Bissell HS-20 instruction manual Operation, Shutdown Procedure

Page 29

Operation

d.Check inlet and forepressure performance by means of the system instrumentation.

e.During operation, the gas load at the inlet of the diffusion pump should not exceed the maxi- mum throughput capability of the pump. This means that the pressure at the inlet flange should not (except in transient conditions) exceed approximately 1 x 10-3Torr (.133 Pa). Dur- ing operation, the discharge or fore pressure must be below the specified tolerable forepres- sure.

2-2 SHUTDOWN PROCEDURE

WARNING

_____________

Boiler temperatures reach 530°F (275°C) which can cause serious burns when touched. Always ensure surfaces have cooled near room temperature before touching them.

Air release or admitting air to a pump with a hot boiler, especially when it is under vacuum, permits a strong oxidizer to contact the hot pump oil and thereby increases the risk of an explosion.

CAUTION

Do not operate the quick-cool coil when the pump is cold or out of ser- vice to prevent harmful collection of condensation on the boiler plate, heater, and heater terminals.

a.Switch off the power to the diffusion pump heaters.

b.Admit cooling water to the quick-cool coil if necessary and continue to circulate it until the pump body just above the boiler heat shield can be touched (approximately 130°F or 54°C). In valved systems which have tight inlet and foreline connections, it is possible to close valves to isolate the diffusion pump at inlet and discharge, to air-release the remainder of the sys- tem, shut off the heat to the diffusion pump, and stop the mechanical pump. With this method, the quick-cool coil does not have to be used. However, the water flow through the pump must be maintained until the boiler cools down below approximately 300°F (150°C).

2-2

Image 29
Contents HS-20 Diffusion Pump Sales and Service Offices Telephone Numbers Warranty Replacement and Adjustment WarrantyPage Page Iii Prohibited Action Explosion-Causing Condition Prohibited Action Result Page Vii Page Page Section Safety Considerations Section I Installation Table of ContentsList of Tables List of IllustrationsModel Technical Specifications Installation GeneralOperating Specifications See Figure ASA Outline Drawing HS-20 Diffusion Pump, with ASA Flanges Unpacking Cleaning a NEW PumpInstallation Utility and System Connections Safety Considerations and InterlocksVacuum Connections Cooling Water Connections See FigureCooling Water Connections Initial Vacuum Test Thermal Switches240/400/430/440/480 V Wiring Diagram HS-20 Diffusion Pump 415 V Wiring Diagram HS-20 Diffusion Pump Adding Pump Fluid Sight Glass Assembly Operation START-UP ProcedureOperation Shutdown ProcedurePeriodic Inspection Maintenance GeneralCleaning MaintenanceDo not overtighten the screw Disassembling and Reassembling the Cold CAP Refer to FigureExternal Fittings Cold Cap Assembly Disassembling the Lower Jet Assembly JET AssemblyDisassembling the Jet Assembly Refer to Figure Inch Jet Assembly Heater Replacement Maintenance Reassembling the Lower Jet AssemblyReassembling the Jet Assembly Jet Coupling Tighten clamping nuts to 250 in.-lbs Maintenance Replaceable Parts Maintenance Poor Pump or System Performance Troubleshooting LeakageOutgassing Troubleshooting