Carrier 19XL specifications Capacity Overrides

Page 31

Ramp Loading Control Ð The ramp loading control slows down the rate at which the compressor loads up. This control can prevent the compressor from loading up during the short period of time when the chiller is started, and the chilled water loop has to be brought down to normal design conditions. This helps reduce electrical demand charges by slowly bringing the chilled water to control point. However, the total power draw during this period remains almost unchanged.

There are 2 methods of ramp loading with the PIC. Ramp loading can be based on chilled water temperature or on mo- tor load.

1.Temperature ramp loading limits the rate at which either leaving chilled water or entering chilled water temper- ature decreases by an operator-con®gured rate. The low- est temperature ramp table will be used the ®rst time the chiller is started (at commissioning). The lowest tem- perature ramp rate will also be used if chiller power has been off for 3 hours or more (even if the motor ramp load is selected).

2.Motor load ramp loading limits the rate at which the compressor motor current or compressor motor load increases by an operator-con®gured rate.

The TEMP (Temperature) PULLDOWN, LOAD PULL DOWN, and SELECT RAMP TYPE may be viewed/modified

on the LID Equipment Con®guration table, Con®g table (see Table 2). Motor load is the default type.

Capacity Override (Table 4) Ð Capacity overrides can prevent some safety shutdowns caused by exceeding motor amperage limit, refrigerant low temperature safety limit, motor high temperature safety limit, and condenser high pres- sure limit. In all cases there are 2 stages of compressor vane control.

1.The vanes are held from opening further, and the status line on the LID indicates the reason for the override.

2.The vanes are closed until condition decreases below the ®rst step set point, and then the vanes are released to nor- mal capacity control.

Whenever the motor current demand limit set point is reached, it activates a capacity override, again with a 2-step process. Exceeding 110% of the rated load amps for more than 30 seconds will initiate a safety shutdown.

The compressor high lift (surge prevention) set point will cause a capacity override as well. When the surge preven- tion set point is reached, the controller normally will only hold the guide vanes from opening. If so equipped, the hot gas bypass valve will open instead of holding the vanes.

Table 4 Ð Capacity Overrides

 

 

 

 

 

 

 

SECOND

OVERRIDE

 

 

 

FIRST STAGE SET POINT

 

STAGE

OVERRIDE

 

 

 

TERMINATION

 

 

 

 

 

 

SET POINT

CAPACITY

 

 

 

 

 

 

 

CONTROL

View/Modify

 

 

 

 

 

 

 

on

Default Value

Con®gurable Range

Value

Value

 

 

LID Screen

 

 

 

 

 

 

 

HIGH

 

HCFC-22

 

HFC-134a

HCFC-22

HFC-134a

.Override

 

Equipment

 

 

 

 

 

Set Point

,Override

CONDENSER

.195 psig

 

125 psig

150 to 245 psig

90 to 200 psig

Service1

 

+ 4 psig

Set Point

PRESSURE

 

 

(1345 kPa)

 

(862 kPa)

(1034 to 1689 kPa)

(620 to 1379 kPa)

(28 kPa)

 

 

 

 

 

HIGH MOTOR

 

 

 

 

 

 

.Override

 

Equipment

.200 F (93.3 C)

150 to 200 F (66 to 93 C)

Set Point

,Override

TEMPERATURE

Service1

+10° F

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

(6° C)

 

LOW

 

 

 

 

 

 

 

 

REFRIGERANT

 

 

 

 

 

 

<Trippoint

.Trippoint

TEMPERATURE

Equipment

,3° F (1.6° C)

2° to 5° F

+ Override

+ Override

(Refrigerant

Service1

(Above Trippoint)

(1° to 3° C)

DT ±1° F

DT +2° F

Override Delta

 

 

 

 

 

 

(0.56° C)

(1.2° C)

Temperature)

 

 

 

 

 

 

 

 

 

 

HCFC-22

 

HFC-134a

HCFC-22

HFC-134a

 

