Hearth and Home Technologies EDV3633 Maintenance Tasks-Qualified Service Technician, Venting

Page 15

Venting

Frequency: Seasonally

By: Homeowner

Tools needed: Protective gloves and safety glasses.

Inspect venting and termination cap for blockage or obstruction such plants, bird nests, leaves, snow, debris, etc.

Verify termination cap clearance to subsequent construction (building additions, decks, fences, or sheds). See Section 6.

Inspect for corrosion or separation.

Verify weather stripping, sealing and flashing remains intact.

Inspect draft shield to verify it is not damaged or missing.

B. Maintenance Tasks-Qualified Service Technician

The following tasks must be performed by a qualified service technician.

Gasket Seal and Glass Assembly Inspection

Frequency: Annually

By: Qualified Service Technician

Tools needed: Protective gloves, drop cloth and a stable work surface.

Inspect gasket seal and its condition.

Inspect fixed glass assembly for scratches and nicks that can lead to breakage when exposed to heat.

Confirm there is no damage to glass or glass frame. Replace as necessary.

Verify that fixed glass assembly is properly retained and attachment components are intact and not damaged. Replace as necessary.

Logs

Frequency: Annually

By: Qualified Service Technician

Tools needed: Protective gloves.

Inspect for damaged or missing logs. Replace as necessary. Refer to Section 14 for log reference.

Verify correct log placement and no flame impingement causing sooting. Correct as necessary.

Firebox

Frequency: Annually

By: Qualified Service Technician

Tools needed: Protective gloves, sandpaper, steel wool, cloths, mineral spirits, primer and touch-up paint.

Inspect for paint condition, warped surfaces, corrosion or perforation. Sand and repaint as necessary.

Replace fireplace if firebox has been perforated.

Control Compartment and Firebox Top

Frequency: Annually

By: Qualified Service Technician

Tools needed: Protective gloves, vacuum cleaner, dust cloths

Vacuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided.

Remove all foreign objects.

Verify unobstructed air circulation.

Burner Ignition and Operation

Frequency: Annually

By: Qualified Service Technician

Tools needed: Protective gloves, vacuum cleaner, whisk broom, flashlight, voltmeter, indexed drill bit set, and a manometer.

Verify burner is properly secured and aligned with pilot or igniter.

Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if necessary.

Replace rockwool materials with new dime-size pieces. DO NOT block ports or obstruct lighting paths. Refer to Section 14 for proper rockwool placement.

Verify batteries have been removed from battery back- up IPI systems to prevent premature battery failure or leaking.

Check for smooth lighting and ignition carryover to all ports. Verify that there is no ignition delay.

Inspect for lifting or other flame problems.

Verify air shutter setting is correct. See Section 14 for required air shutter setting. Verify air shutter is clear of dust and debris.

Inspect orifice for soot, dirt and corrosion. Verify orifice size is correct. See Service Parts List for proper orifice sizing.

Verify manifold and inlet pressures. Adjust regulator as required.

Inspect pilot flame pattern and strength. See Figure 3.1 and 3.2 for proper pilot flame pattern. Clean or replace orifice spud as necessary.

Inspect thermocouple/thermopile or IPI flame sensing rod for soot, corrosion and deterioration. Clean with emery cloth or replace as required.

Verify thermocouple/thermopile or IPI millivolt output. Replace as necessary.

Heatilator • Eclipse • 4049-229 Rev F • 11/08

15

Image 15
Contents Do not Discard this Manual What to do if you smell gasHomeowner Reference Information CongratulationsTable of Contents Installer GuideUser Guide Troubleshooting CONDITIONS, Exclusions & Limitation of Liability Warranty Hearth & Home Technologies Limited WarrantyWarranty Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsGas Fireplace Safety Operating InstructionsYour Fireplace Clear Space Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Fan KitLighting Instructions For Your Safety Read Before Lighting After Fireplace is Lit Frequently Asked QuestionsMaintenance Tasks-Homeowner Maintenance and ServiceVenting Maintenance Tasks-Qualified Service TechnicianEither cobrahead or SIT Typical Appliance System Getting StartedDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Selecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseMantels Mantel Legs or Wall Projections Mantel and Wall ProjectionsVent Termination Minimum Clearances Termination LocationsMinimum Clearances for Termination Use of Elbows Vent Information and DiagramsApproved Pipe Vent Table KeyOne Elbow Vent DiagramsTop Vent Horizontal Termination Installed Vertically HorizontallyThree Elbows Top Vent Vertical Termination 12 ft 3.66 m min 60 ft 18.29 m max Vent Clearances and Framing Pipe Clearances to CombustiblesWall Penetration Framing Installing Ceiling Firestop Install the Ceiling FirestopFlat Ceiling Installation Install Attic Insulation ShieldSecuring and Leveling the Appliance Appliance PreparationInstalling SLP Vent Pipe Assemble Vent SectionsAssemble Slip Sections Disassemble Vent Sections Securing the Vent SectionsInstalling Metal Roof Flashing SLP-FS Install RF4-8Assemble and Install Storm Collar Installing Vertical Termination CapInstall Heat Shields and Horizontal Termi- nation Cap Install Horizontal Termination Cap Gas Connection Gas InformationFuel Conversion Gas PressureOptional Accessories Requirements Wiring RequirementsStanding Pilot Ignition System Wiring Intellifire Ignition System WiringGAS Electrical Service and RepairWall Switch Installation for Fan Optional Junction Box InstallationFacing Material FinishingLogs Appliance SetupRemove Glass Assembly Remove Packaging MaterialsInstall Floor Cover Replace GlassGrilles and Screen Accessories Air Shutter SettingStanding Pilot Ignition System TroubleshootingSymptom Possible Cause Corrective Action TroubleshootingIntellifire Ignition System Will not ignite. If the pilot Reference Materials Appliance Dimension DiagramLength Vent Components DiagramsSLP-HRC-SS EDV3633 Service PartsEDV3633I, EDV3633IL Standing Pilot Valve Assembly Optional Components Contact Information