b.Shall use sealed, permanently lubricated ball-bearing type.

c.Blower fan shall be double-inlet type with forward-curved blades.

d.Shall be constructed from steel with a corrosion resistant finish and dynamically balanced. 23 81 19.13.N. Condenser Fans and Motors

1.Condenser fan motors:

a.Shall be a totally enclosed motor.

b.Shall use permanently lubricated bearings.

c.Shall have inherent thermal overload protection with an automatic reset feature.

d.Shall use a shaft-down design on 04 to 12 models and shaft-up on 14 size with rain shield.

2.Condenser Fans:

a.Shall be a direct-driven propeller type fan.

b.Shall have aluminum blades riveted to corrosion-resistant steel spiders and shall be dynamically balanced. 23 81 19.13.O. Special Features Options and Accessories

1.Integrated Economizers:

a.Integrated, gear-driven parallel modulating blade design type capable of simultaneous economizer and com- pressor operation.

b.Independent modules for vertical or horizontal return configurations shall be available. Vertical return modules shall be available as a factory installed option.

c.Damper blades shall be galvanized steel with composite gears. Plastic or composite blades on intake or return shall not be acceptable.

d.Shall include all hardware and controls to provide free cooling with outdoor air when temperature and/or hu- midity are below setpoints.

e.Shall be equipped with gear driven dampers for both the outdoor ventilation air and the return air for positive air stream control.

f.Shall be equipped with low-leakage dampers, not to exceed 2% leakage at 1 in. wg pressure differential.

g.Shall be capable of introducing up to 100% outdoor air.

h.Shall be equipped with a barometric relief damper capable of relieving up to 100% return air.

i.Shall be designed to close damper(s) during loss-of-power situations with spring return built into motor.

j.Dry bulb outdoor air temperature sensor shall be provided as standard. Outdoor air sensor setpoint shall be adjustable and shall range from 40 to 100_F / 4 to 38_C. Additional sensor options shall be available as ac- cessories.

k.The economizer controller shall also provide control of an accessory power exhaust unit function. Factory set at 100%, with a range of 0% to 100%.

l.The economizer shall maintain minimum airflow into the building during occupied period and provide design ventilation rate for full occupancy. A remote potentiometer may be used to override the damper setpoint.

m.Dampers shall be completely closed when the unit is in the unoccupied mode.

n.Economizer controller shall accept a 2-10 Vdc CO2 sensor input for IAQ/DCV control. In this mode, dampers shall modulate the outdoor air damper to provide ventilation based on the sensor input.

o.Compressor lockout sensor shall open at 35_F (2_C) and close closes at 50_F (10_C).

p.Actuator shall be direct coupled to economizer gear. No linkage arms or control rods shall be acceptable.

q.Economizer controller shall provide indications when in free cooling mode, in the DCV mode, or the exhaust fan contact is closed.

2.Two-Position Damper

a.Damper shall be a Two-Position Damper. Damper travel shall be from the full closed position to the field ad- justable %-open setpoint.

b.Damper shall include adjustable damper travel from 25% to 100% (full open).

c.Damper shall include single or dual blade, gear driven dampers and actuator motor.

d.Actuator shall be direct coupled to damper gear. No linkage arms or control rods shall be acceptable.

e.Damper will admit up to 100% outdoor air for applicable rooftop units.

f.Damper shall close upon indoor (evaporator) fan shutoff and/or loss of power.

g.The damper actuator shall plug into the rooftop unit’s wiring harness plug. No hard wiring shall be required.

h.Outside air hood shall include aluminum water entrainment filter.

3.Manual damper

a.Manual damper package shall consist of damper, air inlet screen, and rain hood which can be preset to admit up to 25 or 50% outdoor air for year round ventilation.

