2.Unit shall be rated in accordance with AHRI Standards 210/240 and 340/360.

3.Unit shall be designed to conform to ASHRAE 15, 2001.

4.Unit shall be UL-tested and certified in accordance with ANSI Z21.47 Standards and UL-listed and certified under Canadian standards as a total package for safety requirements.

5.Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.

6.Unit casing shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen).

7.Unit casing shall be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 5000-hour salt spray.

8.Unit shall be designed in accordance with ISO 9001:2008, and shall be manufactured in a facility registered by ISO 9001:2008.

9.Roof curb shall be designed to conform to NRCA Standards.

10.Unit shall be subjected to a completely automated run test on the assembly line. The data for each unit will be stored at the factory, and must be available upon request.

11.Unit shall be designed in accordance with UL Standard 1995, including tested to withstand rain.

12.Unit shall be constructed to prevent intrusion of snow and tested to prevent snow intrusion into the control box up to 40 mph.

13.Unit shake tested to assurance level 1, ASTM D4169 to ensure shipping reliability.

23 81 19.13.C. Delivery, Storage, and Handling

1.Unit shall be stored and handled per manufacturer’s recommendations.

2.Lifted by crane requires either shipping top panel or spreader bars.

3.Unit shall only be stored or positioned in the upright position.

23 81 19.13.E. Project Conditions

1. As specified in the contract.

23 81 19.13.F. Operating Characteristics

1.Unit shall be capable of starting and running at 115_F (46_C) ambient outdoor temperature, meeting maximum load criteria of AHRI Standard 210/240 or 340/360 at ± 10% voltage.

2.Compressor with standard controls shall be capable of operation down to 40_F (4_C), ambient outdoor temperat- ures. Accessory winter start kit is necessary if mechanically cooling at ambient temperatures down to 25_F (-4_C).

3.Unit shall discharge supply air vertically or horizontally as shown on contract drawings.

4.Unit shall be factory configured for vertical supply & return configurations.

5.Unit shall be field convertible from vertical to horizontal configuration without the use of special conversion kits.

6.Unit shall be capable of mixed operation: vertical supply with horizontal return or horizontal supply with vertical return.

23 81 19.13.G. Electrical Requirements

1.Main power supply voltage, phase, and frequency must match those required by the manufacturer. 23 81 19.13.H. Unit Cabinet

1.Unit cabinet shall be constructed of galvanized steel, and shall be bonderized and coated with a prepainted baked enamel finish on all externally exposed surfaces.

2.Unit cabinet exterior paint shall be: film thickness, (dry) 0.003 inches minimum, gloss (per ASTM D523, 60_F /

16_C): 60, Hardness: H-2H Pencil hardness.

3.Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standards 210/240 or 340/360 minimum exterior sweat criteria. Interior surfaces shall be insulated with a minimum 1/2-in. thick, 1 lb density, flexible fiberglass insulation, neoprene coated on the air side. Aluminum foil-faced fiberglass insulation shall be used in the gas heat compartment.

4.Base of unit shall have a minimum of four locations for thru-the-base gas and electrical connections (factory installed or field installed), standard.

