4.Perfect Humidity Dehumidification System:

a.The Perfect Humidity Dehumidification System shall be factory installed in single stage 580J04-07 and two stage 580J08-14 models with RTPF (round tube plate tin) condenser coils, and shall provide greater dehumidification of the occupied space by two modes of dehumidification operations in addition to its normal design cooling mode:

(1.) Subcooling mode further sub cools the hot liquid refrigerant leaving the condenser coil when both temperat- ure and humidity in the space are not satisfied.

(2.) Hot gas reheat mode shall mix a portion of the hot gas from the discharge of the compressor with the hot liquid refrigerant leaving the condenser coil to create a two-phase heat transfer in the system, resulting in a neutral leaving air temperature when only humidity in the space is not satisfied.

(3.) Includes head pressure controller mentioned below

5.Head Pressure Control Package

a.Controller shall control coil head pressure by condenser fan speed modulation or condenser fan cycling and wind baffles.

b.Shall consist of solid-state control and condenser coil temperature sensor to maintain condensing temperature between 90_F (32_C) and 110_F (43_C) at outdoor ambient temperatures down to -20_F (-29_C).

6.Propane Conversion Kit

a.Package shall contain all the necessary hardware and instructions to convert a standard natural gas unit for use with liquefied propane, up to 2000 ft (610m) elevation.

b.Additional accessory kits may be required for applications above 2000 ft (610m) elevation.

7.Flue Shield

a.Flue shield shall provide protection from the hot sides of the gas flue hood.

8.Condenser Coil Hail Guard Assembly

a.Shall protect against damage from hail.

b.Shall be louvered.

9.Unit-Mounted, Non-Fused Disconnect Switch:

a.Switch shall be factory installed, internally mounted.

b.National Electric Code (NEC) and UL approved non-fused switch shall provide unit power shutoff.

c.Shall be accessible from outside the unit.

d.Shall provide local shutdown and lockout capability.

10.Convenience Outlet:

a.Powered convenience outlet.

(1.) Outlet shall be powered from main line power to the rooftop unit.

(2.) Outlet shall be powered from line side or load side of disconnect by installing contractor, as required by code. If outlet is powered from load side of disconnect, unit electrical ratings shall be UL certified and rated for additional outlet amperage.

(3.) Outlet shall be factory installed and internally mounted with easily accessible 115-v female receptacle. (4.) Outlet shall include 15 amp GFI receptacles with independent fuse protection.

(5.) Voltage required to operate convenience outlet shall be provided by a factory installed step-down trans- former.

(6.) Outlet shall be accessible from outside the unit.

(7.) Outlet shall include a field installed “Wet in Use” cover.

b.Non-Powered convenience outlet.

(1.) Outlet shall be powered from a separate 115/120v power source.

(2.) A transformer shall not be included.

(3.) Outlet shall be factory installed and internally mounted with easily accessible 115-v female receptacle. (4.) Outlet shall include 15 amp GFI receptacles with independent fuse protection.

(5.) Outlet shall be accessible from outside the unit.

(6.) Outlet shall include a field installed “Wet in Use” cover.

11.Flue Discharge Deflector:

a.Flue discharge deflector shall direct unit exhaust vertically instead of horizontally.

b.Deflector shall be defined as a “natural draft” device by the National Fuel and Gas (NFG) code.

12.Thru-the-Base Connectors:

a.Kits shall provide connectors to permit gas and electrical connections to be brought to the unit through the unit basepan.