 

 

 

Minimum:

 

Minimum:

 

 

 

 

HIGH

 

T1 Ð 1.5° F

 

T1 Ð 1.5° F

0.5° to 15° F

0.5° to 15° F

 

Within

 

(0.8° C)

 

(0.8° C)

(0.3° to 8.3° C)

(0.3° to 8.3° C)

 

 

 

 

Lift Limits

COMPRESSOR

Equipment

P1 Ð 75 psid

 

P1 Ð 50 psid

50 to 170 psid

30 to 170 psid

 

 

 

Plus Surge/

LIFT

(517 kPad)

 

(345 kPad)

(345 to 1172 kPad)

(207 to 1172 kPad)

None

Service1

 

HGBP

(Surge

Maximum:

 

Maximum:

 

 

 

 

 

 

 

 

Deadband

Prevention)

 

T2 Ð 10° F

 

T2 Ð 10° F

0.5° to 15° F

0.5° to 15° F

 

 

 

 

Setting

 

 

(5.6° C)

 

(5.6° C)

(0.3° to 8.3° C)

(0.3° to 8.3° C)

 

 

 

 

 

 

 

 

P2 Ð 170 psid

 

P2 Ð 85 psid

50 to 170 psid

30 to 170 psid

 

 

 

 

(1172 kPad)

 

(586 kPad)

(345 to 1172 kPad)

(207 to 1172 kPad)

 

 

MANUAL

Control

 

 

 

 

 

 

Release of

GUIDE VANE

Algorithm

Automatic

0 to 100%

None

Manual

TARGET

Maint01

 

 

 

 

 

 

Control

MOTOR LOAD Ð

 

 

 

 

 

 

>5% of

2% Lower

ACTIVE

Status01

100%

40 to 100%

Than

Set Point

DEMAND LIMIT

 

 

 

 

 

 

Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

Image 31
Contents Safety Considerations Start-Up, Operation, and Maintenance InstructionsContents Contents Abbreviations and Explanations IntroductionRefrigeration Cycle Chiller FamiliarizationMOTOR/OIL Refrigeration Cooling Cycle 19XL Rear View Cooler Pressure Schrader Fitting Take-Apart Rabbet Fit ConnectorCooler In/Out Temperature Sensors Condenser In/Out Temperature SensorsRefrigerant Motor Cooling and Oil Cooling Cycles Lubrication CycleLubrication System Unit-Mounted Solid-State Starter Optional Starting EquipmentPIC Component Panel DenitionsControls Major PIC Components Panel LocationsPressure Transducer, Typical 19XL Controls and Sensor LocationsControl and OIL Heater Voltage Selector S1 Power Panel with OptionsGeneral LID Operation and Menus FigSelect Override Operations − Example of Point Status Screen Status01Example of Time Schedule Operation Screen 19XL Menu Structure 19XL Service Menu Structure 19XL Service Menu Structure Example of Set Point Screen SetpointMenu Status Select Description Range Units Reference Point Name Alarm HistoryLID Screens Example 1 Ð STATUS01 Display ScreenMenu Example 2 Ð STATUS02 Display ScreenExample 3 Ð STATUS03 Display Screen Example 4 Ð Setpoint Display ScreenICE Build Termination Example 5 Ð Configuration Config Display ScreenExample 6 Ð LEAD/LAG Configuration Display Screen ECW Control OptionExample 7 Ð SERVICE1 Display Screen Menu Service Example 8 Ð SERVICE2 Display ScreenSpare Alert Enable Example 9 Ð SERVICE3 Display ScreenBearing Temperature Example 10 Ð Maintenance MAINT01 Display ScreenExample 11 Ð Maintenance MAINT02 Display Screen Discharge TemperatureExample 13 Ð Maintenance MAINT04 Display Screen Example 12 Ð Maintenance MAINT03 Display ScreenDescription RANGE/STATUS Units Reference Point Name PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page Hot Gas Bypass Lead/Lag ControlECW HgbpPage Cent Capacity Ice Build ControlPage To LOG on Example of Attach to Network Device ScreenSequence Fig START-UP/SHUTDOWN/RECYCLERecycle Restart Delta T Equipment Required Using the Optional Storage Tank and PumpoutBefore Initial START-UP Job Data Required19XL Leak Test Procedures Page Ð HCFC-22 Pressure Ð Temperature C Ð HCFC-22 Pressure Ð Temperature FÐ HFC-134a Pressure Ð Temperature C Ð HFC-134a Pressure Ð Temperature FTemperature Pressure Page Check Optional Pumpout Compressor Water Pip Inspect WiringMECHANICAL-TYPE Starters Check StarterBENSHAW, INC. SOLID-STATE Starter Benshaw, Inc. Solid-State Starter Power StackSet Up Chiller Control Conguration Power Up the Controls and Check the Oil HeaterLoad Surge Prevention Occurs TOO Soon Occurs TOO Late Volt Motor Code Amps Correction Factors For 19XL MotorsTests to be Devices Tested Performed Charge Refrigerant into Chiller19XL Chiller Equalization Without PUMP- OUT Unit Control Test Menu FunctionsSize Refrigerant Charges19XL Total Refrigerant Charge CoolerDry Run to Test Start-Up Sequence Initial START-UPCheck Rotation Operator Duties Check Oil Pressure and Compressor StopCalibrate Motor Current Operating InstructionsTo Stop the Chiller Plant Tstat Pumpout and Refrigerant Transfer ProceduresOperating the Optional Pumpout Compressor Transfer Refrigerant from Storage Tank to ChillerTransfer the Refrigerant from Chiller to Storage Tank Chillers with Isolation ValvesTest After Service, Repair, or Major Leak Ð If General MaintenanceReturn Refrigerant to Normal Operating Conditions Guide Vane Actuator Linkage Weekly MaintenanceCheck Safety and Operating Controls Monthly Scheduled MaintenanceTo Change the OIL Inspect the Heat Exchanger Tubes Compressor Bearing and Gear MaintenOptional Pumpout System Controls Troubleshooting Guide MAINT04 MAINT01MAINT02 MAINT03Timing OUT or Timed OUT Shutdown with ON/OFF/RESET-OFFNormal or AUTO.-RESTART Recycle ShutdownAutorestart in Progress LOW Chilled Water Compressor Jumpstart and Refrigerant Protection Normal RUN with RESET, TEMPERATURE, or DemandOUT-OF-RANGE Sensor Failures Normal RUN Overrides Active AlertsLimited Protective Limit Chiller Protect Limit FaultsSpare Sensor Alert Messages Chiller AlertsDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY Other PROBLEMS/MALFUNCTIONSTemperature Voltage Resistance Drop Ð Thermistor Temperature F vs Resistance/Voltage DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Module Address Control ModulesInput Options Module Processor Module Psio Fig Starter Management Module SMM FigOptions Module Switch Options Setting Module InstallationTypical Benshaw, Inc. Solid-State Starter internal View Page Page SCR Benshaw, Inc. Solid-State Starter Troubleshooting GuideProblem Probable Causes Area of Correction RV1Condenser Heat Exchanger DataAdditional Data for Marine Waterboxes Cooler1034 kPa Waterbox Cover WeightsCoolers CondensersCompressor Weights Compressor/Motor WeightsOptional Pumpout System Electrical Data Compressor Fits and Clearances ``Z Compressor Assembly TorquesDescription Torque Ft-lbEXT CLRCOM CommPage CLR Page Chiller Power Panel, Starter Assembly Motor Wiring Schematic Chiller Power Panel, Starter Assembly Motor Wiring Schematic HPS PMRPOT GFRTypical Wye-Delta Unit Mounted Starter Wiring Schematic Index Index Copyright 1996 Carrier Corporation

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.