c.Burners shall incorporate orifices for rated heat output up to 2000 ft (610m) elevation. Additional accessory kits may be required for applications above 2000 ft (610m) elevation, depending on local gas supply condi- tions.

d.Each heat exchanger tube shall contain multiple dimples for increased heating effectiveness.

4.Optional Stainless Steel Heat Exchanger construction

a.Use energy saving, direct-spark ignition system.

b.Use a redundant main gas valve.

c.Burners shall be of the in-shot type constructed of aluminum-coated steel.

d.All gas piping shall enter the unit cabinet at a single location on side of unit (horizontal plane).

e.The optional stainless steel heat exchanger shall be of the tubular-section type, constructed of a minimum of 20-gauge type 409 stainless steel.

f.Type 409 stainless steel shall be used in heat exchanger tubes and vestibule plate.

g.Complete stainless steel heat exchanger allows for greater application flexibility.

5.Optional Low NOx Heat Exchanger construction

a.Low NOx reduction shall be provided to reduce nitrous oxide emissions to meet California’s Air Quality Man- agement District (SCAQMD) low-NOxemissions requirement of 40 nanograms per joule or less.

b.Primary tubes and vestibule plates on low NOx units shall be 409 stainless steel. Other components shall be aluminized steel.

6.Induced draft combustion motor and blower

a.Shall be a direct-drive, single inlet, forward-curved centrifugal type.

b.Shall be made from steel with a corrosion-resistant finish.

c.Shall have permanently lubricated sealed bearings.

d.Shall have inherent thermal overload protection.

e.Shall have an automatic reset feature.

23 81 19.13.J. Coils

1.Standard Aluminum Fin - Copper Tube Coils:

a.Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to seam- less internally grooved copper tubes with all joints brazed.

b.Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst test at 1775 psig.

c.Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to UL 1995 burst test at 1980 psig.

2.Optional Pre-coated aluminum-fin condenser coils:

a.Shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal environments.

b.Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube.

c.Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals.

3.Optional Copper-fin evaporator and condenser coils:

a.Shall be constructed of copper fins mechanically bonded to copper tubes and copper tube sheets.

b.Galvanized steel tube sheets shall not be acceptable.

c.A polymer strip shall prevent coil assembly from contacting the sheet metal coil pan to minimize potential for galvanic corrosion between coil and pan.

4.Optional E-coated aluminum-fin evaporator and condenser coils:

a.Shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins.

b.Coating process shall ensure complete coil encapsulation of tubes, fins and headers.

c.Color shall be high gloss black with gloss per ASTM D523-89.

d.Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges.

e.Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93.

f.Impact resistance shall be up to 160 in.-lb (ASTM D2794-93).

g.Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92).

h.Corrosion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90.

82

Image 82
Contents Product Data Table of Contents Certified to ISOFeatures and Benefits Intake/Exhaust Options Voltage Factory Installed OptionsUnit Type Packaging Cooling TonsEconomizers FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesCondenser Protection Economizer SensorsFactory Options AND/OR Accessories Economizer dry-bulb or enthalpyFactory Options AND/OR Accessories Motormaster Head Pressure ControllerUnit Ahri Cooling Rating TableNOM NET Cooling Seer EER Ieer StagesUnits Heating Rating Table Natural GAS & PropaneAL/SS Heat Exchanger Temp Rise Thermal Afue EfficiencySound Performance Table Stages WeightedHeating Rating Table LOW NOx1 Unit CoolingCooling Heating Minimum Minimum Maximum Airflow Ratings Natural GAS & PropaneMinimum Maximum Physical Data TonsNatural Gas, Propane Heat Heat Anticipator Setting Amps580J*04 580J*05 580J*06 580J*07 Gas Connection Low NOx Gas Heat8.5 Tons 10 12.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D12.5 Tons 580J*08 580J*09 580J*12 580J*14 Gas ConnectionCurbs & Weights Dimensions 580J*04-07 Dimensions 580JCurbs & Weights Dimensions 580J*04-07 Dimension ConditionRoof Curb Details Curbs & Weights Dimensions 580J*08-12 Curbs & Weights Dimensions 580J*08-12 580JCurbs & Weights Dimensions 580J*08-14 Curbs & Weights Dimensions 580J Dimensions 580J-14Curbs & Weights Dimensions 580J 14 Options & Accessory Weights Option / Accessory WeightsApplication Data Min operating ambient temp coolingApplication Data Sizing a rooftopSelection Procedure with 580J*07A EXAMPLE1 Rtpf Ambient TemperatureCooling Capacities SHCEdb 900 1200 15001050 1200 1350 Ewb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 1800 580J*07A 105 115EAT db 21002100 2400 2700 2100 2400 2700 1750 2000580J*08A 105 115 580J*08D 105 115 Rtpf & Novation EA db2250/0.05 3000/0.07 3750/0.09 Condenser Edb Cooling Capacities 2-STAGE Cooling Rtpf only TonsTemp F AIR ENT 2250 3000 3750580J*09A 105 115 580J*09D 105 115 2550/0.04 3400/0.05 4250/0.07 Condenser Edb 2550 3400 4250580J*12A 105 115 580J*12D 105 115 Rtpf & Novation 3000/0.04 4000/0.06 5000/0.07 Condenser Edb Cooling Capacities 2-STAGE Cooling Rtpf only3000 4000 5000 580J*14D 105 115 Rtpf & Novation CONDENSEREdb 3750/0.02 5000/0.06 6250/0.05 Condenser EdbTemp Fair ENT 3750 5000 625012.5 Tons Static Pressure Adders Factory Options and/or AccessoriesTons 580J*04 FAN PerformanceCFM RPM BHP FAN Performance Medium Static Option High Static Option1201 580J*051177 1213 1268 13211506 14931486 Medium Static Option Field---Supplied Drive1 580J*061482 1696 1752 17191713 1736580J*07 580J*08 580J*09 580J*12 579580J*14 Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboECONOMIZER, Barometric Relief and PE Performance 2000 1000580J*05A Stage Cooling Electrical Information580J*04A Stage Cooling 580J*06A Stage Cooling580J*08A Stage Cooling Tons Electrical Information580J*07A Stage Cooling 580J*08D Stage Cooling Tons580J*09D Stage Cooling Tons 580J*09A Stage Cooling Tons580J*12A Stage Cooling 580J*14D Stage Cooling Tons 580J*12D Stage CoolingRLA LRA MCA/MOCP Determination no C.O. or Unpwrd C.O Unit Combustion Power NOM IFM FAN Motor Exhaust No P.EUnbalanced 3-Phase Supply Voltage MCA Mocp MCA/MOCP Determination W/ Pwrd C.OPwrd C.O Mocp FLA LRACont. MCA/MOCP Determination W/ Pwrd C.O Typical Wiring Diagrams Stage Cooling Typical Power DiagramTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Cooling Sequence of OperationHeating Sequence of Operation Optional Perfect Humidity Dehumidification SystemSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 23 07 16 Hvac Equipment Insulation Guide Specifications 580J*04-14Gas Heat/Electric Cooling Packaged Rooftop 23 09 13 Instrumentation and Control Devices for Hvac23 40 13 Panel Air Filters 23 09 33 Electric and Electronic Control System for Hvac23 09 93 Sequence of Operations for Hvac Controls 23 81 19 Self-Contained Air Conditioners580J 580J 580J 580J 580J 580J Catalog No. PDS580J