580J

85

Image 85
Contents Product Data Certified to ISO Table of ContentsFeatures and Benefits Unit Type Packaging Voltage Factory Installed OptionsIntake/Exhaust Options Cooling TonsCondenser Protection FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesEconomizers Economizer SensorsEconomizer dry-bulb or enthalpy Factory Options AND/OR AccessoriesMotormaster Head Pressure Controller Factory Options AND/OR AccessoriesNOM NET Cooling Ahri Cooling Rating TableUnit Seer EER Ieer StagesAL/SS Heat Exchanger Temp Rise Thermal Afue Heating Rating Table Natural GAS & PropaneUnits EfficiencyHeating Rating Table LOW NOx1 Stages WeightedSound Performance Table Unit CoolingCooling Heating Minimum Minimum Maximum Airflow Ratings Natural GAS & PropaneMinimum Maximum Tons Physical Data580J*04 580J*05 580J*06 580J*07 Gas Connection Heat Anticipator Setting AmpsNatural Gas, Propane Heat Low NOx Gas Heat8.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D 10 12.5 Tons580J*08 580J*09 580J*12 580J*14 Gas Connection 12.5 TonsDimensions 580J Curbs & Weights Dimensions 580J*04-07Dimension Condition Curbs & Weights Dimensions 580J*04-07Roof Curb Details Curbs & Weights Dimensions 580J*08-12 580J Curbs & Weights Dimensions 580J*08-12Curbs & Weights Dimensions 580J*08-14 Dimensions 580J-14 Curbs & Weights Dimensions 580JCurbs & Weights Dimensions 580J 14 Option / Accessory Weights Options & Accessory WeightsMin operating ambient temp cooling Application DataSizing a rooftop Application DataSelection Procedure with 580J*07A EXAMPLE1 Cooling Capacities Ambient TemperatureRtpf SHC1050 1200 1350 900 1200 1500Edb Ewb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 EAT db 580J*07A 105 1151800 21002100 2400 2700 1750 2000 2100 2400 2700580J*08A 105 115 EA db 580J*08D 105 115 Rtpf & NovationTemp F AIR ENT Cooling Capacities 2-STAGE Cooling Rtpf only Tons2250/0.05 3000/0.07 3750/0.09 Condenser Edb 2250 3000 3750580J*09A 105 115 580J*09D 105 115 2550 3400 4250 2550/0.04 3400/0.05 4250/0.07 Condenser Edb580J*12A 105 115 580J*12D 105 115 Rtpf & Novation 3000/0.04 4000/0.06 5000/0.07 Condenser Edb Cooling Capacities 2-STAGE Cooling Rtpf only3000 4000 5000 580J*14D 105 115 Rtpf & Novation Temp Fair ENT 3750/0.02 5000/0.06 6250/0.05 Condenser EdbCONDENSEREdb 3750 5000 625012.5 Tons Static Pressure Adders Factory Options and/or AccessoriesTons 580J*04 FAN PerformanceCFM RPM BHP Medium Static Option High Static Option FAN Performance1177 580J*051201 1213 1268 13211506 14931486 Medium Static Option Field---Supplied Drive1 580J*061482 1713 17191696 1752 1736580J*07 580J*08 580J*09 579 580J*12580J*14 Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley Adjustment2000 1000 ECONOMIZER, Barometric Relief and PE Performance580J*04A Stage Cooling Electrical Information580J*05A Stage Cooling 580J*06A Stage Cooling580J*07A Stage Cooling Electrical Information580J*08A Stage Cooling Tons 580J*08D Stage Cooling Tons580J*09D Stage Cooling Tons 580J*09A Stage Cooling Tons580J*12A Stage Cooling 580J*14D Stage Cooling Tons 580J*12D Stage CoolingRLA LRA MCA/MOCP Determination no C.O. or Unpwrd C.O NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerUnbalanced 3-Phase Supply Voltage Pwrd C.O MCA/MOCP Determination W/ Pwrd C.OMCA Mocp Mocp FLA LRACont. MCA/MOCP Determination W/ Pwrd C.O Stage Cooling Typical Power Diagram Typical Wiring DiagramsTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Cooling Sequence of OperationHeating Optional Perfect Humidity Dehumidification System Sequence of OperationSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 Gas Heat/Electric Cooling Packaged Rooftop Guide Specifications 580J*04-1423 07 16 Hvac Equipment Insulation 23 09 13 Instrumentation and Control Devices for Hvac23 09 93 Sequence of Operations for Hvac Controls 23 09 33 Electric and Electronic Control System for Hvac23 40 13 Panel Air Filters 23 81 19 Self-Contained Air Conditioners580J 580J 580J 580J 580J 580J Catalog No. PDS580J