Page 29

b) Connection to a Closed Loop System

Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" OD copper tubing is recommended for the condenser water supply line.

Condenser return outlet is 3/8" FPT. A minimum of 3/8" OD hard pipe is recommended for the condenser return line.

Shut-off valves and drain valves should be installed at both the condenser water supply inlet and condenser return outlet.

The water supply to the condenser should not drop below 4 GPM.

The pressure differential between the condenser water supply inlet and condenser return outlet must be no less than 10 PSIG.

When using a glycol blend, the solution mixture should be less than 30% glycol.

In order to maintain the proper high side pressure, the condenser water supply inlet temperature should not drop below 45°F (7°C) and the condenser return outlet temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation is complete, confirm the condenser return outlet temperature 5 minutes after a freeze cycle starts. If the outlet temperature is not in the proper range, adjust the waterregulating valve to bring it into range.

FD-1001MWH(-C)

Condenser

Icemaker Water

Condenser

Return Outlet

3/8" FPT

Supply Line

Connection to

 

Drain Valve

a Closed Loop

Icemaker Water

 

Water Supply

 

Supply Line

 

 

Shut-Off Valve

 

Condenser Shut-Off Valves

 

 

To convert to top water supply, install the optional Top Water Supply Kit (HS-2123).

Icemaker Water

Supply Inlet

1/2" FPT

Icemaker Icemaker

Drain Outlet

3/4" FPT

Condenser Drain Valves

Separate piping to approved drain. Leave a 2-inch (5-cm) vertical air gap between the end of each pipe and the drain.

2-inch

(5cm) air gap

Condenser Water

Supply Inlet

1/2" FPT

Bin Drain Outlet 3/4" FPT

Storage Bin

Drain Floor

Fig. 16

29

Image 29
Contents Superior Degree Reliability Hoshizaki AMERICA, INC Contents Page Serious injury Important Safety InformationIndicates important information about the use and care UnitFD-1001MAH-C air-cooled Specifications Nameplate RatingFD-1001MWH-C water-cooled FD-1001MRH-C remote air-cooled FD-1001MLH-C low-side, parallel rack system Dimensions / Connections FD-1001MWH-C water-cooled FD-1001MRH-C remote air-cooled FD-1001MLH-C low side, parallel rack system Checks Before Installation II. Installation and Operating InstructionsHow to Remove Panels See FigLocation SetupAdditional Warnings for Remote Air-Cooled Model Electrical ConnectionFor All Models Location Installation of Remote Condenser UnitChecks Before Installation Line Set SetupField Fabricated Line Set Installation Polyol Ester POE OIL Electrical Connection Stacking Remote Condenser Units Connection to an R-404A Parallel Rack System Line Set InstallationRack System-Braze Connection Entire Male Fitting See , 15, or Water Supply and Drain ConnectionsIcemaker FD-1001MAH-C FD-1001MRH-C FD-1001MLH-CConnection FD-1001MWH-C CondenserTo a Potable Water SupplyClosed Loop FD-1001MWH-CConnection to Final Checklist Startup Infrared Sensor Check Bin Control CheckThumbscrew Infrared Sensor Housing Lens Mechanical Backup Bin Control Check Seconds 1.6 minutes Infrared Sensor Shutdown DelayCleaning and Sanitizing Instructions III. Cleaning and MaintenanceCleaning Solution Cleaning ProcedureFloat Switch Assembly Reservoir Cover Infrared Sensor Infrared Sensor Housing Lens Sanitizing Procedure Initial Sanitizing SolutionSanitizing Procedure Final Frequency Area Task MaintenanceDrain the evaporator Preparing the Icemaker for Long StorageRemove the water from the icemaker water supply line Page Hoshizaki AMERICA, INC