Carrier Refrigerant Charges, 19XL Total Refrigerant Charge, Cooler, Size, HCFC-22

Page 54

19XL CHILLER EQUALIZATION WITH PUMPOUT UNIT Ð The following procedure describes how to equal- ize refrigerant pressure on an isolated 19XL chiller using the pumpout unit.

1.Access the TERMINATE LOCKOUT mode in the Con- trol Test.

2.Turn on the chilled water and condenser water pumps to prevent possible freezing.

3.Open valve 4 on the pumpout unit and open valves 1a and 1b on the chiller cooler and condenser, Fig. 27 and

28.Slowly open valve 2 on the pumpout unit to equalize the pressure. This process will take approximately

15minutes.

4.Once the pressures have equalized, the discharge isola- tion valve, cooler isolation valve, optional hot gas bypass isolation valve, and the refrigerant isolation valve can be opened. Close valves 1a and 1b, and all pumpout unit valves.

Whenever turning the discharge isolation valve, be sure to reattach the valve locking device. This will prevent the valve from opening or closing during serv- ice work or during chiller operation.

The full refrigerant charge on the 19XL will vary with chiller components and design conditions, indicated on the job data speci®cations. An approximate charge may be found by adding the condenser charge to the cooler charge listed in Table 8.

Always operate the condenser and chilled water pumps during charging operations to prevent freeze-ups. Use the Control Test Terminate Lockout to monitor conditions and start the pumps.

If the chiller has been shipped with a holding charge , the refrigerant will be added through the refrigerant charging valve (Fig. 27 and 28, valve 7) or to the pumpout charging con- nection. First evacuate the nitrogen holding charge from the

vessels. Charge the refrigerant as a gas until the system pres- sure exceeds 68 psig (469 kPa); [35 psig (141 kPa)]. After the chiller is beyond this pressure the refrigerant should be charged as a liquid until all of the recommended refrigerant charge has been added.

TRIMMING REFRIGERANT CHARGE Ð The 19XL is shipped with the correct charge for the design duty of the chiller. Trimming the charge can be best accomplished when design load is available. To trim, check the temperature difference between leaving chilled water temperature and cooler refrigerant temperature at full load design conditions. If necessary, add or remove refrigerant to bring the tempera- ture difference to design conditions or minimum differential.

 

Table 8 Ð Refrigerant Charges*

 

 

 

 

 

 

 

 

 

 

 

19XL TOTAL REFRIGERANT CHARGE

COOLER

 

Design I

 

Design II

 

 

 

Chiller

 

SIZE

 

Chiller

 

 

 

HCFC-22

HFC-134a

 

 

 

 

 

 

lb

kg

lb

kg

lb

kg

40

 

1420

640

1100

499

900

409

41

 

1490

680

1150

522

950

431

42

 

1550

700

1250

568

1000

454

43

 

1600

730

1350

613

1050

477

50

 

1850

840

1500

681

1100

499

51

 

1900

860

1600

726

1200

545

52

 

1980

900

1750

795

1300

590

53

 

2050

930

1850

840

1350

613

55

 

Ð

Ð

1900

863

1550

704

56

 

Ð

Ð

2200

999

1650

749

57

 

Ð

Ð

2500

1135

1750

795

58

 

Ð

Ð

2700

1226

1900

863

*Design I chillers use HCFC-22. Design II chillers use either HCFC-22 or HFC-134a.

NOTES:

1.The size of the cooler determines refrigerant charge for the entire chiller.

2.Design I chillers have ¯oat chambers.

3.Design II chillers have linear ¯oats.

