LG Electronics RAD-243A, WG1805RY6, WG2405RY6 Troubleshooting Guide, Unit runs but poor cooling

Page 27

Troubleshooting Guide

Troubleshooting Guide

In general, possible trouble is classified in two kinds.

The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application.

Unit runs but poor cooling.

Ineffective Cooling

Check cold air circulation for smooth flow.

Dirty indoor coil (Heat exchanger)

Malfunction of fan

Clogged of air filter.

Obstruction at air outlet

Stop of auto air-swing

Correct above trouble

Check clogging in refrigera- tion circuit.

Repair clogging in refrigera- tion circuit.

Check outdoor coil

(heat exchanger) & the fan operation.

Check gas leakage.

Repair gas leak.

Replacement of unit if the unit is beyond repair.

Satisfactory operation with temperature difference of inlet & outlet air ; 44~50°F(7~10°C)

Check heat load increase.

Unexpected residue

Overloaded circuit

Check inside gas pressure.

Adjusting of refrigerant charged.

Malfunction of compressor.

Replacement of compressor.

Service Manual 26

Image 27
Contents LG Room Air Conditioner Table of Contents Be sure not to do Be sure to follow the instruction Safety PrecautionsThere is risk or fire or electric shock Dimensions Symbols Used in this ManualOutside Dimensions Product Specifications 800/1,850 760/2,710 Select the Best Location InstallationInstallation Check How to Secure the Drain PipeWindow Requirements Installation Kits ContentsPreparation of Chassis Suggested Tool RequirementsCabinet Installation Installation Cooling Only Model FeaturesOperation Control Locations Function of ControlsCooling Only Model with Remote Control and Touch Type WG2405RY6, WG2405RY6WG2405RY6 Cabinet DisassemblyMechanical Parts Front GrilleFan Air Handling PartsCover at the top BlowerCompressor Electrical PartsShroud MotorSynchronous Motor Power CordCapacitor ThermistorRefrigerating Cycle EvaporatorCapillary Tube Disassembly Pulling Vacuum CN-TH1 DiagramModel WG1805RY6 / WG2405RY6 Wiring DiagramComponents Location Main P.W.B Assembly Display P.W.B AssemblyPiping System Troubleshooting GuideUnit runs but poor cooling Troubleshooting GuideFails to Start Possible Trouble Electrical Parts Troubleshooting GuideIC01M 0V? IC01M DC 5V? Delay? IC01M 0V? Possible Trouble 6 Remote controller does not operate Complaint Cause Remedy Room Air Conditioner Voltage LimitsTroubleshooting Guide Troubleshooting Guide Exploded View 130910 135515 135500 554031 148000 W48602 Replacement Parts List Replacement Parts List Replacement Parts List Replacement Parts List No A20887A July