5.Standard All Aluminum Novation Coils:

a.Standard condenser coils shall have all aluminum NOVATION Heat Exchanger Technology design consisting of aluminum multi port flat tube design and aluminum fin. Coils shall be a furnace brazed design and contain epoxy lined shrink wrap on all aluminum to copper connections.

b.Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to UL 1995 burst test at 1980 psig.

6.Optional E-coated aluminum-fin, aluminum tube condenser coils:

a.Shall have a flexible epoxy polymer coating uniformly applied to all coil external surface areas without mater- ial bridging between fins or louvers.

b.Coating process shall ensure complete coil encapsulation, including all exposed fin edges.

c.E-coat thickness of 0.8 to 1.2 mil with top coat having a uniform dry film thickness from 1.0 to 2.0 mil on all external coil surface areas, including fin edges, shall be provided.

d.Shall have superior hardness characteristics of 2H per ASTM D3363-00 and cross-hatch adhesion of 4B-5B per ASTM D3359-02.

e.Shall have superior impact resistance with no cracking, chipping or peeling per NSF/ANSI 51-2002 Method 10.2.

23 81 19.13.K. Refrigerant Components

1.Refrigerant circuit shall include the following control, safety, and maintenance features:

a.Fixed orifice metering system shall prevent mal-distribution of two-phase refrigerant by including multiple fixed orifice devices in each refrigeration circuit. Each orifice is to be optimized to the coil circuit it serves.

b.Refrigerant filter drier - Solid core design.

c.Service gauge connections on suction and discharge lines.

d.Pressure gauge access through a specially designed access port in the top panel of the unit.

2.There shall be gauge line access port in the skin of the rooftop, covered by a black, removable plug.

a.The plug shall be easy to remove and replace.

b.When the plug is removed, the gauge access port shall enable maintenance personnel to route their pressure gauge lines.

c.This gauge access port shall facilitate correct and accurate condenser pressure readings by enabling the read- ing with the compressor access panel on.

d.The plug shall be made of a leak proof, UV-resistant, composite material.

3.Compressors

a.Unit shall use fully hermetic, scroll compressor for each independent refrigeration circuit.

b.Compressor motors shall be cooled by refrigerant gas passing through motor windings.

c.Compressors shall be internally protected from high discharge temperature conditions.

d.Compressors shall be protected from an over-temperature and over-amperage conditions by an internal, motor overload device.

e.Compressor shall be factory mounted on rubber grommets.

f.Compressor motors shall have internal line break thermal, current overload and high pressure differential pro- tection.

g.Crankcase heaters shall not be required for normal operating range, unless required by compressor manufac- turer due to refrigerant charge limits.

23 81 19.13.L. Filter Section

1.Filters access is specified in the unit cabinet section of this specification.

2.Filters shall be held in place by a pivoting filter tray, facilitating easy removal and installation.

3.Shall consist of factory installed, low velocity, throw-away 2-in. thick fiberglass filters.

4.Filters shall be standard, commercially available sizes.

5.Only one size filter per unit is allowed.

23 81 19.13.M. Evaporator Fan and Motor

1.Evaporator fan motor:

a.Shall have permanently lubricated bearings.

b.Shall have inherent automatic-reset thermal overload protection or circuit breaker.

c.Shall have a maximum continuous bhp rating for continuous duty operation; no safety factors above that rating shall be required.

2.Belt-driven Evaporator Fan:

a.Belt drive shall include an adjustable pitch motor pulley.