80

Image 80
Contents Product Data Table of Contents Certified to ISOFeatures and Benefits Voltage Factory Installed Options Unit Type PackagingIntake/Exhaust Options Cooling TonsFACTORY-INSTALLED Options and FIELD-INSTALLED Accessories Condenser ProtectionEconomizers Economizer SensorsFactory Options AND/OR Accessories Economizer dry-bulb or enthalpyFactory Options AND/OR Accessories Motormaster Head Pressure ControllerAhri Cooling Rating Table NOM NET CoolingUnit Seer EER Ieer StagesHeating Rating Table Natural GAS & Propane AL/SS Heat Exchanger Temp Rise Thermal AfueUnits EfficiencyStages Weighted Heating Rating Table LOW NOx1Sound Performance Table Unit CoolingMinimum Maximum Minimum Maximum Airflow Ratings Natural GAS & PropaneCooling Heating Minimum Physical Data TonsHeat Anticipator Setting Amps 580J*04 580J*05 580J*06 580J*07 Gas ConnectionNatural Gas, Propane Heat Low NOx Gas Heat8.5 Tons 10 12.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D12.5 Tons 580J*08 580J*09 580J*12 580J*14 Gas ConnectionCurbs & Weights Dimensions 580J*04-07 Dimensions 580JCurbs & Weights Dimensions 580J*04-07 Dimension ConditionRoof Curb Details Curbs & Weights Dimensions 580J*08-12 Curbs & Weights Dimensions 580J*08-12 580JCurbs & Weights Dimensions 580J*08-14 Curbs & Weights Dimensions 580J Dimensions 580J-14Curbs & Weights Dimensions 580J 14 Options & Accessory Weights Option / Accessory WeightsApplication Data Min operating ambient temp coolingApplication Data Sizing a rooftopSelection Procedure with 580J*07A EXAMPLE1 Ambient Temperature Cooling CapacitiesRtpf SHC900 1200 1500 1050 1200 1350Edb Ewb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 580J*07A 105 115 EAT db1800 21002100 2400 2700 2100 2400 2700 1750 2000580J*08A 105 115 580J*08D 105 115 Rtpf & Novation EA dbCooling Capacities 2-STAGE Cooling Rtpf only Tons Temp F AIR ENT2250/0.05 3000/0.07 3750/0.09 Condenser Edb 2250 3000 3750580J*09A 105 115 580J*09D 105 115 2550/0.04 3400/0.05 4250/0.07 Condenser Edb 2550 3400 4250580J*12A 105 115 580J*12D 105 115 Rtpf & Novation 3000 4000 5000 Cooling Capacities 2-STAGE Cooling Rtpf only3000/0.04 4000/0.06 5000/0.07 Condenser Edb 580J*14D 105 115 Rtpf & Novation 3750/0.02 5000/0.06 6250/0.05 Condenser Edb Temp Fair ENTCONDENSEREdb 3750 5000 6250Tons Static Pressure Adders Factory Options and/or Accessories12.5 Tons CFM RPM BHP FAN Performance580J*04 FAN Performance Medium Static Option High Static Option580J*05 11771201 1213 1268 13211486 14931506 1482 580J*06Medium Static Option Field---Supplied Drive1 1719 17131696 1752 1736580J*07 580J*08 580J*09 580J*12 579580J*14 Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboECONOMIZER, Barometric Relief and PE Performance 2000 1000Electrical Information 580J*04A Stage Cooling580J*05A Stage Cooling 580J*06A Stage CoolingElectrical Information 580J*07A Stage Cooling580J*08A Stage Cooling Tons 580J*08D Stage Cooling Tons580J*12A Stage Cooling 580J*09A Stage Cooling Tons580J*09D Stage Cooling Tons RLA LRA 580J*12D Stage Cooling580J*14D Stage Cooling Tons MCA/MOCP Determination no C.O. or Unpwrd C.O Unit Combustion Power NOM IFM FAN Motor Exhaust No P.EUnbalanced 3-Phase Supply Voltage MCA/MOCP Determination W/ Pwrd C.O Pwrd C.OMCA Mocp Mocp FLA LRACont. MCA/MOCP Determination W/ Pwrd C.O Typical Wiring Diagrams Stage Cooling Typical Power DiagramTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Heating Sequence of OperationCooling Sequence of Operation Optional Perfect Humidity Dehumidification SystemSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 Guide Specifications 580J*04-14 Gas Heat/Electric Cooling Packaged Rooftop23 07 16 Hvac Equipment Insulation 23 09 13 Instrumentation and Control Devices for Hvac23 09 33 Electric and Electronic Control System for Hvac 23 09 93 Sequence of Operations for Hvac Controls23 40 13 Panel Air Filters 23 81 19 Self-Contained Air Conditioners580J 580J 580J 580J 580J 580J Catalog No. PDS580J
Related manuals
Manual 94 pages 40.55 Kb