Carrier 19XL specifications Weekly Maintenance, Guide Vane Actuator Linkage

Page 62

HCFC-22 and HFC-134a should not be mixed with air or oxygen and pressurized for leak testing. In gen- eral, neither refrigerant should not be allowed to be pre- sent with high concentrations of air or oxygen above atmospheric pressures, as the mixture can undergo combustion.

REFRIGERANT TRACER Ð Use an environmentally acceptable refrigerant as a tracer for leak test procedures.

TO PRESSURIZE WITH DRY NITROGEN Ð Another method of leak testing is to pressurize with nitrogen only and use a soap bubble solution or an ultrasonic leak detector to determine if leaks are present. This should only be done if all refrigerant has been evacuated from the vessel.

1.Connect a copper tube from the pressure regulator on the cylinder to the refrigerant charging valve. Never apply full cylinder pressure to the pressurizing line. Follow the listed sequence.

2.Open the charging valve fully.

3.Slowly open the cylinder regulating valve.

4.Observe the pressure gage on the chiller and close the regulating valve when the pressure reaches test level. Do not exceed 140 psig (965 kPa).

5.Close the charging valve on the chiller. Remove the cop- per tube if no longer required.

Repair the Leak, Retest, and Apply Standing Vacuum Test Ð After pressurizing the chiller, test for leaks with an electronic, halide leak detector, soap bubble solution, or an ultrasonic leak detector. Bring the chiller back to atmospheric pressure, repair any leaks found, and retest.

After retesting and ®nding no leaks, apply a standing vacuum test, and then dehydrate the chiller. Refer to the Standing Vacuum Test and Chiller Dehydration in the Before Initial Start-Up section, pages 43 and 47.

Checking Guide Vane Linkage Ð When the chiller is off, the guide vanes are closed and the actuator mecha- nism is in the position shown in Fig. 36. If slack develops in the drive chain, backlash can be eliminated as follows:

1.With the machine shut down and the actuator fully closed, remove the chain guard and loosen the actuator bracket holddown bolts.

2.Loosen guide vane sprocket adjusting bolts.

3.Pry bracket upwards to remove slack, then retighten the bracket holddown bolts.

4.Retighten the guide vane sprocket adjusting bolts. Make sure that the guide vane shaft is rotated fully in the clock- wise direction in order for it to be fully closed.

CHECKING THE AUXILIARY SWITCH ON GUIDE VANE ACTUATOR Ð The auxiliary switch used to activate the oil reclaim system solenoids should move to the OPEN posi- tion when the actuator is 70 degrees open. (At this point the guide vanes should be 30 degrees open.)

Trim Refrigerant Charge Ð If it becomes necessary to adjust the refrigerant charge to obtain optimum chiller per- formance, operate the chiller at design load and then add or remove refrigerant slowly until the difference between leav- ing chilled water temperature and the cooler refrigerant tem- perature reaches design conditions or becomes a minimum. Do not overcharge.

Fig. 36 Ð Guide Vane Actuator Linkage

Refrigerant may be added either through the storage tank or directly into the chiller as described in the Charge Refrigerant into Chiller section.

To remove any excess refrigerant, follow the procedure in Transfer Refrigerant from Chiller to Storage Tank section, Steps 1a and b, page 60.

WEEKLY MAINTENANCE

Check the Lubrication System Ð Mark the oil level on the reservoir sight glass, and observe the level each week while the chiller is shut down.

If the level goes below the lower sight glass, the oil reclaim system will need to be checked for proper operation. If additional oil is required, add it through the oil drain charging valve (Fig. 2A or Fig. 2B). A pump is required for adding oil against refrigerant pressure. The oil charge is approximately 8 gallons (30 L). The added oil must meet Carrier speci®cations for the 19XL. Refer to Changing Oil Filter and Oil Changes sections on page 63. Any additional oil that is added should be logged by noting the amount and date. Any oil that is added due to oil loss that is not related to service will eventually return to the sump. It must be removed when the level is high.

A 1200-watt oil heater is controlled by the PIC to main- tain oil temperature (see the Controls section) when the compressor is off. The LID Status02 table displays whether the heater is energized or not. If the PIC shows that the heater is energized, but the sump is not heating up, the power to the oil heater may be off or the oil level may be too low. Check the oil level, the oil heater contactor voltage, and oil heater resistance.

The PIC will not permit compressor start-up if the oil temperature is too low. The control will continue with start-up only after the temperature is within limits.

