Table 29 – COOLING CAPACITIES |
|
|
|
| 10 TONS | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
| 580J12 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE |
| ||||||||||||||||
|
|
|
|
|
|
|
| AIR ENTERING EVAPORATOR |
|
|
|
|
| ||||||
TEMP (F) AIR ENT |
| 3000/0.04 |
|
|
|
| 4000/0.06 |
|
|
|
| 5000/0.07 |
|
| |||||
CONDENSER (Edb) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
| Air Entering Evaporator |
|
|
|
|
|
| |||||||
|
|
| 72 |
| 67 |
| 62 |
| 72 |
| 67 |
| 62 |
| 72 |
| 67 |
| 62 |
|
| TC | 142.85 |
| 129.44 |
| 116.93 |
| 152.09 |
| 138.44 |
| 125.76 |
| 157.99 |
| 144.23 |
| 132.06 |
75 |
| SHC | 58.38 |
| 74.88 |
| 91.58 |
| 67.96 |
| 89.45 |
| 111.02 |
| 76.63 |
| 102.94 |
| 127.93 |
|
| kW | 7.19 |
| 6.97 |
| 6.79 |
| 6.92 |
| 7.12 |
| 7.35 |
| 7.45 |
| 7.22 |
| 7.02 |
|
| TC | 132.33 |
| 119.68 |
| 107.86 |
| 140.92 |
| 128.03 |
| 116.10 |
| 146.41 |
| 133.41 |
| 121.98 |
85 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SHC | 48.44 |
| 65.56 |
| 82.83 |
| 57.37 |
| 79.50 |
| 101.68 |
| 65.65 |
| 92.58 |
| 118.12 | |
|
| kW | 7.98 |
| 7.77 |
| 7.58 |
| 7.72 |
| 7.92 |
| 8.14 |
| 8.25 |
| 8.01 |
| 7.82 |
|
| TC | 121.41 |
| 109.52 |
| 98.43 |
| 129.35 |
| 117.22 |
| 106.04 |
| 134.43 |
| 122.20 |
| 111.50 |
95 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SHC | 38.19 |
| 55.92 |
| 73.78 |
| 46.47 |
| 69.22 |
| 92.01 |
| 54.34 |
| 81.92 |
| 107.96 | |
|
| kW | 8.87 |
| 8.66 |
| 8.48 |
| 8.61 |
| 8.80 |
| 9.03 |
| 9.14 |
| 8.90 |
| 8.71 |
|
| TC | 110.04 |
| 98.92 |
| 88.56 |
| 117.27 |
| 105.94 |
| 95.53 |
| 121.88 |
| 110.46 |
| 100.54 |
105 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SHC | 27.59 |
| 45.94 |
| 64.39 |
| 35.16 |
| 58.57 |
| 81.98 |
| 42.56 |
| 70.82 |
| 97.40 | |
|
| kW | 9.86 |
| 9.66 |
| 9.48 |
| 9.61 |
| 9.79 |
| 10.02 |
| 10.12 |
| 9.89 |
| 9.70 |
|
| TC | 98.09 |
| 87.74 |
| 78.13 |
| 104.62 |
| 94.08 |
| 84.45 |
| 108.76 |
| 98.13 |
| 89.01 |
115 |
| SHC | 16.52 |
| 35.47 |
| 54.53 |
| 23.37 |
| 47.44 |
| 71.46 |
| 30.32 |
| 59.25 |
| 86.31 |
|
| kW | 10.95 |
| 10.76 |
| 10.60 |
| 10.72 |
| 10.89 |
| 11.10 |
| 11.19 |
| 10.98 |
| 10.81 |
|
|
| |||||||||||||||||
| 580J12 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE |
| |||||||||||||||||
|
|
|
|
|
|
|
| AIR ENTERING EVAPORATOR |
|
|
|
|
| ||||||
|
|
|
|
| 75 Dry Bulb |
|
|
|
| 75 Dry Bulb |
|
|
|
| 75 Dry Bulb |
| |||
TEMP (F) AIR ENT |
| 62.5 Wet Bulb |
|
|
| 64 Wet Bulb |
|
|
| 65.3 Wet Bulb |
| ||||||||
CONDENSER (Edb) |
| (50% Relative) |
|
|
| (56% Relative) |
|
|
| (60% Relative) |
