LG Electronics WG2405RY6, WG1805RY6, RAD-183A, RAD-243A service manual Disassembly

Page 21

Disassembly

NOTICE

Replacement of the refrigeration cycle.

1.When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a FreonTM recovery System.

If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

2.After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.

3.Braze service valves into the pinch-off tube ports, leaving the valves open.

4.Braze the pinch-off tubes with Service valves.

5.Evacuate as follows.

1)Connect the vacuum pump, as illustrated figure 33A.

2)Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise and leave the valves open.

The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system.

CAUTION: If high vacuum equip- ment is used, just crack valves A

and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.

3)Operate the vacuum pump vaccum for 20 to 30 minutes, until 600 microns of vaccum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indi- cate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vac- uum pump.

4)Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 33B. Open valve C.

Discharge the line at the manifold connection.

5)The system is now ready for final charging.

6. Recharge as follows :

1)Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put

in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.

2)Connect the charging cylinder as shown in figure 33B.

With valve C open, discharge the hose at the mani- fold connection.

3)Open valve A and allow the proper charge to enter the system. Valve B is still closed.

4)If more charge is required, the high-side will not take it. Close valve A.

5)With the unit running, open valve B and add the balance of the charge.

a.Do not add the liquid refrigerant to the Low- side.

b.Watch the Low-side gauge; allow pressure to rise to 30 lbs (0.2Mp).

c.Turn off valve B and allow pressure to drop.

d.Repeat steps b. and c. until the balance of the charge is in the system.

6)When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos brazing rod and braze pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.

Service Manual 20

Image 21
Contents LG Room Air Conditioner Table of Contents Be sure not to do Be sure to follow the instruction Safety PrecautionsThere is risk or fire or electric shock Dimensions Symbols Used in this ManualOutside Dimensions Product Specifications 800/1,850 760/2,710 Installation Check InstallationHow to Secure the Drain Pipe Select the Best LocationWindow Requirements Installation Kits ContentsPreparation of Chassis Suggested Tool RequirementsCabinet Installation Installation Operation FeaturesControl Locations Function of Controls Cooling Only ModelCooling Only Model with Remote Control and Touch Type WG2405RY6, WG2405RY6WG2405RY6 Mechanical Parts DisassemblyFront Grille CabinetCover at the top Air Handling PartsBlower FanShroud Electrical PartsMotor CompressorCapacitor Power CordThermistor Synchronous MotorRefrigerating Cycle EvaporatorCapillary Tube Disassembly Pulling Vacuum CN-TH1 DiagramModel WG1805RY6 / WG2405RY6 Wiring DiagramComponents Location Main P.W.B Assembly Display P.W.B AssemblyPiping System Troubleshooting GuideUnit runs but poor cooling Troubleshooting GuideFails to Start Possible Trouble Electrical Parts Troubleshooting GuideIC01M 0V? IC01M DC 5V? Delay? IC01M 0V? Possible Trouble 6 Remote controller does not operate Complaint Cause Remedy Room Air Conditioner Voltage LimitsTroubleshooting Guide Troubleshooting Guide Exploded View 130910 135515 135500 554031 148000 W48602 Replacement Parts List Replacement Parts List Replacement Parts List Replacement Parts List No A20887A July