Carrier 19XL specifications Example of Time Schedule Operation Screen

Page 16

3.Press RELEASE to remove the override and return the point to the PIC's automatic control.

Override IndicationÐ An override value is indicated by

``SUPVSR,'' ``SERVC,'' or ``BEST'' ¯ashing next to the point value on the Status table.

TIME SCHEDULE OPERATION (Fig. 16)

1.On the Menu screen, press SCHEDULE .

2.Press NEXT or PREVIOUS to highlight the de- sired schedule.

PSIO Software Version 08 and lower: OCCPC01S Ð LOCAL Time Schedule OCCPC02S Ð CCN Time Schedule

PSIO Software Version 09 and higher:

OCCPC01S Ð LOCAL Time Schedule

OCCPC02S Ð ICE BUILD Time Schedule

OCCPC03-99S Ð CCN Time Schedule (Actual

number is de®ned in

Con®g table.)

3. Press SELECT to access and view the time schedule.

Fig. 16 Ð Example of Time Schedule

Operation Screen

4.Press NEXT or PREVIOUS to highlight the de- sired period or override that you wish to change.

5.Press SELECT to access the highlighted period or override.

6.a. Press INCREASE or DECREASE to change the

time values. Override values are in one-hour incre- ments, up to 4 hours.

b. Press ENABLE to select days in the day-of-week

®elds. Press DISABLE to eliminate days from the period.

7.Press ENTER to register the values and to move horizontally (left to right) within a period.

8.Press EXIT to leave the period or override.

9.Either return to Step 4 to select another period or override, or press EXIT again to leave the current time schedule screen and save the changes.

10.Holiday Designation (HOLIDEF table) may be found in the Service Operation section, page 38. You must assign the month, day, and duration for the holiday. The Broad- cast function in the Brodefs table also must be enabled for holiday periods to function.

