9.Capacitor

1.Remove the control box. (Refer to section 19)

2.Remove the knobs and the screw that fasten control panel from control box.

3.Remove the screw that located in the front.

4.Open the bottom side of control box.

5.Remove the screw and the clamp that fastens the capacitor.

6.Disconnect all the leads of capacitor terminals.

7.Re-install the components by referring to the removal procedure, above. (See Figure 27)

10.Power Cord

1.Remove the control box. (Refer to section 19)

2.Open the control box. (Refer to section 25)

3.Disconnect the grounding screw from the control box.

4.Disconnect the 2 receptacles.

5.Remove a screw which fastens the clip cord. (See Figure 28)

6.Remove the power cord.

7.Re-install the component by referring to the

above removal procedure, above.

(Use only one ground-marked hole for ground connection.)

8.If the supply cord of this appliance is damaged, it must be replaced by the special cord. (The special cord means the cord that has the same specification marked on the supply cord attached at the unit.)

11.Thermistor

1.Remove the control box. (Refer to section 19)

2.Unfold the control box. (Refer to section 25)

3.Disconnect the themistor terminals from main P.W.B Assembly.

4.Remove the thermistor.

6.Re-install the components by refereing to the above removal procedure above. (See Figure 29)

12.Synchronous Motor

1.Remove the control box. (Refer to section 19)

2.Unfold the control box. (Refer to section 25)

3.Remove the crankshaft.

4.Disconnect all the leads of the synchronous motor.

5.Remove the 2 screws which fasten the syn- chronous motor. (See Figure. 30)

6.Re-install the components by referring to the above removal procedure above.

Disassembly

Figure 27

Figure 28

Figure 29

Figure 30

Service Manual 18

Image 19
Contents LG Room Air Conditioner Table of Contents Be sure not to do Be sure to follow the instruction Safety PrecautionsThere is risk or fire or electric shock Symbols Used in this Manual DimensionsOutside Dimensions Product Specifications 800/1,850 760/2,710 Select the Best Location InstallationInstallation Check How to Secure the Drain PipeWindow Requirements Installation Kits ContentsPreparation of Chassis Suggested Tool RequirementsCabinet Installation Installation Cooling Only Model FeaturesOperation Control Locations Function of ControlsWG2405RY6, WG2405RY6 Cooling Only Model with Remote Control and Touch TypeWG2405RY6 Cabinet DisassemblyMechanical Parts Front GrilleFan Air Handling PartsCover at the top BlowerCompressor Electrical PartsShroud MotorSynchronous Motor Power CordCapacitor ThermistorEvaporator Refrigerating CycleCapillary Tube Disassembly Pulling Vacuum CN-TH1 DiagramModel WG1805RY6 / WG2405RY6 Wiring DiagramComponents Location Main P.W.B Assembly Display P.W.B AssemblyPiping System Troubleshooting GuideUnit runs but poor cooling Troubleshooting GuideFails to Start Possible Trouble Electrical Parts Troubleshooting GuideIC01M 0V? IC01M DC 5V? Delay? IC01M 0V? Possible Trouble 6 Remote controller does not operate Complaint Cause Remedy Room Air Conditioner Voltage LimitsTroubleshooting Guide Troubleshooting Guide Exploded View 130910 135515 135500 554031 148000 W48602 Replacement Parts List Replacement Parts List Replacement Parts List Replacement Parts List No A20887A July