FAN PERFORMANCE
Table 33 – 580J*04 |
|
|
| 1 PHASE |
|
| 3 TON HORIZONTAL SUPPLY | |||||
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
| |||||
CFM |
| 0.2 |
| 0.4 | 0.6 |
|
| 0.8 |
| 1.0 | ||
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | |||
|
| |||||||||||
|
| Field Supplied Drive1 |
| Standard Static Option |
|
| Medium Static Option | |||||
900 |
| 553 | 0.14 | 681 | 0.22 | 782 | 0.32 | 870 | 0.42 | 948 | 0.53 | |
975 |
| 575 | 0.16 | 700 | 0.25 | 801 | 0.35 | 888 | 0.46 | 965 | 0.57 | |
1050 |
| 597 | 0.18 | 720 | 0.28 | 820 | 0.38 | 906 | 0.49 | 983 | 0.61 | |
1125 |
| 620 | 0.21 | 741 | 0.31 | 839 | 0.42 | 925 | 0.54 | 1001 | 0.66 | |
1200 |
| 643 | 0.23 | 762 | 0.34 |
|
| 944 | 0.58 | 1020 | 0.71 | |
859 | 0.46 | |||||||||||
1275 |
| 667 | 0.27 | 783 | 0.38 | 879 | 0.50 | 963 | 0.63 | 1038 | 0.76 | |
1350 |
| 691 | 0.30 | 805 | 0.42 | 900 | 0.55 | 983 | 0.68 | 1057 | 0.82 | |
1425 |
| 715 | 0.34 | 827 | 0.47 | 920 | 0.60 | 1002 | 0.74 | 1076 | 0.88 | |
1500 |
| 740 | 0.38 | 849 | 0.52 | 941 | 0.66 | 1023 | 0.80 | 1096 | 0.95 | |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
| |||||
CFM |
|
| 1.2 |
| 1.4 | 1.6 |
|
| 1.8 |
| 2.0 | |
| RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | ||
|
| |||||||||||
|
|
|
| Medium Static Option |
|
|
| Field Supplied Drive2 |
| |||
900 |
| 1019 | 0.64 | 1084 | 0.76 | 1146 | 0.89 | 1203 | 1.02 | 1258 | 1.16 | |
975 |
| 1036 | 0.69 | 1101 | 0.81 | 1162 | 0.94 | 1219 | 1.08 | |||
1050 |
| 1053 | 0.74 | 1118 | 0.86 |
|
| 1236 | 1.14 | |||
| 1179 | 1.00 | ||||||||||
1125 |
| 1071 | 0.79 | 1135 | 0.92 | 1196 | 1.06 | 1253 | 1.20 | |||
1200 |
| 1089 | 0.84 | 1153 | 0.98 | 1213 | 1.12 | |||||
1275 |
| 1107 | 0.90 | 1171 | 1.04 | 1231 | 1.19 | |||||
1350 |
| 1126 | 0.96 |
|
| |||||||
| 1189 | 1.11 | ||||||||||
1425 |
| 1144 | 1.03 | 1208 | 1.18 | |||||||
1500 |
| 1163 | 1.10 |
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field supplied drive is required.
1.Recommend using field supplied fan pulley (part no. KR11AG006) and belt (part no. KR30AE039).
2.Recommend using field supplied motor pulley (part no. KR11HY161) and belt (part no. KR30AE035).
Table 34 – 580J*04 |
|
|
| 1 PHASE |
|
| 3 TON VERTICAL SUPPLY | |||||
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
| |||||
CFM |
| 0.2 |
| 0.4 | 0.6 |
| 0.8 |
| 1.0 |
| ||
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | |||
| ||||||||||||
| Field Supplied Drive1 |
| Standard Static Option |
| Medium Static Option |
| ||||||
900 | 567 | 0.15 | 688 | 0.22 | 786 |
| 0.30 | 871 | 0.37 | 947 | 0.44 | |
975 | 591 | 0.17 | 710 | 0.26 | 807 |
| 0.34 | 891 | 0.42 | 966 | 0.49 | |
1050 | 615 | 0.20 | 732 | 0.29 | 828 |
| 0.38 | 911 | 0.47 | 985 | 0.55 | |
1125 | 641 | 0.23 | 755 | 0.33 | 849 |
| 0.42 | 931 | 0.52 | 1005 | 0.61 | |
1200 | 666 | 0.26 | 778 | 0.37 |
|
| 0.47 | 952 | 0.57 | 1025 | 0.67 | |
871 | ||||||||||||
1275 | 693 | 0.29 | 802 | 0.41 | 893 |
| 0.53 | 974 | 0.63 | 1046 | 0.74 | |
1350 | 719 | 0.33 | 826 | 0.46 | 916 |
| 0.58 | 995 | 0.70 | 1067 | 0.81 | |
1425 | 746 | 0.38 | 850 | 0.51 | 939 |
| 0.64 | 1017 | 0.76 | 1088 | 0.89 | |
1500 | 773 | 0.42 |
|
| 963 |
| 0.70 | 1040 | 0.84 | 1110 | 0.96 | |
875 | 0.57 |
| ||||||||||
|
|
|
|
|
|
|
| |||||
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
| |||||
CFM |
| 1.2 |
| 1.4 | 1.6 |
| 1.8 |
| 2.0 |
| ||
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | |||
| ||||||||||||
|
|
| Medium Static Option |
|
|
|
| Field Supplied Drive2 |
| |||
900 | 1016 | 0.51 | 1080 | 0.57 | 1139 |
| 0.64 | 1195 | 0.71 | 1249 | 0.77 | |
975 | 1034 | 0.57 | 1098 | 0.64 | 1157 |
| 0.72 | 1213 | 0.79 | 1266 | 0.86 | |
1050 | 1053 | 0.63 | 1116 | 0.71 |
|
| 0.79 | 1231 | 0.87 | 1284 | 0.95 | |
1176 |
| |||||||||||
1125 | 1073 | 0.70 | 1135 | 0.79 | 1194 |
| 0.87 | 1250 | 0.96 | 1302 | 1.04 | |
1200 | 1093 | 0.77 | 1155 | 0.87 | 1213 |
| 0.96 | 1268 | 1.05 | 1321 | 1.14 | |
1275 | 1113 | 0.85 | 1174 | 0.95 | 1232 |
| 1.05 | 1287 | 1.15 | |||
1350 | 1133 | 0.92 |
|
| 1252 |
| 1.14 | |||||
1194 | 1.03 |
| ||||||||||
1425 | 1154 | 1.01 | 1215 | 1.12 |
| |||||||
1500 | 1175 | 1.09 |
|
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field supplied drive is required.
1.Recommend using field supplied fan pulley (part no. KR11AG006) and belt (part no. KR30AE039).
2.Recommend using field supplied motor pulley (part no. KR11HY161) and belt (part no. KR30AE035).
580J
49