Bryant 580J 23 09 33 Electric and Electronic Control System for Hvac, 23 40 13 Panel Air Filters

Page 79

11.Shall have a battery back-up capable of a minimum of 10,000 hours of data and time clock retention during power outages.

12.Shall have built-in support for Bryant technician tool.

13.Shall include an EIA-485 protocol communication port, an access port for connection of either a computer or a Bryant technician tool, an EIA-485 port for network communication to intelligent space sensors and displays, and a port to connect an optional LonWorks communications card.

14.Software upgrades will be accomplished by either local or remote download. No software upgrades through chip replacements are allowed.

23 09 33 Electric and Electronic Control System for HVAC

23 09 33.13 Decentralized, Rooftop Units:

23 09 33.13.A. General:

1.Shall be complete with self-contained low-voltage control circuit protected by a resettable circuit breaker on the 24-v transformer side. Transformer shall have 75VA capability.

2.Shall utilize color-coded wiring.

3.Shall include a central control terminal board to conveniently and safely provide connection points for vital con- trol functions such as: smoke detectors, phase monitor, gas controller, economizer, thermostat, DDC control op- tions, and low and high pressure switches.

4.The heat exchanger shall be controlled by an integrated gas controller (IGC) microprocessor. See heat exchanger section of this specification.

5.Unit shall include a minimum of one 8-pin screw terminal connection board for connection of control wiring.

23 09 33.23.B. Safeties:

1.Compressor over-temperature, over-current. High internal pressure differential.

2.Low pressure switch.

a.Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high pres- sure switches. They shall physically prevent the cross-wiring of the safety switches between circuits 1 and 2.

b.Low pressure switch shall use different color wire than the high pressure switch. The purpose is to assist the installer and service technician to correctly wire and or troubleshoot the rooftop unit.

3.High pressure switch.

a.Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high pres- sure switches. They shall physically prevent the cross-wiring of the safety switches between circuits 1 and 2.

b.High pressure switch shall use different color wire than the low pressure switch. The purpose is to assist the installer and service technician to correctly wire and or troubleshoot the rooftop unit.

4.Automatic reset, motor thermal overload protector.

5.Heating section shall be provided with the following minimum protections:

a.High temperature limit switches.

b.Induced draft motor speed sensor.

c.Flame rollout switch.

d.Flame proving controls.

23 09 93 Sequence of Operations for HVAC Controls

23 09 93.13 Decentralized, Rooftop Units:

23 09 93.13 INSERT SEQUENCE OF OPERATION

23 40 13 Panel Air Filters

23 40 13.13 Decentralized, Rooftop Units:

23 40 13.13.A. Standard filter section

1.Shall consist of factory installed, low velocity, disposable 2-in. thick fiberglass filters of commercially available sizes.

2.Unit shall use only one filter size. Multiple sizes are not acceptable.

3.Filters shall be accessible through an access panel with “no-tool” removal as described in the unit cabinet section of this specification (23 81 19.13.H).

23 81 19 Self-Contained Air Conditioners

23 81 19.13 Small-Capacity Self-Contained Air Conditioners (580J*04-14)

23 81 19.13.A. General

1.Outdoor, rooftop mounted, electrically controlled, heating and cooling unit utilizing a fully hermetic scroll com- pressor(s) for cooling duty and gas combustion for heating duty.