62

Image 62
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Contents Introduction Abbreviations and ExplanationsMOTOR/OIL Refrigeration Cooling Cycle Chiller FamiliarizationRefrigeration Cycle 19XL Rear View Condenser In/Out Temperature Sensors Take-Apart Rabbet Fit ConnectorCooler In/Out Temperature Sensors Cooler Pressure Schrader FittingLubrication Cycle Refrigerant Motor Cooling and Oil Cooling CyclesLubrication System Starting Equipment Unit-Mounted Solid-State Starter OptionalMajor PIC Components Panel Locations DenitionsControls PIC Component Panel19XL Controls and Sensor Locations Pressure Transducer, TypicalPower Panel with Options Control and OIL Heater Voltage Selector S1Select LID Operation and Menus FigGeneral − Example of Point Status Screen Status01 Override OperationsExample of Time Schedule Operation Screen 19XL Menu Structure 19XL Service Menu Structure 19XL Service Menu Structure Setpoint Example of Set Point ScreenExample 1 Ð STATUS01 Display Screen Description Range Units Reference Point Name Alarm HistoryLID Screens Menu Status SelectExample 4 Ð Setpoint Display Screen Example 2 Ð STATUS02 Display ScreenExample 3 Ð STATUS03 Display Screen MenuECW Control Option Example 5 Ð Configuration Config Display ScreenExample 6 Ð LEAD/LAG Configuration Display Screen ICE Build TerminationExample 7 Ð SERVICE1 Display Screen Example 9 Ð SERVICE3 Display Screen Example 8 Ð SERVICE2 Display ScreenSpare Alert Enable Menu ServiceDischarge Temperature Example 10 Ð Maintenance MAINT01 Display ScreenExample 11 Ð Maintenance MAINT02 Display Screen Bearing TemperatureDescription RANGE/STATUS Units Reference Point Name Example 12 Ð Maintenance MAINT03 Display ScreenExample 13 Ð Maintenance MAINT04 Display Screen PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page Hgbp Lead/Lag ControlECW Hot Gas BypassPage Ice Build Control Cent CapacityPage Example of Attach to Network Device Screen To LOG onSTART-UP/SHUTDOWN/RECYCLE Sequence FigRecycle Restart Delta T Job Data Required Using the Optional Storage Tank and PumpoutBefore Initial START-UP Equipment Required19XL Leak Test Procedures Page Ð HCFC-22 Pressure Ð Temperature F Ð HCFC-22 Pressure Ð Temperature CTemperature Pressure Ð HFC-134a Pressure Ð Temperature FÐ HFC-134a Pressure Ð Temperature C Page Inspect Wiring Check Optional Pumpout Compressor Water PipCheck Starter MECHANICAL-TYPE StartersBenshaw, Inc. Solid-State Starter Power Stack BENSHAW, INC. SOLID-STATE StarterPower Up the Controls and Check the Oil Heater Set Up Chiller Control CongurationLoad Surge Prevention Occurs TOO Soon Occurs TOO Late Amps Correction Factors For 19XL Motors Volt Motor CodeControl Test Menu Functions Charge Refrigerant into Chiller19XL Chiller Equalization Without PUMP- OUT Unit Tests to be Devices Tested PerformedCooler Refrigerant Charges19XL Total Refrigerant Charge SizeCheck Rotation Initial START-UPDry Run to Test Start-Up Sequence Operating Instructions Check Oil Pressure and Compressor StopCalibrate Motor Current Operator DutiesTo Stop the Chiller Plant Transfer Refrigerant from Storage Tank to Chiller Pumpout and Refrigerant Transfer ProceduresOperating the Optional Pumpout Compressor TstatChillers with Isolation Valves Transfer the Refrigerant from Chiller to Storage TankReturn Refrigerant to Normal Operating Conditions General MaintenanceTest After Service, Repair, or Major Leak Ð If Weekly Maintenance Guide Vane Actuator LinkageTo Change the OIL Scheduled MaintenanceCheck Safety and Operating Controls Monthly Compressor Bearing and Gear Mainten Inspect the Heat Exchanger TubesOptional Pumpout System Controls Troubleshooting Guide MAINT03 MAINT01MAINT02 MAINT04Shutdown with ON/OFF/RESET-OFF Timing OUT or Timed OUTAutorestart in Progress Recycle ShutdownNormal or AUTO.-RESTART LOW Chilled Water Normal RUN with RESET, TEMPERATURE, or Demand Compressor Jumpstart and Refrigerant ProtectionLimited Normal RUN Overrides Active AlertsOUT-OF-RANGE Sensor Failures Chiller Protect Limit Faults Protective LimitChiller Alerts Spare Sensor Alert MessagesOther PROBLEMS/MALFUNCTIONS DESCRIPTION/MALFUNCTION Probable CAUSE/REMEDYÐ Thermistor Temperature F vs Resistance/Voltage Drop Temperature Voltage Resistance DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Input Options Module Control ModulesModule Address Options Module Starter Management Module SMM FigProcessor Module Psio Fig Installation Switch Options Setting ModuleTypical Benshaw, Inc. Solid-State Starter internal View Page Page RV1 Benshaw, Inc. Solid-State Starter Troubleshooting GuideProblem Probable Causes Area of Correction SCRCooler Heat Exchanger DataAdditional Data for Marine Waterboxes CondenserCondensers Waterbox Cover WeightsCoolers 1034 kPaOptional Pumpout System Electrical Data Compressor/Motor WeightsCompressor Weights Compressor Fits and Clearances Ft-lb Compressor Assembly TorquesDescription Torque ``ZComm CLRCOM EXTPage CLR Page Chiller Power Panel, Starter Assembly Motor Wiring Schematic Chiller Power Panel, Starter Assembly Motor Wiring Schematic GFR PMRPOT HPSTypical Wye-Delta Unit Mounted Starter Wiring Schematic Index Index Copyright 1996 Carrier Corporation

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.