Bryant 580J manual Static Pressure Adders Factory Options and/or Accessories, Tons

Page 48

580J

Table 32 – STATIC PRESSURE ADDERS (Factory Options and/or Accessories)

Economizer

 

 

 

 

3 --- 6 TONS

 

 

 

 

 

 

 

 

 

 

 

CFM (in. wg)

600

800

1000

1250

1500

 

1750

2000

2250

2500

2750

3000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vertical

0.01

0.02

0.04

0.05

0.07

 

0.09

0.12

0.15

0.18

0.22

0.26

 

 

 

 

 

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal

0.02

0.03

0.04

0.06

0.08

 

0.10

0.13

0.15

0.18

0.23

0.28

 

 

 

 

 

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5 --- 12.5 TONS

 

 

 

 

 

 

 

 

CFM (in. wg)

2250

2500

2750

3000

3250

 

3500

3750

4000

4250

4500

4750

5000

5250

5500

5750

6000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vertical

0.06

0.08

0.09

0.12

0.13

 

0.15

0.17

0.20

0.22

0.25

0.29

0.33

0.36

0.40

0.44

0.48

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal

0.08

0.10

0.13

0.15

0.18

 

0.21

0.25

0.28

0.30

0.34

0.39

0.43

0.47

0.51

0.56

0.60

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Perfect Humidity

 

 

 

 

 

3---6 TONS

 

 

 

 

CFM (in. wg)

1000

1250

1500

1750

2000

2250

2500

2750

3000

3

Tons

0.04

0.052

0.07

---

---

---

---

---

---

4 Tons

---

0.106

0.138

0.172

0.21

---

---

---

---

5 Tons

---

---

0.138

0.172

0.21

0.252

0.30

---

---

6 Tons

---

---

---

0.112

0.125

0.161

0.19

0.22

0.25

 

 

 

 

 

 

 

7.5---12.5 TONS

 

 

 

 

 

 

 

 

CFM (in. wg)

2250

2500

2750

3000

3250

3500

3750

4000

4250

4500

4750

5000

5250

5500

5750

6000

7.5 Tons

0.12

0.14

0.16

0.19

0.21

0.23

0.26

---

---

---

---

---

---

---

---

---

8.5 Tons

---

0.11

0.12

0.13

0.15

0.17

0.18

0.20

0.22

---

---

---

---

---

---

---

10 Tons

---

---

---

0.13

0.15

0.17

0.18

0.20

0.22

0.24

0.26

0.28

---

---

---

---

12.5 Tons

---

---

---

---

---

0.17

0.18

0.20

0.22

0.24

0.26

0.28

0.31

0.33

0.36

0.39

General fan performance notes:

1.Interpolation is permissible. Do not extrapolate.

2.External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure caused by any FIOPs or accessories.

3.Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories may add static pressure losses, as shown in the tables above. Selection software is available, through your salesperson, to help you select the best motor/drive combination for your application.

4.The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would work, Bryant recommended the lower horsepower option.

5.For information on the electrical properties of Bryant motors, please see the Electrical information section of this book.

6.For more information on the performance limits of Bryant motors, see the application data section of this book.

7.The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors. Motors regulated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase, squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have to be replaced by an EPACT compliant energy efficient motor. Variable speed motors are exempt from EPACT compliance require- ments. Therefore, the indoor fan motors for Bryant 580J04-14 units are exempt from these requirements.