84

Image 84
Contents Product Data Table of Contents Certified to ISOFeatures and Benefits Voltage Factory Installed Options Unit Type PackagingIntake/Exhaust Options Cooling TonsFACTORY-INSTALLED Options and FIELD-INSTALLED Accessories Condenser ProtectionEconomizers Economizer SensorsFactory Options AND/OR Accessories Economizer dry-bulb or enthalpyFactory Options AND/OR Accessories Motormaster Head Pressure ControllerAhri Cooling Rating Table NOM NET CoolingUnit Seer EER Ieer StagesHeating Rating Table Natural GAS & Propane AL/SS Heat Exchanger Temp Rise Thermal AfueUnits EfficiencyStages Weighted Heating Rating Table LOW NOx1Sound Performance Table Unit CoolingMinimum Maximum Airflow Ratings Natural GAS & Propane Cooling Heating MinimumMinimum Maximum Physical Data TonsHeat Anticipator Setting Amps 580J*04 580J*05 580J*06 580J*07 Gas ConnectionNatural Gas, Propane Heat Low NOx Gas Heat8.5 Tons 10 12.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D12.5 Tons 580J*08 580J*09 580J*12 580J*14 Gas ConnectionCurbs & Weights Dimensions 580J*04-07 Dimensions 580JCurbs & Weights Dimensions 580J*04-07 Dimension ConditionRoof Curb Details Curbs & Weights Dimensions 580J*08-12 Curbs & Weights Dimensions 580J*08-12 580JCurbs & Weights Dimensions 580J*08-14 Curbs & Weights Dimensions 580J Dimensions 580J-14Curbs & Weights Dimensions 580J 14 Options & Accessory Weights Option / Accessory WeightsApplication Data Min operating ambient temp coolingApplication Data Sizing a rooftopSelection Procedure with 580J*07A EXAMPLE1 Ambient Temperature Cooling CapacitiesRtpf SHC900 1200 1500 1050 1200 1350Edb Ewb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 580J*07A 105 115 EAT db1800 21002100 2400 2700 2100 2400 2700 1750 2000580J*08A 105 115 580J*08D 105 115 Rtpf & Novation EA dbCooling Capacities 2-STAGE Cooling Rtpf only Tons Temp F AIR ENT2250/0.05 3000/0.07 3750/0.09 Condenser Edb 2250 3000 3750580J*09A 105 115 580J*09D 105 115 2550/0.04 3400/0.05 4250/0.07 Condenser Edb 2550 3400 4250580J*12A 105 115 580J*12D 105 115 Rtpf & Novation Cooling Capacities 2-STAGE Cooling Rtpf only 3000/0.04 4000/0.06 5000/0.07 Condenser Edb3000 4000 5000 580J*14D 105 115 Rtpf & Novation 3750/0.02 5000/0.06 6250/0.05 Condenser Edb Temp Fair ENTCONDENSEREdb 3750 5000 6250Static Pressure Adders Factory Options and/or Accessories 12.5 TonsTons FAN Performance 580J*04CFM RPM BHP FAN Performance Medium Static Option High Static Option580J*05 11771201 1213 1268 13211493 15061486 580J*06 Medium Static Option Field---Supplied Drive11482 1719 17131696 1752 1736580J*07 580J*08 580J*09 580J*12 579580J*14 Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboECONOMIZER, Barometric Relief and PE Performance 2000 1000Electrical Information 580J*04A Stage Cooling580J*05A Stage Cooling 580J*06A Stage CoolingElectrical Information 580J*07A Stage Cooling580J*08A Stage Cooling Tons 580J*08D Stage Cooling Tons580J*09A Stage Cooling Tons 580J*09D Stage Cooling Tons580J*12A Stage Cooling 580J*12D Stage Cooling 580J*14D Stage Cooling TonsRLA LRA MCA/MOCP Determination no C.O. or Unpwrd C.O Unit Combustion Power NOM IFM FAN Motor Exhaust No P.EUnbalanced 3-Phase Supply Voltage MCA/MOCP Determination W/ Pwrd C.O Pwrd C.OMCA Mocp Mocp FLA LRACont. MCA/MOCP Determination W/ Pwrd C.O Typical Wiring Diagrams Stage Cooling Typical Power DiagramTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Sequence of Operation CoolingHeating Sequence of Operation Optional Perfect Humidity Dehumidification SystemSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 Guide Specifications 580J*04-14 Gas Heat/Electric Cooling Packaged Rooftop23 07 16 Hvac Equipment Insulation 23 09 13 Instrumentation and Control Devices for Hvac23 09 33 Electric and Electronic Control System for Hvac 23 09 93 Sequence of Operations for Hvac Controls23 40 13 Panel Air Filters 23 81 19 Self-Contained Air Conditioners580J 580J 580J 580J 580J 580J Catalog No. PDS580J