580J

79

Image 79
Contents Product Data Certified to ISO Table of ContentsFeatures and Benefits Cooling Tons Voltage Factory Installed OptionsUnit Type Packaging Intake/Exhaust OptionsEconomizer Sensors FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesCondenser Protection EconomizersEconomizer dry-bulb or enthalpy Factory Options AND/OR AccessoriesMotormaster Head Pressure Controller Factory Options AND/OR AccessoriesSeer EER Ieer Stages Ahri Cooling Rating TableNOM NET Cooling UnitEfficiency Heating Rating Table Natural GAS & PropaneAL/SS Heat Exchanger Temp Rise Thermal Afue UnitsUnit Cooling Stages WeightedHeating Rating Table LOW NOx1 Sound Performance TableCooling Heating Minimum Minimum Maximum Airflow Ratings Natural GAS & PropaneMinimum Maximum Tons Physical DataLow NOx Gas Heat Heat Anticipator Setting Amps580J*04 580J*05 580J*06 580J*07 Gas Connection Natural Gas, Propane Heat8.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D 10 12.5 Tons580J*08 580J*09 580J*12 580J*14 Gas Connection 12.5 TonsDimensions 580J Curbs & Weights Dimensions 580J*04-07Dimension Condition Curbs & Weights Dimensions 580J*04-07Roof Curb Details Curbs & Weights Dimensions 580J*08-12 580J Curbs & Weights Dimensions 580J*08-12Curbs & Weights Dimensions 580J*08-14 Dimensions 580J-14 Curbs & Weights Dimensions 580JCurbs & Weights Dimensions 580J 14 Option / Accessory Weights Options & Accessory WeightsMin operating ambient temp cooling Application DataSizing a rooftop Application DataSelection Procedure with 580J*07A EXAMPLE1 SHC Ambient TemperatureCooling Capacities RtpfEwb 900 1200 15001050 1200 1350 Edb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 2100 580J*07A 105 115EAT db 18002100 2400 2700 1750 2000 2100 2400 2700580J*08A 105 115 EA db 580J*08D 105 115 Rtpf & Novation2250 3000 3750 Cooling Capacities 2-STAGE Cooling Rtpf only TonsTemp F AIR ENT 2250/0.05 3000/0.07 3750/0.09 Condenser Edb580J*09A 105 115 580J*09D 105 115 2550 3400 4250 2550/0.04 3400/0.05 4250/0.07 Condenser Edb580J*12A 105 115 580J*12D 105 115 Rtpf & Novation 3000/0.04 4000/0.06 5000/0.07 Condenser Edb Cooling Capacities 2-STAGE Cooling Rtpf only3000 4000 5000 580J*14D 105 115 Rtpf & Novation 3750 5000 6250 3750/0.02 5000/0.06 6250/0.05 Condenser EdbTemp Fair ENT CONDENSEREdb12.5 Tons Static Pressure Adders Factory Options and/or AccessoriesTons 580J*04 FAN PerformanceCFM RPM BHP Medium Static Option High Static Option FAN Performance1213 1268 1321 580J*051177 12011506 14931486 Medium Static Option Field---Supplied Drive1 580J*061482 1736 17191713 1696 1752580J*07 580J*08 580J*09 579 580J*12580J*14 Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley Adjustment2000 1000 ECONOMIZER, Barometric Relief and PE Performance580J*06A Stage Cooling Electrical Information580J*04A Stage Cooling 580J*05A Stage Cooling580J*08D Stage Cooling Tons Electrical Information580J*07A Stage Cooling 580J*08A Stage Cooling Tons580J*09D Stage Cooling Tons 580J*09A Stage Cooling Tons580J*12A Stage Cooling 580J*14D Stage Cooling Tons 580J*12D Stage CoolingRLA LRA MCA/MOCP Determination no C.O. or Unpwrd C.O NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerUnbalanced 3-Phase Supply Voltage Mocp FLA LRA MCA/MOCP Determination W/ Pwrd C.OPwrd C.O MCA MocpCont. MCA/MOCP Determination W/ Pwrd C.O Stage Cooling Typical Power Diagram Typical Wiring DiagramsTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Cooling Sequence of OperationHeating Optional Perfect Humidity Dehumidification System Sequence of OperationSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 23 09 13 Instrumentation and Control Devices for Hvac Guide Specifications 580J*04-14Gas Heat/Electric Cooling Packaged Rooftop 23 07 16 Hvac Equipment Insulation23 81 19 Self-Contained Air Conditioners 23 09 33 Electric and Electronic Control System for Hvac23 09 93 Sequence of Operations for Hvac Controls 23 40 13 Panel Air Filters580J 580J 580J 580J 580J 580J Catalog No. PDS580J