48

Image 48
Contents Product Data Table of Contents Certified to ISOFeatures and Benefits Voltage Factory Installed Options Unit Type PackagingIntake/Exhaust Options Cooling TonsFACTORY-INSTALLED Options and FIELD-INSTALLED Accessories Condenser ProtectionEconomizers Economizer SensorsFactory Options AND/OR Accessories Economizer dry-bulb or enthalpyFactory Options AND/OR Accessories Motormaster Head Pressure ControllerAhri Cooling Rating Table NOM NET CoolingUnit Seer EER Ieer StagesHeating Rating Table Natural GAS & Propane AL/SS Heat Exchanger Temp Rise Thermal AfueUnits EfficiencyStages Weighted Heating Rating Table LOW NOx1Sound Performance Table Unit CoolingMinimum Maximum Airflow Ratings Natural GAS & Propane Cooling Heating MinimumMinimum Maximum Physical Data TonsHeat Anticipator Setting Amps 580J*04 580J*05 580J*06 580J*07 Gas ConnectionNatural Gas, Propane Heat Low NOx Gas Heat8.5 Tons 10 12.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D12.5 Tons 580J*08 580J*09 580J*12 580J*14 Gas ConnectionCurbs & Weights Dimensions 580J*04-07 Dimensions 580JCurbs & Weights Dimensions 580J*04-07 Dimension ConditionRoof Curb Details Curbs & Weights Dimensions 580J*08-12 Curbs & Weights Dimensions 580J*08-12 580JCurbs & Weights Dimensions 580J*08-14 Curbs & Weights Dimensions 580J Dimensions 580J-14Curbs & Weights Dimensions 580J 14 Options & Accessory Weights Option / Accessory WeightsApplication Data Min operating ambient temp coolingApplication Data Sizing a rooftopSelection Procedure with 580J*07A EXAMPLE1 Ambient Temperature Cooling CapacitiesRtpf SHC900 1200 1500 1050 1200 1350Edb Ewb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 580J*07A 105 115 EAT db1800 21002100 2400 2700 2100 2400 2700 1750 2000580J*08A 105 115 580J*08D 105 115 Rtpf & Novation EA dbCooling Capacities 2-STAGE Cooling Rtpf only Tons Temp F AIR ENT2250/0.05 3000/0.07 3750/0.09 Condenser Edb 2250 3000 3750580J*09A 105 115 580J*09D 105 115 2550/0.04 3400/0.05 4250/0.07 Condenser Edb 2550 3400 4250580J*12A 105 115 580J*12D 105 115 Rtpf & Novation Cooling Capacities 2-STAGE Cooling Rtpf only 3000/0.04 4000/0.06 5000/0.07 Condenser Edb3000 4000 5000 580J*14D 105 115 Rtpf & Novation 3750/0.02 5000/0.06 6250/0.05 Condenser Edb Temp Fair ENTCONDENSEREdb 3750 5000 6250Static Pressure Adders Factory Options and/or Accessories 12.5 TonsTons FAN Performance 580J*04CFM RPM BHP FAN Performance Medium Static Option High Static Option580J*05 11771201 1213 1268 13211493 15061486 580J*06 Medium Static Option Field---Supplied Drive11482 1719 17131696 1752 1736580J*07 580J*08 580J*09 580J*12 579580J*14 Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboECONOMIZER, Barometric Relief and PE Performance 2000 1000Electrical Information 580J*04A Stage Cooling580J*05A Stage Cooling 580J*06A Stage CoolingElectrical Information 580J*07A Stage Cooling580J*08A Stage Cooling Tons 580J*08D Stage Cooling Tons580J*09A Stage Cooling Tons 580J*09D Stage Cooling Tons580J*12A Stage Cooling 580J*12D Stage Cooling 580J*14D Stage Cooling TonsRLA LRA MCA/MOCP Determination no C.O. or Unpwrd C.O Unit Combustion Power NOM IFM FAN Motor Exhaust No P.EUnbalanced 3-Phase Supply Voltage MCA/MOCP Determination W/ Pwrd C.O Pwrd C.OMCA Mocp Mocp FLA LRACont. MCA/MOCP Determination W/ Pwrd C.O Typical Wiring Diagrams Stage Cooling Typical Power DiagramTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Sequence of Operation CoolingHeating Sequence of Operation Optional Perfect Humidity Dehumidification SystemSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 Guide Specifications 580J*04-14 Gas Heat/Electric Cooling Packaged Rooftop23 07 16 Hvac Equipment Insulation 23 09 13 Instrumentation and Control Devices for Hvac23 09 33 Electric and Electronic Control System for Hvac 23 09 93 Sequence of Operations for Hvac Controls23 40 13 Panel Air Filters 23 81 19 Self-Contained Air Conditioners580J 580J 580J 580J 580J 580J Catalog No. PDS580J