Carrier 19XL specifications Check Starter, MECHANICAL-TYPE Starters

Page 48

6.Be sure that fused disconnects or circuit breakers have been supplied for the oil pump, power panel, and pumpout unit.

7.Check that all electrical equipment and controls are prop- erly grounded in accordance with job drawings, certi- ®ed drawings, and all applicable electrical codes.

8.Make sure that the customer's contractor has veri®ed proper operation of the pumps, cooling tower fans, and associated auxiliary equipment. This includes ensuring that motors are properly lubricated and have proper elec- trical supply and proper rotation.

9.For ®eld-installed starters only, test the chiller compres- sor motor and its power lead insulation resistance with

a500-v insulation tester such as a megohmmeter. (Use

a5000-v tester for motors rated over 600 v.) Factory- mounted starters do not require a megohm test.

a.Open the starter main disconnect switch and follow lockout/tagout rules.

If the motor starter is a solid-state starter, the motor leads must be disconnected from the starter before an insulation test is performed. The voltage generated from the tester can damage the starter solid-state components.

b.With the tester connected to the motor leads, take 10-second and 60-second megohm readings as follows:

6-Lead Motor Ð Tie all 6 leads together and test be- tween the lead group and ground. Next tie leads in pairs, 1 and 4, 2 and 5, and 3 and 6. Test between each pair while grounding the third pair.

3-Lead Motor Ð Tie terminals 1, 2, and 3 together and test between the group and ground.

c.Divide the 60-second resistance reading by the 10-second reading. The ratio, or polarization index, must be one or higher. Both the 10- and 60-second readings must be at least 50 megohms.

If the readings on a ®eld-installed starter are unsat- isfactory, repeat the test at the motor with the power leads disconnected. Satisfactory readings in this sec- ond test indicate the fault is in the power leads.

NOTE: Unit-mounted starters do not have to be meg- ohm tested.

10.Tighten up all wiring connections to the plugs on the SMM, 8-input, and PSIO modules.

11.Ensure that the voltage selector switch inside the power panel is switched to the incoming voltage rating.

12.On chillers with free-standing starters, inspect the power panel to ensure that the contractor has fed the wires into the bottom of the panel. Wiring into the top of the panel can cause debris to fall into the contactors. Clean and inspect the contactors if this has occurred.

Carrier Comfort Network Interface Ð The Carrier Comfort Network (CCN) communication bus wiring is sup- plied and installed by the electrical contractor. It consists of shielded, 3-conductor cable with drain wire.

The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system element on either side of it; the negative pins must be wired to the negative pins; the sig- nal ground pins must be wired to signal ground pins.

To attach the CCN communication bus wiring, refer to the certi®ed drawings and wiring diagrams. The wire is in- serted into the CCN communications plug (COMM1) on the PSIO module. This plug also is referred to as J5.

NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/ nylon, vinyl, Te¯on, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl or Te¯on with a minimum operating tempera- ture range of ±20 C to 60 C is required. See table below for cables that meet the requirements.

MANUFACTURER

CABLE NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

 

 

When connecting the CCN communication bus to a sys- tem element, a color code system for the entire network is recommended to simplify installation and checkout. The fol- lowing color code is recommended:

SIGNAL

CCN BUS CONDUCTOR

PSIO MODULE

COMM 1 PLUG (J5)

TYPE

INSULATION COLOR

PIN NO.

 

 

+

RED

1

Ground

WHITE

2

±

BLACK

3

 

 

 

Check Starter

BE AWARE that certain automatic start arrangements can engage the starter. Open the disconnect ahead of the starter in addition to shutting off the chiller or pump.

Use the instruction and service manual supplied by the starter manufacturer to verify that the starter has been in- stalled correctly.

The main disconnect on the starter front panel may not deenergize all internal circuits. Open all internal and re- mote disconnects before servicing the starter.

Whenever a starter safety trip device activates, wait at least 30 seconds before resetting the safety. The microprocessor maintains its output to the 1CR relay for 10 seconds to de- termine the fault mode of failure.

MECHANICAL-TYPE STARTERS

1.Check all ®eld wiring connections for tightness, clear- ance from moving parts, and correct connection.

2.Check the contactor(s) to be sure they move freely. Check the mechanical interlock between contactors to ensure that 1S and 2M contactors cannot be closed at the same time. Check all other electro-mechanical devices, e.g., relays, timers, for free movement. If the devices do not move freely, contact the starter manufacturer for replacement components.

