SEQUENCE OF OPERATION (cont.)

580J

On the initial power to the EconoMi$er IV control, it will take the damper up to 2 1/2 minutes before it begins to position itself. After the initial power-up, further changes in damper position can take up to 30 seconds to initiate. Damper movement from full closed to full open (or vice versa) will take between 1 1/2 and 2 1/2 minutes. If free cooling can be used as determined from the appropriate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), then the control will modulate the dampers open to maintain the mixed air temperature setpoint at 50_F (10_C) to 55_F (13_C). If there is a further demand for cooling (cooling second stage - Y2 is energized), then the control will bring on compressor stage 1 to maintain the mixed air temperature setpoint. The EconoMi$er IV damper will be open at maximum position. EconoMi$er IV operation is limited to a single compressor.

Heating

The sequence of operation for the heating is the same as an electromechanical unit with no economizer. The only difference is how the economizer acts. The economizer will stay at the Economizer Minimum Position while the evaporator fan is operating. The outdoor air damper is closed when the indoor fan is not operating.

Optional Perfect Humidity Dehumidification System

Units with the factory equipped Perfect Humidity option are capable of providing multiple modes of improved dehumidification as a variation of the normal cooling cycle. The Perfect Humidity option includes additional valves in the liquid line and discharge line of each refrigerant circuit, a small reheat condenser coil downstream of the evaporator, and Motormaster

variable-speed control of some or all outdoor fans. Operation of the revised refrigerant circuit for each mode is described below.

NOTE: x = refrigerant circuit A, B, or C.

Normal Cooling

Refrigerant flows from the outdoor condenser through the normally open Cooling Valve (CV.x) to the expansion device. Reheat1 Valve (RH1.x) and Reheat2 Valve (RH2.x) are closed.

Reheat1 (Subcooling Mode) - 580J04-14

This mode increases latent cooling and decreases sensible cooling compared to normal cooling. Refrigerant flows from the outdoor condenser, through the normally open Reheat1 Valve (RH1.x), and through the reheat condenser coil to the expansion device. Cooling Valve (CV.x) and Reheat2 Valve (RH2.x) are closed.

Reheat2 (Hot Gas Reheat Mode) - 580J04-14

This mode provides maximum latent cooling with little to no sensible capacity. This mode can operate to provide dehumidification when there is no cooling demand. Like Reheat1 mode, refrigerant flows from the outdoor condenser, through the normally open Reheat1 Valve (RH1.x), and through the reheat condenser coil to the expansion device. The Cooling Valve (CV.x) is closed. Reheat2 Valve (RH2.x) is open which provides some compressor discharge gas to the reheat condenser to further increase the reheat of the evaporator airstream.

RH2.x

 

 

RH1.x

COND COIL

PERFECT HUMIDITY

COMP

COIL

 

CV.x

OUTDOOR AIR

 

METERING

DEVICE

EVAP COIL

CLOSED VALVE

OPEN VALVE

INDOOR ENTERING

AIR

a48-8172

 

C09455

Normal Cooling Mode - Perfect Humidity System (580J04-14)

