Bryant manual Guide Specifications 580J*04-14, Gas Heat/Electric Cooling Packaged Rooftop

Page 78

580J

GUIDE SPECIFICATIONS - 580J*04-14

Note about this specification:

Bryant wrote this specification in the 2004 version of the “Masterformat” as published by the Construction Specification Institute. Please feel free to copy this specification directly into your building spec.

Gas Heat/Electric Cooling Packaged Rooftop

HVAC Guide Specifications

Size Range:

3 to 12.5 Nominal Tons

Section

Description

23 06 80

Schedules for Decentralized HVAC Equipment

23 06 80.13 Decentralized Unitary HVAC Equipment Schedule

23 06 80.13.A. Rooftop unit schedule

1.Schedule is per the project specification requirements.

23 07 16 HVAC Equipment Insulation

23 07 16.13 Decentralized, Rooftop Units:

23 07 16.13.A. Evaporator fan compartment:

1.Interior cabinet surfaces shall be insulated with a minimum 1/2-in. thick, minimum 1 1/2 lb density, flexible fiberglass insulation bonded with a phenolic binder, neoprene coated on the air side.

2.Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.

23 07 16.13.B. Gas heat compartment:

1.Aluminum foil-faced fiberglass insulation shall be used.

2.Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.

23 09 13 Instrumentation and Control Devices for HVAC

23 09 13.23 Sensors and Transmitters

23 09 13.23.A. Thermostats

1.Thermostat must

a.energize both “W” and “G” when calling for heat.

b.have capability to energize 2 different stages of cooling, and 2 different stages of heating.

c.include capability for occupancy scheduling.

23 09 23 Direct-digital Control system for HVAC

23 09 23.13 Decentralized, Rooftop Units:

23 09 23.13.A. N/A

23 09 23.13.B. RTU-MP - Open protocol, direct digital controller:

1.Shall be ASHRAE 62-2001 compliant.

2.Shall accept 18-30VAC, 50-60Hz, and consumer 15VA or less power.

3.Shall have an operating temperature range from -40_F (-40_C) to 130_F (54_C), 10% - 90% RH (non-condens- ing).

4.Shall include built-in protocol for BACNET (MS/TP and PTP modes), Modbus (RTU and ASCII), Johnson N2 and LonWorks. LonWorks Echelon processor required for all Lon applications shall be contained in separate com- munication board.

5.Shall allow access of up to 62 network variables (SNVT). Shall be compatible with all open controllers

6.Baud rate Controller shall be selectable using a dipswitch.

7.Shall have an LED display independently showing the status of serial communication, running, errors, power, all digital outputs, and all analog inputs.

8.Shall accept the following inputs: space temperature, setpoint adjustment, outdoor air temperature, indoor air qu- ality, outdoor air quality, compressor lock-out, fire shutdown, enthalpy switch, and fan status/filter status/ humid- ity/ remote occupancy.

9.Shall provide the following outputs: economizer, fan, cooling stage 1, cooling stage 2, heat stage 1, heat stage 2, heat stage 3/ exhaust/ reversing valve.

10.Shall have built-in surge protection circuitry through solid state polyswitches. Polyswitches shall be used on in- coming power and network connections. Polyswitches will return to normal when the “trip” condition clears.

