Page 27

APPLICATION DATA (cont.)

Sizing a rooftop

Bigger isn’t necessarily better. While an air conditioner needs to have enough capacity to meet the design loads, it doesn’t need excess capacity. In fact, excess capacity typically results in very poor part load performance and humidity control.

Using higher design temperatures than ASHRAE recommends for your location, adding “safety factors” to the calculated load, are all signs of oversizing air conditioners. Oversizing the air conditioner leads to poor humidity control, reduced efficiency, higher utility bills, larger indoor temperature swings, excessive noise, and increased wear and tear on the air conditioner.

Rather than oversizing an air conditioner, engineers should “right size” or even slightly undersize air conditioners. Correctly sizing an air conditioner controls humidity better; promotes efficiency; reduces utility bills; extends equipment life, and maintains even, comfortable temperatures. Please contact your local Bryant representative for assistance.

Low ambient applications

The optional Bryant economizer can adequately cool your space by bringing in fresh, cool outside air. In fact, when so equipped, accessory low ambient kit may not be necessary. In low ambient conditions, unless the outdoor air is excessively humid or contaminated, economizer based “free cooling” is the preferred less costly and energy conscious method.

In low ambient applications where outside air might not be desired (such as contaminated or excessively humid outdoor environments), your Bryant rooftop can operate at ambient temperatures down to -20_F (-29_C) using the recommended accessory Motormaster low ambient controller.

580J

27

Image 27
Contents Product Data Certified to ISO Table of ContentsFeatures and Benefits Cooling Tons Voltage Factory Installed OptionsUnit Type Packaging Intake/Exhaust OptionsEconomizer Sensors FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesCondenser Protection EconomizersEconomizer dry-bulb or enthalpy Factory Options AND/OR AccessoriesMotormaster Head Pressure Controller Factory Options AND/OR AccessoriesSeer EER Ieer Stages Ahri Cooling Rating TableNOM NET Cooling UnitEfficiency Heating Rating Table Natural GAS & PropaneAL/SS Heat Exchanger Temp Rise Thermal Afue UnitsUnit Cooling Stages WeightedHeating Rating Table LOW NOx1 Sound Performance TableMinimum Maximum Airflow Ratings Natural GAS & Propane Cooling Heating MinimumMinimum Maximum Tons Physical DataLow NOx Gas Heat Heat Anticipator Setting Amps580J*04 580J*05 580J*06 580J*07 Gas Connection Natural Gas, Propane Heat8.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D 10 12.5 Tons580J*08 580J*09 580J*12 580J*14 Gas Connection 12.5 TonsDimensions 580J Curbs & Weights Dimensions 580J*04-07Dimension Condition Curbs & Weights Dimensions 580J*04-07Roof Curb Details Curbs & Weights Dimensions 580J*08-12 580J Curbs & Weights Dimensions 580J*08-12Curbs & Weights Dimensions 580J*08-14 Dimensions 580J-14 Curbs & Weights Dimensions 580JCurbs & Weights Dimensions 580J 14 Option / Accessory Weights Options & Accessory WeightsMin operating ambient temp cooling Application DataSizing a rooftop Application DataSelection Procedure with 580J*07A EXAMPLE1 SHC Ambient TemperatureCooling Capacities RtpfEwb 900 1200 15001050 1200 1350 Edb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 2100 580J*07A 105 115EAT db 18002100 2400 2700 1750 2000 2100 2400 2700580J*08A 105 115 EA db 580J*08D 105 115 Rtpf & Novation2250 3000 3750 Cooling Capacities 2-STAGE Cooling Rtpf only TonsTemp F AIR ENT 2250/0.05 3000/0.07 3750/0.09 Condenser Edb580J*09A 105 115 580J*09D 105 115 2550 3400 4250 2550/0.04 3400/0.05 4250/0.07 Condenser Edb580J*12A 105 115 580J*12D 105 115 Rtpf & Novation Cooling Capacities 2-STAGE Cooling Rtpf only 3000/0.04 4000/0.06 5000/0.07 Condenser Edb3000 4000 5000 580J*14D 105 115 Rtpf & Novation 3750 5000 6250 3750/0.02 5000/0.06 6250/0.05 Condenser EdbTemp Fair ENT CONDENSEREdbStatic Pressure Adders Factory Options and/or Accessories 12.5 TonsTons FAN Performance 580J*04CFM RPM BHP Medium Static Option High Static Option FAN Performance1213 1268 1321 580J*051177 12011493 15061486 580J*06 Medium Static Option Field---Supplied Drive11482 1736 17191713 1696 1752580J*07 580J*08 580J*09 579 580J*12580J*14 Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley Adjustment2000 1000 ECONOMIZER, Barometric Relief and PE Performance580J*06A Stage Cooling Electrical Information580J*04A Stage Cooling 580J*05A Stage Cooling580J*08D Stage Cooling Tons Electrical Information580J*07A Stage Cooling 580J*08A Stage Cooling Tons580J*09A Stage Cooling Tons 580J*09D Stage Cooling Tons580J*12A Stage Cooling 580J*12D Stage Cooling 580J*14D Stage Cooling TonsRLA LRA MCA/MOCP Determination no C.O. or Unpwrd C.O NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerUnbalanced 3-Phase Supply Voltage Mocp FLA LRA MCA/MOCP Determination W/ Pwrd C.OPwrd C.O MCA MocpCont. MCA/MOCP Determination W/ Pwrd C.O Stage Cooling Typical Power Diagram Typical Wiring DiagramsTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Sequence of Operation CoolingHeating Optional Perfect Humidity Dehumidification System Sequence of OperationSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 23 09 13 Instrumentation and Control Devices for Hvac Guide Specifications 580J*04-14Gas Heat/Electric Cooling Packaged Rooftop 23 07 16 Hvac Equipment Insulation23 81 19 Self-Contained Air Conditioners 23 09 33 Electric and Electronic Control System for Hvac23 09 93 Sequence of Operations for Hvac Controls 23 40 13 Panel Air Filters580J 580J 580J 580J 580J 580J Catalog No. PDS580J