Carrier 19XL specifications Control Modules, Module Address, Input Options Module

Page 78

Control Modules

Turn controller power off before servicing controls. This ensures safety and prevents damage to controller.

The Processor module (PSIO), 8-input (Options) mod- ules, Starter Management Module (SMM), and the Local Interface Device (LID) module perform continuous di- agnostic evaluations of the hardware to determine its con- dition. See Fig. 39-43. Proper operation of all modules is indicated by LEDs (light-emitting diodes) located on the side of the LID, and on the top horizontal surface of the PSIO, SMM, and 8-input modules.

RED LED Ð If the LED is blinking continuously at a 2-second rate, it is indicating proper operation. If it is lit continuously it indicates a problem requiring replacement of the module. Off continuously indicates that the power should be checked. If the red LED blinks 3 times per sec- ond, a software error has been discovered and the module must be replaced. If there is no input power, check fuses and the circuit breaker. If fuse is good, check for shorted sec- ondary of transformer, or if power is present to the module, replace the module.

GREEN LEDs Ð There are one or 2 green LEDs on each type of module. These LEDs indicate communication status between different parts of the controller and the network mod- ules as follows:

LID Module

Upper LED Ð Communication with CCN network, if present; blinks when communication occurs.

Lower LED Ð Communication with PSIO module; must blink every 5 to 8 seconds when the LID default screen is displayed.

PSIO Module

Green LED Closest to Communications Connection Ð Com- munication with SMM and 8-input module; must blink continuously.

Other Green LED Ð Communication with LID; must blink every 3 to 5 seconds.

8-Input Modules and SMM

Green LED Ð Communication with PSIO module; will blink continuously.

Notes on Module Operation

1.The chiller operator monitors and modi®es con®gura- tions in the microprocessor through the 4 softkeys and the LID. Communication with the LID and the PSIO is accomplished through the CCN bus. The communication between the PSIO, SMM, and both 8-input modules is accomplished through the sensor bus, which is a 3-wire cable.

On sensor bus terminal strips, Terminal 1 of PSIO mod- ule is connected to Terminal 1 of each of the other modules. Terminals 2 and 3 are connected in the same manner. See Fig. 39-43. If a Terminal 2 wire is connected to Terminal 1, the system does not work.

2.If a green LED is solid on, check communication wiring. If a green LED is off, check the red LED operation. If the

red LED is normal, check the module address switches (Fig. 39-43). Proper addresses are:

MODULE

ADDRESS

S1

S2

 

SMM (Starter Management Module)

3

2

8-input Options Module 1

6

4

8-input Options Module 2

7

2

If all modules indicate communications failure, check com- munications plug on the PSIO module for proper seating. Also check the wiring (CCN bus Ð 1:red, 2:wht, 3:blk; Sensor bus Ð 1:red, 2:blk, 3:clr/wht). If a good connec- tion is assured and the condition persists, replace the PSIO module.

If only one 8-input module or SMM indicates commu- nication failure, check the communications plug on that module. If a good connection is assured and the condi- tion persists, replace the module.

All system operating intelligence rests in the PSIO mod- ule. Some safety shutdown logic resides in the SMM in case communications are lost between the 2 modules. The PSIO monitors conditions using input ports on the PSIO, the SMM, and the 8-input modules. Outputs are con- trolled by the PSIO and SMM as well.

3.Power is supplied to modules within the control panel via 21-vac power sources.

The transformers are located within the power panel, with the exception of the SMM, which operates from a 24-vac power source and has its own 24-vac transformer located within the starter.

Within the power panel, T1 supplies power to the LID, the PSIO, and the 5-vac power supply for the transduc- ers. The other 21-vac transformer is T4, which supplies power to both 8-input modules (if present). T4 is capable of supplying power to two modules; if additional mod- ules are added, another power supply will be required.

Power is connected to Terminals 1 and 2 of the power input connection on each module.

