Hearth and Home Technologies EDV3633L, EDV3633IL Minimum Clearances for Termination

Page 23

D

E

V

LB C

V

Fixed

Closed

 

F V

B

H

O

N

V

B V

VOpenable Fixed Closed

 

V

 

B

B

J

X

 

 

 

 

 

A

GAS METER

 

 

 

 

 

 

G

 

 

 

V

 

M

 

V

I

V

K X

 

 

A

V TERMINATION CAP

Measure vertical clearances from this surface

T

X AIR SUPPLY INLET

Q P

V

R

S

RESTRICTION ZONE (TERMINATION NOT ALLOWED)

V U

V

W

Electrical Service

D*

V

U

V

Measure horizontal clearances

Covered Alcove

Applications

from this surface.

 

Clearances to Electrical Service

Dimension Descriptions

AClearance above the ground, a veranda, porch, deck or balcony - 12 in. (30 cm) minimum. *

BClearance to window or door that may be opened – 10,000 BTUs or less, 6 in. (15 cm) minimum; 10,000-50,000 BTUs, 9 in. (23 cm) minimum; over 50,000 BTUs, 12 in. (30 cm) minimum. *

CClearance to permanently closed window – 12 in. (30 cm) minimum - recommended to prevent condensation on window.

DVertical clearance to ventilated soffit located above the termination within a horizontal distance of 2 ft (60 cm) from the centerline of the termination

– 18 in. (46 cm) minimum. **

EVertical clearance to unventilated soffit - 12 in. (30 cm) minimum. **

FClearance to outside corner - 6 in. (15 cm) minimum.

GClearance to inside corner - 6 in. (15 cm) minimum.

HNot to be installed above a meter/regulator assembly within 3 ft (90 cm) horizontally* from the center line of the regulator (Canada only)

IClearance to service regulator vent outlet – 3 ft (.91 m) U.S. minimum and 3 ft (.91 m) Canada minimum. *

JClearance to non-mechanical air supply inlet into building or the combustion air inlet to any other appliance – 9” (23 cm) U.S. minimum and 12 in. (30 cm) Canada minimum. *

KClearance to mechanical air supply inlet - 3 ft (.91 m) U.S. minimum and 6 ft (1.8 m) Canada minimum. *

LClearance above a paved sidewalk or paved driveway located on public property - 7 ft (2.1 m) minimum.

A vent may not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

MClearance under veranda, porch, deck or balcony - 12 in. (30 cm) minimum. * Recommended 30 in. (76 cm) for vinyl or plastic.

Only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor. *

NVertical clearance between two horizontal termination caps – 12 in. (30 cm) minimum.

OHorizontal clearance between two horizontal termination caps – 12 in. (30 cm) minimum.

Figure 6.4 Minimum Clearances for Termination

P6” - Non-vinyl sidewalls 12” – Vinyl sidewalls

Q18” – Non-vinyl soffit and overhang 42” – Vinyl soffit and overhang

R8 ft.

 

 

S min

T max

1 cap

 

3 ft

2 x S actual

2 caps

 

6 ft

1 x S actual

3 caps

 

9 ft

2/3 x S actual

4 caps

 

12 ft

1/2 x S actual

S min = # term caps x 3

T max = (2/# term caps) x S (actual)

U6” min. – Clearance from sides of electrical service. W 12” min. – Clearance above electrical service.

* As specified in CGA B149 Installation Codes

Note: Local codes or regulations may require different clearances. ** Clearance required to vinyl soffit material – 30 in. (76 cm) minimum.

Note: Location of the vent termination must not interfere with access to the electrical service.

WARNING!

In the U.S.: Vent system termination is NOT permitted in screened porches. You must follow side wall, overhang and ground clearances as stated in the instructions.

In Canada: Vent system termination is NOT permitted in screened porches. Vent system termination is permitted in porch areas with two or more sides open. You must follow all side wall, overhang and ground clearances as stated in the instructions.

Hearth & Home Technologies assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.

CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.

Heatilator • Eclipse • 4049-229 Rev F • 11/08

23

Image 23
Contents Do not Discard this Manual What to do if you smell gasHomeowner Reference Information CongratulationsUser Guide Table of ContentsInstaller Guide Troubleshooting CONDITIONS, Exclusions & Limitation of Liability Warranty Hearth & Home Technologies Limited WarrantyWarranty Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsYour Fireplace Gas Fireplace SafetyOperating Instructions Clear Space Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Fan KitLighting Instructions For Your Safety Read Before Lighting After Fireplace is Lit Frequently Asked QuestionsMaintenance Tasks-Homeowner Maintenance and ServiceVenting Maintenance Tasks-Qualified Service TechnicianEither cobrahead or SIT Typical Appliance System Getting StartedInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Selecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseMantels Mantel Legs or Wall Projections Mantel and Wall ProjectionsVent Termination Minimum Clearances Termination LocationsMinimum Clearances for Termination Use of Elbows Vent Information and DiagramsApproved Pipe Vent Table KeyOne Elbow Vent DiagramsTop Vent Horizontal Termination Installed Vertically HorizontallyThree Elbows Top Vent Vertical Termination 12 ft 3.66 m min 60 ft 18.29 m max Wall Penetration Framing Vent Clearances and FramingPipe Clearances to Combustibles Installing Ceiling Firestop Install the Ceiling FirestopFlat Ceiling Installation Install Attic Insulation ShieldSecuring and Leveling the Appliance Appliance PreparationAssemble Slip Sections Installing SLP Vent PipeAssemble Vent Sections Disassemble Vent Sections Securing the Vent SectionsInstalling Metal Roof Flashing SLP-FS Install RF4-8Assemble and Install Storm Collar Installing Vertical Termination CapInstall Heat Shields and Horizontal Termi- nation Cap Install Horizontal Termination Cap Gas Connection Gas InformationFuel Conversion Gas PressureOptional Accessories Requirements Wiring RequirementsStanding Pilot Ignition System Wiring Intellifire Ignition System WiringGAS Electrical Service and RepairWall Switch Installation for Fan Optional Junction Box InstallationFacing Material FinishingLogs Appliance SetupRemove Glass Assembly Remove Packaging MaterialsGrilles and Screen Install Floor CoverReplace Glass Accessories Air Shutter SettingStanding Pilot Ignition System TroubleshootingSymptom Possible Cause Corrective Action TroubleshootingIntellifire Ignition System Will not ignite. If the pilot Reference Materials Appliance Dimension DiagramLength Vent Components DiagramsSLP-HRC-SS EDV3633 Service PartsEDV3633I, EDV3633IL Standing Pilot Valve Assembly Optional Components Contact Information