48

Image 48
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Contents Introduction Abbreviations and ExplanationsChiller Familiarization Refrigeration CycleMOTOR/OIL Refrigeration Cooling Cycle 19XL Rear View Take-Apart Rabbet Fit Connector Cooler In/Out Temperature SensorsCondenser In/Out Temperature Sensors Cooler Pressure Schrader FittingLubrication Cycle Refrigerant Motor Cooling and Oil Cooling CyclesLubrication System Starting Equipment Unit-Mounted Solid-State Starter OptionalDenitions ControlsMajor PIC Components Panel Locations PIC Component Panel19XL Controls and Sensor Locations Pressure Transducer, TypicalPower Panel with Options Control and OIL Heater Voltage Selector S1LID Operation and Menus Fig GeneralSelect − Example of Point Status Screen Status01 Override OperationsExample of Time Schedule Operation Screen 19XL Menu Structure 19XL Service Menu Structure 19XL Service Menu Structure Setpoint Example of Set Point ScreenDescription Range Units Reference Point Name Alarm History LID ScreensExample 1 Ð STATUS01 Display Screen Menu Status SelectExample 2 Ð STATUS02 Display Screen Example 3 Ð STATUS03 Display ScreenExample 4 Ð Setpoint Display Screen MenuExample 5 Ð Configuration Config Display Screen Example 6 Ð LEAD/LAG Configuration Display ScreenECW Control Option ICE Build TerminationExample 7 Ð SERVICE1 Display Screen Example 8 Ð SERVICE2 Display Screen Spare Alert EnableExample 9 Ð SERVICE3 Display Screen Menu ServiceExample 10 Ð Maintenance MAINT01 Display Screen Example 11 Ð Maintenance MAINT02 Display ScreenDischarge Temperature Bearing TemperatureExample 12 Ð Maintenance MAINT03 Display Screen Example 13 Ð Maintenance MAINT04 Display ScreenDescription RANGE/STATUS Units Reference Point Name PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page Lead/Lag Control ECWHgbp Hot Gas BypassPage Ice Build Control Cent CapacityPage Example of Attach to Network Device Screen To LOG onSTART-UP/SHUTDOWN/RECYCLE Sequence FigRecycle Restart Delta T Using the Optional Storage Tank and Pumpout Before Initial START-UPJob Data Required Equipment Required19XL Leak Test Procedures Page Ð HCFC-22 Pressure Ð Temperature F Ð HCFC-22 Pressure Ð Temperature CÐ HFC-134a Pressure Ð Temperature F Ð HFC-134a Pressure Ð Temperature CTemperature Pressure Page Inspect Wiring Check Optional Pumpout Compressor Water PipCheck Starter MECHANICAL-TYPE StartersBenshaw, Inc. Solid-State Starter Power Stack BENSHAW, INC. SOLID-STATE StarterPower Up the Controls and Check the Oil Heater Set Up Chiller Control CongurationLoad Surge Prevention Occurs TOO Soon Occurs TOO Late Amps Correction Factors For 19XL Motors Volt Motor CodeCharge Refrigerant into Chiller 19XL Chiller Equalization Without PUMP- OUT UnitControl Test Menu Functions Tests to be Devices Tested PerformedRefrigerant Charges 19XL Total Refrigerant ChargeCooler SizeInitial START-UP Dry Run to Test Start-Up SequenceCheck Rotation Check Oil Pressure and Compressor Stop Calibrate Motor CurrentOperating Instructions Operator DutiesTo Stop the Chiller Plant Pumpout and Refrigerant Transfer Procedures Operating the Optional Pumpout CompressorTransfer Refrigerant from Storage Tank to Chiller TstatChillers with Isolation Valves Transfer the Refrigerant from Chiller to Storage TankGeneral Maintenance Test After Service, Repair, or Major Leak Ð IfReturn Refrigerant to Normal Operating Conditions Weekly Maintenance Guide Vane Actuator LinkageScheduled Maintenance Check Safety and Operating Controls MonthlyTo Change the OIL Compressor Bearing and Gear Mainten Inspect the Heat Exchanger TubesOptional Pumpout System Controls Troubleshooting Guide MAINT01 MAINT02MAINT03 MAINT04Shutdown with ON/OFF/RESET-OFF Timing OUT or Timed OUTRecycle Shutdown Normal or AUTO.-RESTARTAutorestart in Progress LOW Chilled Water Normal RUN with RESET, TEMPERATURE, or Demand Compressor Jumpstart and Refrigerant ProtectionNormal RUN Overrides Active Alerts OUT-OF-RANGE Sensor FailuresLimited Chiller Protect Limit Faults Protective LimitChiller Alerts Spare Sensor Alert MessagesOther PROBLEMS/MALFUNCTIONS DESCRIPTION/MALFUNCTION Probable CAUSE/REMEDYÐ Thermistor Temperature F vs Resistance/Voltage Drop Temperature Voltage Resistance DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Control Modules Module AddressInput Options Module Starter Management Module SMM Fig Processor Module Psio FigOptions Module Installation Switch Options Setting ModuleTypical Benshaw, Inc. Solid-State Starter internal View Page Page Benshaw, Inc. Solid-State Starter Troubleshooting Guide Problem Probable Causes Area of CorrectionRV1 SCRHeat Exchanger Data Additional Data for Marine WaterboxesCooler CondenserWaterbox Cover Weights CoolersCondensers 1034 kPaCompressor/Motor Weights Compressor WeightsOptional Pumpout System Electrical Data Compressor Fits and Clearances Compressor Assembly Torques Description TorqueFt-lb ``ZCLR COMComm EXTPage CLR Page Chiller Power Panel, Starter Assembly Motor Wiring Schematic Chiller Power Panel, Starter Assembly Motor Wiring Schematic PMR POTGFR HPSTypical Wye-Delta Unit Mounted Starter Wiring Schematic Index Index Copyright 1996 Carrier Corporation

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.