76

Image 76
Contents Product Data Table of Contents Certified to ISOFeatures and Benefits Voltage Factory Installed Options Unit Type PackagingIntake/Exhaust Options Cooling TonsFACTORY-INSTALLED Options and FIELD-INSTALLED Accessories Condenser ProtectionEconomizers Economizer SensorsFactory Options AND/OR Accessories Economizer dry-bulb or enthalpyFactory Options AND/OR Accessories Motormaster Head Pressure ControllerAhri Cooling Rating Table NOM NET CoolingUnit Seer EER Ieer StagesHeating Rating Table Natural GAS & Propane AL/SS Heat Exchanger Temp Rise Thermal AfueUnits EfficiencyStages Weighted Heating Rating Table LOW NOx1Sound Performance Table Unit CoolingCooling Heating Minimum Minimum Maximum Airflow Ratings Natural GAS & PropaneMinimum Maximum Physical Data TonsHeat Anticipator Setting Amps 580J*04 580J*05 580J*06 580J*07 Gas ConnectionNatural Gas, Propane Heat Low NOx Gas Heat8.5 Tons 10 12.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D12.5 Tons 580J*08 580J*09 580J*12 580J*14 Gas ConnectionCurbs & Weights Dimensions 580J*04-07 Dimensions 580JCurbs & Weights Dimensions 580J*04-07 Dimension ConditionRoof Curb Details Curbs & Weights Dimensions 580J*08-12 Curbs & Weights Dimensions 580J*08-12 580JCurbs & Weights Dimensions 580J*08-14 Curbs & Weights Dimensions 580J Dimensions 580J-14Curbs & Weights Dimensions 580J 14 Options & Accessory Weights Option / Accessory WeightsApplication Data Min operating ambient temp coolingApplication Data Sizing a rooftopSelection Procedure with 580J*07A EXAMPLE1 Ambient Temperature Cooling CapacitiesRtpf SHC900 1200 1500 1050 1200 1350Edb Ewb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 580J*07A 105 115 EAT db1800 21002100 2400 2700 2100 2400 2700 1750 2000580J*08A 105 115 580J*08D 105 115 Rtpf & Novation EA dbCooling Capacities 2-STAGE Cooling Rtpf only Tons Temp F AIR ENT2250/0.05 3000/0.07 3750/0.09 Condenser Edb 2250 3000 3750580J*09A 105 115 580J*09D 105 115 2550/0.04 3400/0.05 4250/0.07 Condenser Edb 2550 3400 4250580J*12A 105 115 580J*12D 105 115 Rtpf & Novation 3000/0.04 4000/0.06 5000/0.07 Condenser Edb Cooling Capacities 2-STAGE Cooling Rtpf only3000 4000 5000 580J*14D 105 115 Rtpf & Novation 3750/0.02 5000/0.06 6250/0.05 Condenser Edb Temp Fair ENTCONDENSEREdb 3750 5000 625012.5 Tons Static Pressure Adders Factory Options and/or AccessoriesTons 580J*04 FAN PerformanceCFM RPM BHP FAN Performance Medium Static Option High Static Option580J*05 11771201 1213 1268 13211506 14931486 Medium Static Option Field---Supplied Drive1 580J*061482 1719 17131696 1752 1736580J*07 580J*08 580J*09 580J*12 579580J*14 Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboECONOMIZER, Barometric Relief and PE Performance 2000 1000Electrical Information 580J*04A Stage Cooling580J*05A Stage Cooling 580J*06A Stage CoolingElectrical Information 580J*07A Stage Cooling580J*08A Stage Cooling Tons 580J*08D Stage Cooling Tons580J*09D Stage Cooling Tons 580J*09A Stage Cooling Tons580J*12A Stage Cooling 580J*14D Stage Cooling Tons 580J*12D Stage CoolingRLA LRA MCA/MOCP Determination no C.O. or Unpwrd C.O Unit Combustion Power NOM IFM FAN Motor Exhaust No P.EUnbalanced 3-Phase Supply Voltage MCA/MOCP Determination W/ Pwrd C.O Pwrd C.OMCA Mocp Mocp FLA LRACont. MCA/MOCP Determination W/ Pwrd C.O Typical Wiring Diagrams Stage Cooling Typical Power DiagramTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Cooling Sequence of OperationHeating Sequence of Operation Optional Perfect Humidity Dehumidification SystemSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 Guide Specifications 580J*04-14 Gas Heat/Electric Cooling Packaged Rooftop23 07 16 Hvac Equipment Insulation 23 09 13 Instrumentation and Control Devices for Hvac23 09 33 Electric and Electronic Control System for Hvac 23 09 93 Sequence of Operations for Hvac Controls23 40 13 Panel Air Filters 23 81 19 Self-Contained Air Conditioners580J 580J 580J 580J 580J 580J Catalog No. PDS580J