SEQUENCE OF OPERATION

General

The sequence below describes the sequence of operation for an electromechanical unit with and without a factory installed EconoMi$er IV (called “economizer” in this sequence). For information regarding a direct digital controller, see the start-up, operations, and troubleshooting manual for the applicable controller.

Electromechanical units with no economizer

Cooling —

When the thermostat calls for cooling, terminals G and Y1 are energized. As a result, the indoor fan contactor (IFC) and the compressor contactor (C1) are energized, causing the indoor fan motor (IFM), compressor #1, and outdoor fan to start. If the unit has 2 stages of cooling, the thermostat will additionally energize Y2. The Y2 signal will energize compressor contactor #2 (C2), causing compressor #2 to start. Regardless of the number of stages, the outdoor fan motor runs continuously while unit is cooling.

Heating

NOTE: Legacy Linet (580J) units have either 1 or 2 stages of gas heat.

When the thermostat calls for heating, power is sent to W on the Integrated Gas Controller (IGC) board. An LED (light-emitting diode) on the IGC board turns on and remains on during normal operation. A check is made to ensure that the rollout switch and limit switch are closed. If the check was successful, the induced-draft motor is energized, and when its speed is satisfactory, as proven by the “hall effect” sensor, the ignition activation period begins. The burners will ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second attempt. This sequence is repeated for 15 minutes or until the burners light. If, after the 15 minutes, the burners still have not lit, heating is locked out. To reset the control, break 24-v power to the thermostat.

When ignition occurs, the IGC board will continue to monitor the condition of the rollout switch, the limit switches, the “hall effect” sensor, as well as the flame sensor. 45 seconds after ignition occurs, assuming the unit is controlled through a room thermostat set for fan auto, the indoor fan motor will energize (and the outdoor air dampers will open to their minimum position). If, for some reason, the over-temperature limit opens prior to the start of the indoor fan blower, the unit will shorten the 45-second delay to 5 seconds less than the time from initiation of heat to when the limit tripped. Gas will not be interrupted to the burners and heating will continue. Once the fan-on delay has been modified, it will not change back to 45 seconds until power is reset to the control.

On units with 2 stages of heat, when additional heat is required, W2 closes and initiates power to the second stage of the main gas valve. When the thermostat is satisfied, W1 and W2 open and the gas valve closes, interrupting the flow of gas to the main burners.

If the call for W1 lasted less than 1 minute, the heating cycle will not terminate until 1 minute after W1 became active. If the unit is controlled through a room thermostat set for fan auto, the indoor fan motor will continue to operate for an additional 45 seconds then stop. If the over-temperature limit opens after the indoor motor is stopped, but within 10 minutes of W1 becoming inactive, on the next cycle the time will be extended by 15 seconds. The maximum delay is 3 minutes. Once modified, the fan off delay will not change back to 45 seconds unless power is reset to the control. A LED indicator is provided on the IGC to monitor operation.

Electromechanical units with an economizer

Cooling —

When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor air damper is modulated by the EconoMi$er IV control to provide a 50_F (10_C) to 55_F (13_C) mixed air temperature into the zone. As the mixed air temperature fluctuates above 55_F (13_C)or below 50_F (10_C) dampers will be modulated (open or close) to bring the mixed air temperature back within control. If mechanical cooling is utilized with free cooling, the outdoor air damper will maintain its current position at the time the compressor is started. If the increase in cooling capacity causes the mixed air temperature to drop below 45_F (7_C), then the outdoor air damper position will be decreased to the minimum position. If the mixed air temperature continues to fall, the outdoor air damper will close. Control returns to normal once the mixed air temperature rises above 48_F (9_C). The power exhaust fans will be energized and de-energized, if installed, as the outdoor air damper opens and closes.

If field installed accessory CO2 sensors are connected to the EconoMi$er IV control, a demand controlled ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 setpoint, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor air damper will be proportionally closed. For EconoMi$er IV operation, there must be a thermostat call for the fan (G). If the unit is occupied and the fan is on, the damper will operate at minimum position. Otherwise, the damper will be closed.

When the EconoMi$er IV control is in the occupied mode and a call for cooling exists (Y1 on the thermostat), the control will first check for indoor fan operation. If the fan is not on, then cooling will not be activated. If the fan is on, then the control will open the EconoMi$er IV damper to the minimum position.