580J

83

Image 83
Contents Product Data Certified to ISO Table of ContentsFeatures and Benefits Cooling Tons Voltage Factory Installed OptionsUnit Type Packaging Intake/Exhaust OptionsEconomizer Sensors FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesCondenser Protection EconomizersEconomizer dry-bulb or enthalpy Factory Options AND/OR AccessoriesMotormaster Head Pressure Controller Factory Options AND/OR AccessoriesSeer EER Ieer Stages Ahri Cooling Rating TableNOM NET Cooling UnitEfficiency Heating Rating Table Natural GAS & PropaneAL/SS Heat Exchanger Temp Rise Thermal Afue UnitsUnit Cooling Stages WeightedHeating Rating Table LOW NOx1 Sound Performance TableMinimum Maximum Minimum Maximum Airflow Ratings Natural GAS & PropaneCooling Heating Minimum Tons Physical DataLow NOx Gas Heat Heat Anticipator Setting Amps580J*04 580J*05 580J*06 580J*07 Gas Connection Natural Gas, Propane Heat8.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D 10 12.5 Tons580J*08 580J*09 580J*12 580J*14 Gas Connection 12.5 TonsDimensions 580J Curbs & Weights Dimensions 580J*04-07Dimension Condition Curbs & Weights Dimensions 580J*04-07Roof Curb Details Curbs & Weights Dimensions 580J*08-12 580J Curbs & Weights Dimensions 580J*08-12Curbs & Weights Dimensions 580J*08-14 Dimensions 580J-14 Curbs & Weights Dimensions 580JCurbs & Weights Dimensions 580J 14 Option / Accessory Weights Options & Accessory WeightsMin operating ambient temp cooling Application DataSizing a rooftop Application DataSelection Procedure with 580J*07A EXAMPLE1 SHC Ambient TemperatureCooling Capacities RtpfEwb 900 1200 15001050 1200 1350 Edb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 2100 580J*07A 105 115EAT db 18002100 2400 2700 1750 2000 2100 2400 2700580J*08A 105 115 EA db 580J*08D 105 115 Rtpf & Novation2250 3000 3750 Cooling Capacities 2-STAGE Cooling Rtpf only TonsTemp F AIR ENT 2250/0.05 3000/0.07 3750/0.09 Condenser Edb580J*09A 105 115 580J*09D 105 115 2550 3400 4250 2550/0.04 3400/0.05 4250/0.07 Condenser Edb580J*12A 105 115 580J*12D 105 115 Rtpf & Novation 3000 4000 5000 Cooling Capacities 2-STAGE Cooling Rtpf only3000/0.04 4000/0.06 5000/0.07 Condenser Edb 580J*14D 105 115 Rtpf & Novation 3750 5000 6250 3750/0.02 5000/0.06 6250/0.05 Condenser EdbTemp Fair ENT CONDENSEREdbTons Static Pressure Adders Factory Options and/or Accessories12.5 Tons CFM RPM BHP FAN Performance580J*04 Medium Static Option High Static Option FAN Performance1213 1268 1321 580J*051177 12011486 14931506 1482 580J*06Medium Static Option Field---Supplied Drive1 1736 17191713 1696 1752580J*07 580J*08 580J*09 579 580J*12580J*14 Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley Adjustment2000 1000 ECONOMIZER, Barometric Relief and PE Performance580J*06A Stage Cooling Electrical Information580J*04A Stage Cooling 580J*05A Stage Cooling580J*08D Stage Cooling Tons Electrical Information580J*07A Stage Cooling 580J*08A Stage Cooling Tons580J*12A Stage Cooling 580J*09A Stage Cooling Tons580J*09D Stage Cooling Tons RLA LRA 580J*12D Stage Cooling580J*14D Stage Cooling Tons MCA/MOCP Determination no C.O. or Unpwrd C.O NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerUnbalanced 3-Phase Supply Voltage Mocp FLA LRA MCA/MOCP Determination W/ Pwrd C.OPwrd C.O MCA MocpCont. MCA/MOCP Determination W/ Pwrd C.O Stage Cooling Typical Power Diagram Typical Wiring DiagramsTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Heating Sequence of OperationCooling Optional Perfect Humidity Dehumidification System Sequence of OperationSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 23 09 13 Instrumentation and Control Devices for Hvac Guide Specifications 580J*04-14Gas Heat/Electric Cooling Packaged Rooftop 23 07 16 Hvac Equipment Insulation23 81 19 Self-Contained Air Conditioners 23 09 33 Electric and Electronic Control System for Hvac23 09 93 Sequence of Operations for Hvac Controls 23 40 13 Panel Air Filters580J 580J 580J 580J 580J 580J Catalog No. PDS580J