Page 20

TO VIEW AND CHANGE SET POINTS (Fig. 19)

1.To view the Set Point table, at the Menu screen press

SETPOINT .

2.There are 4 set points on this screen: Base Demand Limit; LCW Set Point (leaving chilled water set point); ECW Set Point (entering chilled water set point); and ICE BUILD set point (PSIO Software Version 09 and higher only). Only one of the chilled water set points can be active at one time, and the type of set point is activated in the Serv- ice menu. ICE BUILD is also activated and con®gured in the Service menu.

Fig. 19 Ð Example of Set Point Screen

3.Press NEXT or PREVIOUS to highlight the desired set point entry.

4.Press SELECT to modify the highlighted set point.

5.Press INCREASE or DECREASE to change the se- lected set point value.

6.Press ENTER to save the changes and return to the previous screen.

SERVICE OPERATION Ð To view the menu-driven pro- grams available for Service Operation, see Service Opera- tion section, page 38. For examples of LID display screens, see Table 2.

20

Image 20
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Contents Introduction Abbreviations and ExplanationsMOTOR/OIL Refrigeration Cooling Cycle Chiller FamiliarizationRefrigeration Cycle 19XL Rear View Take-Apart Rabbet Fit Connector Cooler In/Out Temperature SensorsCondenser In/Out Temperature Sensors Cooler Pressure Schrader FittingLubrication Cycle Refrigerant Motor Cooling and Oil Cooling CyclesLubrication System Starting Equipment Unit-Mounted Solid-State Starter OptionalDenitions ControlsMajor PIC Components Panel Locations PIC Component Panel19XL Controls and Sensor Locations Pressure Transducer, TypicalPower Panel with Options Control and OIL Heater Voltage Selector S1Select LID Operation and Menus FigGeneral − Example of Point Status Screen Status01 Override OperationsExample of Time Schedule Operation Screen 19XL Menu Structure 19XL Service Menu Structure 19XL Service Menu Structure Setpoint Example of Set Point ScreenDescription Range Units Reference Point Name Alarm History LID ScreensExample 1 Ð STATUS01 Display Screen Menu Status SelectExample 2 Ð STATUS02 Display Screen Example 3 Ð STATUS03 Display ScreenExample 4 Ð Setpoint Display Screen MenuExample 5 Ð Configuration Config Display Screen Example 6 Ð LEAD/LAG Configuration Display ScreenECW Control Option ICE Build TerminationExample 7 Ð SERVICE1 Display Screen Example 8 Ð SERVICE2 Display Screen Spare Alert EnableExample 9 Ð SERVICE3 Display Screen Menu ServiceExample 10 Ð Maintenance MAINT01 Display Screen Example 11 Ð Maintenance MAINT02 Display ScreenDischarge Temperature Bearing TemperatureDescription RANGE/STATUS Units Reference Point Name Example 12 Ð Maintenance MAINT03 Display ScreenExample 13 Ð Maintenance MAINT04 Display Screen PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page Lead/Lag Control ECWHgbp Hot Gas BypassPage Ice Build Control Cent CapacityPage Example of Attach to Network Device Screen To LOG onSTART-UP/SHUTDOWN/RECYCLE Sequence FigRecycle Restart Delta T Using the Optional Storage Tank and Pumpout Before Initial START-UPJob Data Required Equipment Required19XL Leak Test Procedures Page Ð HCFC-22 Pressure Ð Temperature F Ð HCFC-22 Pressure Ð Temperature CTemperature Pressure Ð HFC-134a Pressure Ð Temperature FÐ HFC-134a Pressure Ð Temperature C Page Inspect Wiring Check Optional Pumpout Compressor Water PipCheck Starter MECHANICAL-TYPE StartersBenshaw, Inc. Solid-State Starter Power Stack BENSHAW, INC. SOLID-STATE StarterPower Up the Controls and Check the Oil Heater Set Up Chiller Control CongurationLoad Surge Prevention Occurs TOO Soon Occurs TOO Late Amps Correction Factors For 19XL Motors Volt Motor CodeCharge Refrigerant into Chiller 19XL Chiller Equalization Without PUMP- OUT UnitControl Test Menu Functions Tests to be Devices Tested PerformedRefrigerant Charges 19XL Total Refrigerant ChargeCooler SizeCheck Rotation Initial START-UPDry Run to Test Start-Up Sequence Check Oil Pressure and Compressor Stop Calibrate Motor CurrentOperating Instructions Operator DutiesTo Stop the Chiller Plant Pumpout and Refrigerant Transfer Procedures Operating the Optional Pumpout CompressorTransfer Refrigerant from Storage Tank to Chiller TstatChillers with Isolation Valves Transfer the Refrigerant from Chiller to Storage TankReturn Refrigerant to Normal Operating Conditions General MaintenanceTest After Service, Repair, or Major Leak Ð If Weekly Maintenance Guide Vane Actuator LinkageTo Change the OIL Scheduled MaintenanceCheck Safety and Operating Controls Monthly Compressor Bearing and Gear Mainten Inspect the Heat Exchanger TubesOptional Pumpout System Controls Troubleshooting Guide MAINT01 MAINT02MAINT03 MAINT04Shutdown with ON/OFF/RESET-OFF Timing OUT or Timed OUTAutorestart in Progress Recycle ShutdownNormal or AUTO.-RESTART LOW Chilled Water Normal RUN with RESET, TEMPERATURE, or Demand Compressor Jumpstart and Refrigerant ProtectionLimited Normal RUN Overrides Active AlertsOUT-OF-RANGE Sensor Failures Chiller Protect Limit Faults Protective LimitChiller Alerts Spare Sensor Alert MessagesOther PROBLEMS/MALFUNCTIONS DESCRIPTION/MALFUNCTION Probable CAUSE/REMEDYÐ Thermistor Temperature F vs Resistance/Voltage Drop Temperature Voltage Resistance DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Input Options Module Control ModulesModule Address Options Module Starter Management Module SMM FigProcessor Module Psio Fig Installation Switch Options Setting ModuleTypical Benshaw, Inc. Solid-State Starter internal View Page Page Benshaw, Inc. Solid-State Starter Troubleshooting Guide Problem Probable Causes Area of CorrectionRV1 SCRHeat Exchanger Data Additional Data for Marine WaterboxesCooler CondenserWaterbox Cover Weights CoolersCondensers 1034 kPaOptional Pumpout System Electrical Data Compressor/Motor WeightsCompressor Weights Compressor Fits and Clearances Compressor Assembly Torques Description TorqueFt-lb ``ZCLR COMComm EXTPage CLR Page Chiller Power Panel, Starter Assembly Motor Wiring Schematic Chiller Power Panel, Starter Assembly Motor Wiring Schematic PMR POTGFR HPSTypical Wye-Delta Unit Mounted Starter Wiring Schematic Index Index Copyright 1996 Carrier Corporation

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.