580J

75

Image 75
Contents Product Data Certified to ISO Table of ContentsFeatures and Benefits Cooling Tons Voltage Factory Installed OptionsUnit Type Packaging Intake/Exhaust OptionsEconomizer Sensors FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesCondenser Protection EconomizersEconomizer dry-bulb or enthalpy Factory Options AND/OR AccessoriesMotormaster Head Pressure Controller Factory Options AND/OR AccessoriesSeer EER Ieer Stages Ahri Cooling Rating TableNOM NET Cooling UnitEfficiency Heating Rating Table Natural GAS & PropaneAL/SS Heat Exchanger Temp Rise Thermal Afue UnitsUnit Cooling Stages WeightedHeating Rating Table LOW NOx1 Sound Performance TableMinimum Maximum Airflow Ratings Natural GAS & Propane Cooling Heating MinimumMinimum Maximum Tons Physical DataLow NOx Gas Heat Heat Anticipator Setting Amps580J*04 580J*05 580J*06 580J*07 Gas Connection Natural Gas, Propane Heat8.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D 10 12.5 Tons580J*08 580J*09 580J*12 580J*14 Gas Connection 12.5 TonsDimensions 580J Curbs & Weights Dimensions 580J*04-07Dimension Condition Curbs & Weights Dimensions 580J*04-07Roof Curb Details Curbs & Weights Dimensions 580J*08-12 580J Curbs & Weights Dimensions 580J*08-12Curbs & Weights Dimensions 580J*08-14 Dimensions 580J-14 Curbs & Weights Dimensions 580JCurbs & Weights Dimensions 580J 14 Option / Accessory Weights Options & Accessory WeightsMin operating ambient temp cooling Application DataSizing a rooftop Application DataSelection Procedure with 580J*07A EXAMPLE1 SHC Ambient TemperatureCooling Capacities RtpfEwb 900 1200 15001050 1200 1350 Edb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 2100 580J*07A 105 115EAT db 18002100 2400 2700 1750 2000 2100 2400 2700580J*08A 105 115 EA db 580J*08D 105 115 Rtpf & Novation2250 3000 3750 Cooling Capacities 2-STAGE Cooling Rtpf only TonsTemp F AIR ENT 2250/0.05 3000/0.07 3750/0.09 Condenser Edb580J*09A 105 115 580J*09D 105 115 2550 3400 4250 2550/0.04 3400/0.05 4250/0.07 Condenser Edb580J*12A 105 115 580J*12D 105 115 Rtpf & Novation Cooling Capacities 2-STAGE Cooling Rtpf only 3000/0.04 4000/0.06 5000/0.07 Condenser Edb3000 4000 5000 580J*14D 105 115 Rtpf & Novation 3750 5000 6250 3750/0.02 5000/0.06 6250/0.05 Condenser EdbTemp Fair ENT CONDENSEREdbStatic Pressure Adders Factory Options and/or Accessories 12.5 TonsTons FAN Performance 580J*04CFM RPM BHP Medium Static Option High Static Option FAN Performance1213 1268 1321 580J*051177 12011493 15061486 580J*06 Medium Static Option Field---Supplied Drive11482 1736 17191713 1696 1752580J*07 580J*08 580J*09 579 580J*12580J*14 Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley Adjustment2000 1000 ECONOMIZER, Barometric Relief and PE Performance580J*06A Stage Cooling Electrical Information580J*04A Stage Cooling 580J*05A Stage Cooling580J*08D Stage Cooling Tons Electrical Information580J*07A Stage Cooling 580J*08A Stage Cooling Tons580J*09A Stage Cooling Tons 580J*09D Stage Cooling Tons580J*12A Stage Cooling 580J*12D Stage Cooling 580J*14D Stage Cooling TonsRLA LRA MCA/MOCP Determination no C.O. or Unpwrd C.O NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerUnbalanced 3-Phase Supply Voltage Mocp FLA LRA MCA/MOCP Determination W/ Pwrd C.OPwrd C.O MCA MocpCont. MCA/MOCP Determination W/ Pwrd C.O Stage Cooling Typical Power Diagram Typical Wiring DiagramsTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Sequence of Operation CoolingHeating Optional Perfect Humidity Dehumidification System Sequence of OperationSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 23 09 13 Instrumentation and Control Devices for Hvac Guide Specifications 580J*04-14Gas Heat/Electric Cooling Packaged Rooftop 23 07 16 Hvac Equipment Insulation23 81 19 Self-Contained Air Conditioners 23 09 33 Electric and Electronic Control System for Hvac23 09 93 Sequence of Operations for Hvac Controls 23 40 13 Panel Air Filters580J 580J 580J 580J 580J 580J Catalog No. PDS580J