78

Image 78
Contents Product Data Table of Contents Certified to ISOFeatures and Benefits Intake/Exhaust Options Voltage Factory Installed OptionsUnit Type Packaging Cooling TonsEconomizers FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesCondenser Protection Economizer SensorsFactory Options AND/OR Accessories Economizer dry-bulb or enthalpyFactory Options AND/OR Accessories Motormaster Head Pressure ControllerUnit Ahri Cooling Rating TableNOM NET Cooling Seer EER Ieer StagesUnits Heating Rating Table Natural GAS & PropaneAL/SS Heat Exchanger Temp Rise Thermal Afue EfficiencySound Performance Table Stages WeightedHeating Rating Table LOW NOx1 Unit CoolingMinimum Maximum Airflow Ratings Natural GAS & Propane Cooling Heating MinimumMinimum Maximum Physical Data TonsNatural Gas, Propane Heat Heat Anticipator Setting Amps580J*04 580J*05 580J*06 580J*07 Gas Connection Low NOx Gas Heat8.5 Tons 10 12.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D12.5 Tons 580J*08 580J*09 580J*12 580J*14 Gas ConnectionCurbs & Weights Dimensions 580J*04-07 Dimensions 580JCurbs & Weights Dimensions 580J*04-07 Dimension ConditionRoof Curb Details Curbs & Weights Dimensions 580J*08-12 Curbs & Weights Dimensions 580J*08-12 580JCurbs & Weights Dimensions 580J*08-14 Curbs & Weights Dimensions 580J Dimensions 580J-14Curbs & Weights Dimensions 580J 14 Options & Accessory Weights Option / Accessory WeightsApplication Data Min operating ambient temp coolingApplication Data Sizing a rooftopSelection Procedure with 580J*07A EXAMPLE1 Rtpf Ambient TemperatureCooling Capacities SHCEdb 900 1200 15001050 1200 1350 Ewb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 1800 580J*07A 105 115EAT db 21002100 2400 2700 2100 2400 2700 1750 2000580J*08A 105 115 580J*08D 105 115 Rtpf & Novation EA db2250/0.05 3000/0.07 3750/0.09 Condenser Edb Cooling Capacities 2-STAGE Cooling Rtpf only TonsTemp F AIR ENT 2250 3000 3750580J*09A 105 115 580J*09D 105 115 2550/0.04 3400/0.05 4250/0.07 Condenser Edb 2550 3400 4250580J*12A 105 115 580J*12D 105 115 Rtpf & Novation Cooling Capacities 2-STAGE Cooling Rtpf only 3000/0.04 4000/0.06 5000/0.07 Condenser Edb3000 4000 5000 580J*14D 105 115 Rtpf & Novation CONDENSEREdb 3750/0.02 5000/0.06 6250/0.05 Condenser EdbTemp Fair ENT 3750 5000 6250Static Pressure Adders Factory Options and/or Accessories 12.5 TonsTons FAN Performance 580J*04CFM RPM BHP FAN Performance Medium Static Option High Static Option1201 580J*051177 1213 1268 13211493 15061486 580J*06 Medium Static Option Field---Supplied Drive11482 1696 1752 17191713 1736580J*07 580J*08 580J*09 580J*12 579580J*14 Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboECONOMIZER, Barometric Relief and PE Performance 2000 1000580J*05A Stage Cooling Electrical Information580J*04A Stage Cooling 580J*06A Stage Cooling580J*08A Stage Cooling Tons Electrical Information580J*07A Stage Cooling 580J*08D Stage Cooling Tons580J*09A Stage Cooling Tons 580J*09D Stage Cooling Tons580J*12A Stage Cooling 580J*12D Stage Cooling 580J*14D Stage Cooling TonsRLA LRA MCA/MOCP Determination no C.O. or Unpwrd C.O Unit Combustion Power NOM IFM FAN Motor Exhaust No P.EUnbalanced 3-Phase Supply Voltage MCA Mocp MCA/MOCP Determination W/ Pwrd C.OPwrd C.O Mocp FLA LRACont. MCA/MOCP Determination W/ Pwrd C.O Typical Wiring Diagrams Stage Cooling Typical Power DiagramTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Sequence of Operation CoolingHeating Sequence of Operation Optional Perfect Humidity Dehumidification SystemSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 23 07 16 Hvac Equipment Insulation Guide Specifications 580J*04-14Gas Heat/Electric Cooling Packaged Rooftop 23 09 13 Instrumentation and Control Devices for Hvac23 40 13 Panel Air Filters 23 09 33 Electric and Electronic Control System for Hvac23 09 93 Sequence of Operations for Hvac Controls 23 81 19 Self-Contained Air Conditioners580J 580J 580J 580J 580J 580J Catalog No. PDS580J