Fig. 39 Ð PSIO Module Address Selector Switch

Locations and LED Locations

78

Image 78
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Contents Introduction Abbreviations and ExplanationsChiller Familiarization Refrigeration CycleMOTOR/OIL Refrigeration Cooling Cycle 19XL Rear View Condenser In/Out Temperature Sensors Take-Apart Rabbet Fit ConnectorCooler In/Out Temperature Sensors Cooler Pressure Schrader FittingLubrication Cycle Refrigerant Motor Cooling and Oil Cooling CyclesLubrication System Starting Equipment Unit-Mounted Solid-State Starter OptionalMajor PIC Components Panel Locations DenitionsControls PIC Component Panel19XL Controls and Sensor Locations Pressure Transducer, TypicalPower Panel with Options Control and OIL Heater Voltage Selector S1LID Operation and Menus Fig GeneralSelect − Example of Point Status Screen Status01 Override OperationsExample of Time Schedule Operation Screen 19XL Menu Structure 19XL Service Menu Structure 19XL Service Menu Structure Setpoint Example of Set Point ScreenExample 1 Ð STATUS01 Display Screen Description Range Units Reference Point Name Alarm HistoryLID Screens Menu Status SelectExample 4 Ð Setpoint Display Screen Example 2 Ð STATUS02 Display ScreenExample 3 Ð STATUS03 Display Screen MenuECW Control Option Example 5 Ð Configuration Config Display ScreenExample 6 Ð LEAD/LAG Configuration Display Screen ICE Build TerminationExample 7 Ð SERVICE1 Display Screen Example 9 Ð SERVICE3 Display Screen Example 8 Ð SERVICE2 Display ScreenSpare Alert Enable Menu ServiceDischarge Temperature Example 10 Ð Maintenance MAINT01 Display ScreenExample 11 Ð Maintenance MAINT02 Display Screen Bearing TemperatureExample 12 Ð Maintenance MAINT03 Display Screen Example 13 Ð Maintenance MAINT04 Display ScreenDescription RANGE/STATUS Units Reference Point Name PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page Hgbp Lead/Lag ControlECW Hot Gas BypassPage Ice Build Control Cent CapacityPage Example of Attach to Network Device Screen To LOG onSTART-UP/SHUTDOWN/RECYCLE Sequence FigRecycle Restart Delta T Job Data Required Using the Optional Storage Tank and PumpoutBefore Initial START-UP Equipment Required19XL Leak Test Procedures Page Ð HCFC-22 Pressure Ð Temperature F Ð HCFC-22 Pressure Ð Temperature CÐ HFC-134a Pressure Ð Temperature F Ð HFC-134a Pressure Ð Temperature CTemperature Pressure Page Inspect Wiring Check Optional Pumpout Compressor Water PipCheck Starter MECHANICAL-TYPE StartersBenshaw, Inc. Solid-State Starter Power Stack BENSHAW, INC. SOLID-STATE StarterPower Up the Controls and Check the Oil Heater Set Up Chiller Control CongurationLoad Surge Prevention Occurs TOO Soon Occurs TOO Late Amps Correction Factors For 19XL Motors Volt Motor CodeControl Test Menu Functions Charge Refrigerant into Chiller19XL Chiller Equalization Without PUMP- OUT Unit Tests to be Devices Tested PerformedCooler Refrigerant Charges19XL Total Refrigerant Charge SizeInitial START-UP Dry Run to Test Start-Up SequenceCheck Rotation Operating Instructions Check Oil Pressure and Compressor StopCalibrate Motor Current Operator DutiesTo Stop the Chiller Plant Transfer Refrigerant from Storage Tank to Chiller Pumpout and Refrigerant Transfer ProceduresOperating the Optional Pumpout Compressor TstatChillers with Isolation Valves Transfer the Refrigerant from Chiller to Storage TankGeneral Maintenance Test After Service, Repair, or Major Leak Ð IfReturn Refrigerant to Normal Operating Conditions Weekly Maintenance Guide Vane Actuator LinkageScheduled Maintenance Check Safety and Operating Controls MonthlyTo Change the OIL Compressor Bearing and Gear Mainten Inspect the Heat Exchanger TubesOptional Pumpout System Controls Troubleshooting Guide MAINT03 MAINT01MAINT02 MAINT04Shutdown with ON/OFF/RESET-OFF Timing OUT or Timed OUTRecycle Shutdown Normal or AUTO.-RESTARTAutorestart in Progress LOW Chilled Water Normal RUN with RESET, TEMPERATURE, or Demand Compressor Jumpstart and Refrigerant ProtectionNormal RUN Overrides Active Alerts OUT-OF-RANGE Sensor FailuresLimited Chiller Protect Limit Faults Protective LimitChiller Alerts Spare Sensor Alert MessagesOther PROBLEMS/MALFUNCTIONS DESCRIPTION/MALFUNCTION Probable CAUSE/REMEDYÐ Thermistor Temperature F vs Resistance/Voltage Drop Temperature Voltage Resistance DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Control Modules Module AddressInput Options Module Starter Management Module SMM Fig Processor Module Psio FigOptions Module Installation Switch Options Setting ModuleTypical Benshaw, Inc. Solid-State Starter internal View Page Page RV1 Benshaw, Inc. Solid-State Starter Troubleshooting GuideProblem Probable Causes Area of Correction SCRCooler Heat Exchanger DataAdditional Data for Marine Waterboxes CondenserCondensers Waterbox Cover WeightsCoolers 1034 kPaCompressor/Motor Weights Compressor WeightsOptional Pumpout System Electrical Data Compressor Fits and Clearances Ft-lb Compressor Assembly TorquesDescription Torque ``ZComm CLRCOM EXTPage CLR Page Chiller Power Panel, Starter Assembly Motor Wiring Schematic Chiller Power Panel, Starter Assembly Motor Wiring Schematic GFR PMRPOT HPSTypical Wye-Delta Unit Mounted Starter Wiring Schematic Index Index Copyright 1996 Carrier Corporation

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.