54

Image 54
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Contents Introduction Abbreviations and ExplanationsChiller Familiarization Refrigeration CycleMOTOR/OIL Refrigeration Cooling Cycle 19XL Rear View Condenser In/Out Temperature Sensors Take-Apart Rabbet Fit ConnectorCooler In/Out Temperature Sensors Cooler Pressure Schrader FittingLubrication Cycle Refrigerant Motor Cooling and Oil Cooling CyclesLubrication System Starting Equipment Unit-Mounted Solid-State Starter OptionalMajor PIC Components Panel Locations DenitionsControls PIC Component Panel19XL Controls and Sensor Locations Pressure Transducer, TypicalPower Panel with Options Control and OIL Heater Voltage Selector S1LID Operation and Menus Fig GeneralSelect − Example of Point Status Screen Status01 Override OperationsExample of Time Schedule Operation Screen 19XL Menu Structure 19XL Service Menu Structure 19XL Service Menu Structure Setpoint Example of Set Point ScreenExample 1 Ð STATUS01 Display Screen Description Range Units Reference Point Name Alarm HistoryLID Screens Menu Status SelectExample 4 Ð Setpoint Display Screen Example 2 Ð STATUS02 Display ScreenExample 3 Ð STATUS03 Display Screen MenuECW Control Option Example 5 Ð Configuration Config Display ScreenExample 6 Ð LEAD/LAG Configuration Display Screen ICE Build TerminationExample 7 Ð SERVICE1 Display Screen Example 9 Ð SERVICE3 Display Screen Example 8 Ð SERVICE2 Display ScreenSpare Alert Enable Menu ServiceDischarge Temperature Example 10 Ð Maintenance MAINT01 Display ScreenExample 11 Ð Maintenance MAINT02 Display Screen Bearing TemperatureExample 12 Ð Maintenance MAINT03 Display Screen Example 13 Ð Maintenance MAINT04 Display ScreenDescription RANGE/STATUS Units Reference Point Name PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page Hgbp Lead/Lag ControlECW Hot Gas BypassPage Ice Build Control Cent CapacityPage Example of Attach to Network Device Screen To LOG onSTART-UP/SHUTDOWN/RECYCLE Sequence FigRecycle Restart Delta T Job Data Required Using the Optional Storage Tank and PumpoutBefore Initial START-UP Equipment Required19XL Leak Test Procedures Page Ð HCFC-22 Pressure Ð Temperature F Ð HCFC-22 Pressure Ð Temperature CÐ HFC-134a Pressure Ð Temperature F Ð HFC-134a Pressure Ð Temperature CTemperature Pressure Page Inspect Wiring Check Optional Pumpout Compressor Water PipCheck Starter MECHANICAL-TYPE StartersBenshaw, Inc. Solid-State Starter Power Stack BENSHAW, INC. SOLID-STATE StarterPower Up the Controls and Check the Oil Heater Set Up Chiller Control CongurationLoad Surge Prevention Occurs TOO Soon Occurs TOO Late Amps Correction Factors For 19XL Motors Volt Motor CodeControl Test Menu Functions Charge Refrigerant into Chiller19XL Chiller Equalization Without PUMP- OUT Unit Tests to be Devices Tested PerformedCooler Refrigerant Charges19XL Total Refrigerant Charge SizeInitial START-UP Dry Run to Test Start-Up SequenceCheck Rotation Operating Instructions Check Oil Pressure and Compressor StopCalibrate Motor Current Operator DutiesTo Stop the Chiller Plant Transfer Refrigerant from Storage Tank to Chiller Pumpout and Refrigerant Transfer ProceduresOperating the Optional Pumpout Compressor TstatChillers with Isolation Valves Transfer the Refrigerant from Chiller to Storage TankGeneral Maintenance Test After Service, Repair, or Major Leak Ð IfReturn Refrigerant to Normal Operating Conditions Weekly Maintenance Guide Vane Actuator LinkageScheduled Maintenance Check Safety and Operating Controls MonthlyTo Change the OIL Compressor Bearing and Gear Mainten Inspect the Heat Exchanger TubesOptional Pumpout System Controls Troubleshooting Guide MAINT03 MAINT01MAINT02 MAINT04Shutdown with ON/OFF/RESET-OFF Timing OUT or Timed OUTRecycle Shutdown Normal or AUTO.-RESTARTAutorestart in Progress LOW Chilled Water Normal RUN with RESET, TEMPERATURE, or Demand Compressor Jumpstart and Refrigerant ProtectionNormal RUN Overrides Active Alerts OUT-OF-RANGE Sensor FailuresLimited Chiller Protect Limit Faults Protective LimitChiller Alerts Spare Sensor Alert MessagesOther PROBLEMS/MALFUNCTIONS DESCRIPTION/MALFUNCTION Probable CAUSE/REMEDYÐ Thermistor Temperature F vs Resistance/Voltage Drop Temperature Voltage Resistance DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Control Modules Module AddressInput Options Module Starter Management Module SMM Fig Processor Module Psio FigOptions Module Installation Switch Options Setting ModuleTypical Benshaw, Inc. Solid-State Starter internal View Page Page RV1 Benshaw, Inc. Solid-State Starter Troubleshooting GuideProblem Probable Causes Area of Correction SCRCooler Heat Exchanger DataAdditional Data for Marine Waterboxes CondenserCondensers Waterbox Cover WeightsCoolers 1034 kPaCompressor/Motor Weights Compressor WeightsOptional Pumpout System Electrical Data Compressor Fits and Clearances Ft-lb Compressor Assembly TorquesDescription Torque ``ZComm CLRCOM EXTPage CLR Page Chiller Power Panel, Starter Assembly Motor Wiring Schematic Chiller Power Panel, Starter Assembly Motor Wiring Schematic GFR PMRPOT HPSTypical Wye-Delta Unit Mounted Starter Wiring Schematic Index Index Copyright 1996 Carrier Corporation

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.