| ||||||||
|
|
|
|
|
|
|
|
| Air Entering Evaporator |
|
|
|
|
|
| ||||
|
|
| 3000 | 4000 |
| 5000 | 3000 | 4000 |
| 5000 |
| 3000 | 4000 |
| 5000 | ||||
|
| TC | 44.78 | 39.41 |
| 31.89 | 53.22 | 49.44 |
| 43.38 |
| 60.56 | 58.12 |
| 53.32 | ||||
80 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| SHC |
|
|
|
| ||||||||||||||
|
| kW | 6.96 | 6.77 |
| 6.52 | 7.26 | 7.13 |
| 6.91 |
| 7.54 | 7.45 |
| 7.27 | ||||
|
| TC | 45.84 | 40.46 |
| 32.86 | 54.28 | 50.51 |
| 44.45 |
| 61.61 | 59.19 |
| 54.40 | ||||
75 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| SHC | 0.53 | 0.40 |
| 0.29 | 0.60 | 0.47 |
| 0.37 |
| 0.64 | 0.52 |
| 0.42 | |||||
|
| kW | 6.77 | 6.56 |
| 6.29 | 7.11 | 6.95 |
| 6.72 |
| 7.41 | 7.31 |
| 7.12 | ||||
|
| TC | 46.91 | 41.48 |
| 33.50 | 55.36 | 51.59 |
| 45.50 |
| 62.69 | 60.28 |
| 55.49 | ||||
70 |
| SHC | 1.51 | 1.38 |
| 1.27 | 1.57 | 1.45 |
| 1.35 |
| 1.61 | 1.50 |
| 1.40 | ||||
|
| kW | 6.54 | 6.32 |
| 6.02 | 6.90 | 6.74 |
| 6.49 |
| 7.23 | 7.13 |
| 6.92 | ||||
|
| TC | 48.88 | 43.42 |
| 35.76 | 57.29 | 53.56 |
| 47.48 |
| 64.56 | 62.16 |
| 57.42 | ||||
60 |
| SHC | 3.44 | 3.34 |
| 3.24 | 3.51 | 3.40 |
| 3.31 |
| 3.55 | 3.45 |
| 3.37 | ||||
|
| kW | 6.45 | 6.16 |
| 6.70 | 6.93 | 6.72 |
| 6.39 |
| 7.38 | 7.24 |
| 6.96 | ||||
|
| TC | 50.83 | 45.28 |
| 37.67 | 59.22 | 55.52 |
| 49.43 |
| 66.05 | 64.03 |
| 59.34 | ||||
50 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| SHC | 5.38 | 5.29 |
| 5.20 | 5.45 | 5.36 |
| 5.28 |
| 5.48 | 5.40 |
| 5.33 | |||||
|
| kW | 6.46 | 6.01 |
| 6.34 | 6.98 | 6.71 |
| 6.29 |
| 8.15 | 7.38 |
| 7.02 | ||||
|
| TC | 52.82 | 47.29 |
| 39.50 | 61.14 | 57.48 |
| 51.39 |
| 68.23 | 65.88 |
| 61.25 | ||||
40 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| SHC | 7.32 | 7.24 |
| 7.20 | 7.38 | 7.31 |
| 7.24 |
| 7.43 | 7.36 |
| 7.29 | |||||
|
| kW | 6.29 | 6.09 |
| 6.12 | 7.05 | 6.72 |
| 6.29 |
| 7.78 | 7.55 |
| 7.10 |
NOTE: Perfect Humidity only available on
LEGEND |
| NOTES: |
|
| ||
Edb | Entering | 1. Direct interpolation is permissible. Do not extrapolate. | ||||
Ewb | Entering | 2. The following formulas may be used: | ||||
kW | Compressor Motor Power Input |
| sensible capacity (Btuh) |
| ||
Idb | Leaving | tldb = tedb – | ||||
1.10 x cfm | ||||||
Iwb | Leaving | tlwb = | ||||
SHC | Sensible Heat Capacity (1000 Btuh) Gross | |||||
leaving evaporator coil (hlwb) | ||||||
TC | Total Capacity (1000 Btuh) Gross |
| total capacity (Btuh) |
| ||
|
|
| hlwb = hewb – | |||
|
|
| 4.5 x cfm |
Where: hewb = Enthalpy of air entering evaporator coil
580J
45