16

Image 16
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Contents Introduction Abbreviations and ExplanationsRefrigeration Cycle Chiller FamiliarizationMOTOR/OIL Refrigeration Cooling Cycle 19XL Rear View Take-Apart Rabbet Fit Connector Cooler In/Out Temperature SensorsCondenser In/Out Temperature Sensors Cooler Pressure Schrader FittingLubrication Cycle Refrigerant Motor Cooling and Oil Cooling CyclesLubrication System Starting Equipment Unit-Mounted Solid-State Starter OptionalDenitions ControlsMajor PIC Components Panel Locations PIC Component Panel19XL Controls and Sensor Locations Pressure Transducer, TypicalPower Panel with Options Control and OIL Heater Voltage Selector S1General LID Operation and Menus FigSelect − Example of Point Status Screen Status01 Override OperationsExample of Time Schedule Operation Screen 19XL Menu Structure 19XL Service Menu Structure 19XL Service Menu Structure Setpoint Example of Set Point ScreenDescription Range Units Reference Point Name Alarm History LID ScreensExample 1 Ð STATUS01 Display Screen Menu Status SelectExample 2 Ð STATUS02 Display Screen Example 3 Ð STATUS03 Display ScreenExample 4 Ð Setpoint Display Screen MenuExample 5 Ð Configuration Config Display Screen Example 6 Ð LEAD/LAG Configuration Display ScreenECW Control Option ICE Build TerminationExample 7 Ð SERVICE1 Display Screen Example 8 Ð SERVICE2 Display Screen Spare Alert EnableExample 9 Ð SERVICE3 Display Screen Menu ServiceExample 10 Ð Maintenance MAINT01 Display Screen Example 11 Ð Maintenance MAINT02 Display ScreenDischarge Temperature Bearing TemperatureExample 13 Ð Maintenance MAINT04 Display Screen Example 12 Ð Maintenance MAINT03 Display ScreenDescription RANGE/STATUS Units Reference Point Name PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page Lead/Lag Control ECWHgbp Hot Gas BypassPage Ice Build Control Cent CapacityPage Example of Attach to Network Device Screen To LOG onSTART-UP/SHUTDOWN/RECYCLE Sequence FigRecycle Restart Delta T Using the Optional Storage Tank and Pumpout Before Initial START-UPJob Data Required Equipment Required19XL Leak Test Procedures Page Ð HCFC-22 Pressure Ð Temperature F Ð HCFC-22 Pressure Ð Temperature CÐ HFC-134a Pressure Ð Temperature C Ð HFC-134a Pressure Ð Temperature FTemperature Pressure Page Inspect Wiring Check Optional Pumpout Compressor Water PipCheck Starter MECHANICAL-TYPE StartersBenshaw, Inc. Solid-State Starter Power Stack BENSHAW, INC. SOLID-STATE StarterPower Up the Controls and Check the Oil Heater Set Up Chiller Control CongurationLoad Surge Prevention Occurs TOO Soon Occurs TOO Late Amps Correction Factors For 19XL Motors Volt Motor CodeCharge Refrigerant into Chiller 19XL Chiller Equalization Without PUMP- OUT UnitControl Test Menu Functions Tests to be Devices Tested PerformedRefrigerant Charges 19XL Total Refrigerant ChargeCooler SizeDry Run to Test Start-Up Sequence Initial START-UPCheck Rotation Check Oil Pressure and Compressor Stop Calibrate Motor CurrentOperating Instructions Operator DutiesTo Stop the Chiller Plant Pumpout and Refrigerant Transfer Procedures Operating the Optional Pumpout CompressorTransfer Refrigerant from Storage Tank to Chiller TstatChillers with Isolation Valves Transfer the Refrigerant from Chiller to Storage TankTest After Service, Repair, or Major Leak Ð If General MaintenanceReturn Refrigerant to Normal Operating Conditions Weekly Maintenance Guide Vane Actuator LinkageCheck Safety and Operating Controls Monthly Scheduled MaintenanceTo Change the OIL Compressor Bearing and Gear Mainten Inspect the Heat Exchanger TubesOptional Pumpout System Controls Troubleshooting Guide MAINT01 MAINT02MAINT03 MAINT04Shutdown with ON/OFF/RESET-OFF Timing OUT or Timed OUTNormal or AUTO.-RESTART Recycle ShutdownAutorestart in Progress LOW Chilled Water Normal RUN with RESET, TEMPERATURE, or Demand Compressor Jumpstart and Refrigerant ProtectionOUT-OF-RANGE Sensor Failures Normal RUN Overrides Active AlertsLimited Chiller Protect Limit Faults Protective LimitChiller Alerts Spare Sensor Alert MessagesOther PROBLEMS/MALFUNCTIONS DESCRIPTION/MALFUNCTION Probable CAUSE/REMEDYÐ Thermistor Temperature F vs Resistance/Voltage Drop Temperature Voltage Resistance DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Module Address Control ModulesInput Options Module Processor Module Psio Fig Starter Management Module SMM FigOptions Module Installation Switch Options Setting ModuleTypical Benshaw, Inc. Solid-State Starter internal View Page Page Benshaw, Inc. Solid-State Starter Troubleshooting Guide Problem Probable Causes Area of CorrectionRV1 SCRHeat Exchanger Data Additional Data for Marine WaterboxesCooler CondenserWaterbox Cover Weights CoolersCondensers 1034 kPaCompressor Weights Compressor/Motor WeightsOptional Pumpout System Electrical Data Compressor Fits and Clearances Compressor Assembly Torques Description TorqueFt-lb ``ZCLR COMComm EXTPage CLR Page Chiller Power Panel, Starter Assembly Motor Wiring Schematic Chiller Power Panel, Starter Assembly Motor Wiring Schematic PMR POTGFR HPSTypical Wye-Delta Unit Mounted Starter Wiring Schematic Index Index Copyright 1996 Carrier Corporation

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.