18.0 Fault Finding
I
1.
2.
Check supply pressure at the gas valve:-
Minimum 17 mbar
Check and correct if necessary
1.The mechanical set of the gas valve (CO2 values - see instruction)
2.Flame sensing electrode and lead connections
3.Flame sensing electrode position
Flame current should be more than 0.5 μ A
YES
NO
Replace PCB
Replace flame sensing electrode
J
1. | Overheat thermostat operated or | NO |
|
| Allow to cool. Continuity | YES |
|
| |||
| faulty, i.e. continuity across |
|
| across thermostat terminals |
| Replace safety thermostat | |||||
|
|
|
|
|
| ||||||
| thermostat terminals |
|
|
| more than 1.5 ohm |
|
|
| |||
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| |
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Replace PCB |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
K
| Is there 230V at: |
|
|
|
|
| ||
|
|
|
|
|
| YES | ||
1. |
|
|
|
|
| |||
| Motor |
| ||||||
|
|
|
| NO | ||||
2. |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| ||
| PCB - X3 connector terminals |
|
| |||||
|
|
|
| |||||
| 5 | & 6 central heating mode |
|
|
| |||
| 5 | & 7 domestic hot water mode |
|
|
|
YES
Change pump supply cable
Replace motor
Replace PCB
L
M
1.
1.
Fan connections correct at fan.
PCB - X401 connector terminals 5,6,7 & 8
Temperature sensors faulty. Cold resistance approximately 10kΩ @ 25° C (CH sensor)
20kΩ @ 25° C (Flue sensor)
(resistance reduces with increase in temp.)
YES | Replace fan |
|
NO
Replace sensor
|
|
| YES |
| ||
2. | If pump is running the heat exchanger could be | Replace heat exchanger | ||||
|
|
| ||||
| obstructed |
|
|
|
| |
|
|
|
|
|
|
© Baxi Heating UK Ltd 2011 | 55 |