CURBS & WEIGHTS DIMENSIONS - 580J*08-12 (cont.)

580J

C

B

C08526

Fig. 6 - 580J 08-12

D

A

C08337

 

 

 

Fig. 7 - Service Clearance

 

 

 

LOC

DIMENSION

CONDITION

 

48---

in (1219 mm)

Unit disconnect is mounted on panel

 

36---

in (914 mm)

If dimension--- B is 12--- in (305 mm)

A

18---

in (457 mm)

No disconnect, convenience outlet option

 

18---

in (457 mm)

Recommended service clearance (use electric screwdriver)

 

12---

in (305 mm)

Minimum clearance (use manual ratchet screwdriver)

 

 

 

 

 

36---

in (914 mm)

Unit has economizer

B

12---

in (305 mm)

If dimension--- A is 36--- in (914 mm)

 

 

Special

Check for sources of flue products within 10--- ft of unit fresh air intake hood

 

 

 

 

C

36---

in (914 mm)

Side condensate drain is used

18---

in (457 mm)

Minimum clearance

 

 

 

 

 

 

48---

in (1219 mm)

No flue discharge accessory installed, surface is combustible material

D

42---

in (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)

36---

in (914 mm)

Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)

 

 

 

Special

Check for adjacent units or building fresh air intakes within 10--- ft of this unit’s flue outlet

 

 

 

 

21

Image 21
Contents Product Data Certified to ISO Table of ContentsFeatures and Benefits Unit Type Packaging Voltage Factory Installed OptionsIntake/Exhaust Options Cooling TonsCondenser Protection FACTORY-INSTALLED Options and FIELD-INSTALLED AccessoriesEconomizers Economizer SensorsEconomizer dry-bulb or enthalpy Factory Options AND/OR AccessoriesMotormaster Head Pressure Controller Factory Options AND/OR AccessoriesNOM NET Cooling Ahri Cooling Rating TableUnit Seer EER Ieer StagesAL/SS Heat Exchanger Temp Rise Thermal Afue Heating Rating Table Natural GAS & PropaneUnits EfficiencyHeating Rating Table LOW NOx1 Stages WeightedSound Performance Table Unit CoolingMinimum Maximum Airflow Ratings Natural GAS & Propane Cooling Heating MinimumMinimum Maximum Tons Physical Data580J*04 580J*05 580J*06 580J*07 Gas Connection Heat Anticipator Setting AmpsNatural Gas, Propane Heat Low NOx Gas Heat8.5 Tons Refrigeration System 580J*12A 580J*12D 580J*14D 10 12.5 Tons580J*08 580J*09 580J*12 580J*14 Gas Connection 12.5 TonsDimensions 580J Curbs & Weights Dimensions 580J*04-07Dimension Condition Curbs & Weights Dimensions 580J*04-07Roof Curb Details Curbs & Weights Dimensions 580J*08-12 580J Curbs & Weights Dimensions 580J*08-12Curbs & Weights Dimensions 580J*08-14 Dimensions 580J-14 Curbs & Weights Dimensions 580JCurbs & Weights Dimensions 580J 14 Option / Accessory Weights Options & Accessory WeightsMin operating ambient temp cooling Application DataSizing a rooftop Application DataSelection Procedure with 580J*07A EXAMPLE1 Cooling Capacities Ambient TemperatureRtpf SHC1050 1200 1350 900 1200 1500Edb Ewb580J*05A 105 115 1200 1600 2000 580J*06A 105 115 1750 2000 2250 EAT db 580J*07A 105 1151800 21002100 2400 2700 1750 2000 2100 2400 2700580J*08A 105 115 EA db 580J*08D 105 115 Rtpf & NovationTemp F AIR ENT Cooling Capacities 2-STAGE Cooling Rtpf only Tons2250/0.05 3000/0.07 3750/0.09 Condenser Edb 2250 3000 3750580J*09A 105 115 580J*09D 105 115 2550 3400 4250 2550/0.04 3400/0.05 4250/0.07 Condenser Edb580J*12A 105 115 580J*12D 105 115 Rtpf & Novation Cooling Capacities 2-STAGE Cooling Rtpf only 3000/0.04 4000/0.06 5000/0.07 Condenser Edb3000 4000 5000 580J*14D 105 115 Rtpf & Novation Temp Fair ENT 3750/0.02 5000/0.06 6250/0.05 Condenser EdbCONDENSEREdb 3750 5000 6250Static Pressure Adders Factory Options and/or Accessories 12.5 TonsTons FAN Performance 580J*04CFM RPM BHP Medium Static Option High Static Option FAN Performance1177 580J*051201 1213 1268 13211493 15061486 580J*06 Medium Static Option Field---Supplied Drive11482 1713 17191696 1752 1736580J*07 580J*08 580J*09 579 580J*12580J*14 Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley Adjustment2000 1000 ECONOMIZER, Barometric Relief and PE Performance580J*04A Stage Cooling Electrical Information580J*05A Stage Cooling 580J*06A Stage Cooling580J*07A Stage Cooling Electrical Information580J*08A Stage Cooling Tons 580J*08D Stage Cooling Tons580J*09A Stage Cooling Tons 580J*09D Stage Cooling Tons580J*12A Stage Cooling 580J*12D Stage Cooling 580J*14D Stage Cooling TonsRLA LRA MCA/MOCP Determination no C.O. or Unpwrd C.O NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerUnbalanced 3-Phase Supply Voltage Pwrd C.O MCA/MOCP Determination W/ Pwrd C.OMCA Mocp Mocp FLA LRACont. MCA/MOCP Determination W/ Pwrd C.O Stage Cooling Typical Power Diagram Typical Wiring DiagramsTypical Wiring Diagrams Stage Typical Wiring Diagram C08578 Sequence of Operation CoolingHeating Optional Perfect Humidity Dehumidification System Sequence of OperationSubcooling Mode Reheat 1 Perfect Humidity System 580J04-14 Gas Heat/Electric Cooling Packaged Rooftop Guide Specifications 580J*04-1423 07 16 Hvac Equipment Insulation 23 09 13 Instrumentation and Control Devices for Hvac23 09 93 Sequence of Operations for Hvac Controls 23 09 33 Electric and Electronic Control System for Hvac23 40 13 Panel Air Filters 23 81 19 Self-Contained Air Conditioners580J 580J 580J 580J 580J 580J Catalog No. PDS580J