LG Electronics RAD-183A, WG1805RY6, WG2405RY6, RAD-243A service manual Troubleshooting Guide

Page 34

Troubleshooting Guide

COMPLAINT

CAUSE

REMEDY

 

 

 

 

Compressor will not run,

Thermostat

Check the position of knob If not at the coldest set-

but fan motor runs.

 

ting, advance the knob to this setting and restart

 

 

 

unit.

 

 

 

Check continuity of the thermostat. Replace ther-

 

 

 

mostat if circuit is open.

 

 

 

 

 

 

Thermistor

Check the TEMP control. If not at the lowest num-

 

 

 

ber, set TEMP control to this setting and restart

 

 

 

the unit. Check the continuity of the thermistor.

 

 

 

Replace the thermistor if the circuit is open.

 

 

 

 

 

 

Capacitor (Discharge

Check the capacitor.

 

 

capacitor before servicing.)

Replace if not within ±10% of manufacturers rat-

 

 

 

ing. Replace if shorted, open, or damaged.

 

 

 

 

 

 

Compressor

Check the compressor for open circuit or ground. If

 

 

 

open or grounded, replace the compressor.

 

 

 

 

 

 

Overload

Check the compressor overload, if externally

 

 

 

mounted. Replace if open. (If the compressor tem-

 

 

 

perature is high, remove the overload, cool it, and

 

 

 

retest.)

 

 

 

 

Compressor cycles on

Voltage

Check the voltage.

overload.

 

If not within limits, call an electrician.

 

 

 

 

 

 

Overload

Check overload, if externally mounted.

 

 

 

Replace if open. (If the compressor temperature is

 

 

 

high, remove the overload, cool, and retest.)

 

 

 

 

Compressor cycles on

Fan motor

If not running, determine the cause. Replace if

overload.

 

required.

 

 

 

 

 

 

Condenser air flow restric-

Remove the cabinet. inspect the interior surface of

 

 

tion

the condenser; if restricted, clean carefully with a

 

 

 

vacuum cleaner (do not damage fins) or brush.

 

 

 

Clean the interior base before reassembling.

 

 

 

 

 

 

Condenser fins (damaged)

If condenser fins are closed over a large area on

 

 

 

the coil surface, head pressures will increase,

 

 

 

causing the compressor to overload. Straighten

 

 

 

the fins or replace the coil.

 

 

 

Compressor cycles on

Capacitor

Test capacitor.

overload.

Wiring

Check the terminals. If loose, repair or replace.

 

 

 

 

 

 

Refrigerating system

Check the system for a restriction.

 

 

 

Insufficient cooling or heat-

Air filter

If restricted, clean of replace.

ing

 

 

Exhaust damper door

Close if open.

 

 

 

 

 

 

 

 

Unit undersized

Determine if the unit is properly sized for the area

 

 

 

to be cooled.

 

 

 

Excessive noise

Turbo or fan

Check the set screw or clamp. If loose or missing,

 

 

 

correct. If the turbo or fan is hitting air guide,

 

 

 

rearrange the air handling parts.

 

 

 

 

 

 

Copper tubing

Remove the cabinet carefully and rearrange tubing

 

 

 

not to contact cabinet, compressor, shroud, and

 

 

 

barrier.

 

 

 

 

33Room Air Conditioner

Image 34
Contents LG Room Air Conditioner Table of Contents Safety Precautions Be sure not to do Be sure to follow the instructionThere is risk or fire or electric shock Symbols Used in this Manual DimensionsOutside Dimensions Product Specifications 800/1,850 760/2,710 How to Secure the Drain Pipe InstallationInstallation Check Select the Best LocationInstallation Kits Contents Window RequirementsSuggested Tool Requirements Preparation of ChassisCabinet Installation Installation Control Locations Function of Controls FeaturesOperation Cooling Only ModelWG2405RY6, WG2405RY6 Cooling Only Model with Remote Control and Touch TypeWG2405RY6 Front Grille DisassemblyMechanical Parts CabinetBlower Air Handling PartsCover at the top FanMotor Electrical PartsShroud CompressorThermistor Power CordCapacitor Synchronous MotorEvaporator Refrigerating CycleCapillary Tube Disassembly Pulling Vacuum Diagram CN-TH1Wiring Diagram Model WG1805RY6 / WG2405RY6Main P.W.B Assembly Display P.W.B Assembly Components LocationTroubleshooting Guide Piping SystemTroubleshooting Guide Unit runs but poor coolingFails to Start Electrical Parts Troubleshooting Guide Possible TroubleIC01M 0V? IC01M DC 5V? Delay? IC01M 0V? Possible Trouble 6 Remote controller does not operate Room Air Conditioner Voltage Limits Complaint Cause RemedyTroubleshooting Guide Troubleshooting Guide Exploded View 130910 135515 135500 554031 148000 W48602 Replacement Parts List Replacement Parts List Replacement Parts List Replacement Parts List No A20887A July