Carrier 19XL specifications Example 8 Ð SERVICE2 Display Screen, Spare Alert Enable, Menu Service

Page 25

Table 2 Ð LID Screens (cont)

EXAMPLE 8 Ð SERVICE2 DISPLAY SCREEN

To access this display from the LID default screen:

1.Press MENU .

2.Press SERVICE .

3.Scroll down to highlight EQUIPMENT SERVICE.

4.Press SELECT .

5.Scroll down to highlight SERVICE2.

6.Press SELECT .

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME

DEFAULT VALUE

OPTIONS BOARD 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 mA POWER CONFIGURATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External = 0, Internal = 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET 20 mA Power Source

0,1

 

res

 

 

 

 

 

 

 

 

 

 

 

20 ma

0

 

 

 

 

 

 

 

 

 

 

 

 

DEMAND 20 mA Power Source

0,1

 

dem

 

 

 

 

 

 

 

 

20 ma

0

 

 

 

 

 

 

 

 

 

SPARE ALERT ENABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disable = 0, Low = 1, High = 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp = Alert Threshold

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHWS Temp Enable

0-2

 

chws

 

 

 

 

 

en

0

CHWS Temp Alert

±40-245 (±40-118)

DEG F (DEG C)

chws

 

 

 

 

 

al

245 (118)

CHWR Temp Enable

0-2

 

chwr

 

 

 

 

en

0

CHWR Temp Alert

±40-245 (±40-118)

DEG F (DEG C)

chwr

 

 

 

 

 

al

245 (118)

Reset Temp Enable

0-2

 

rres

 

 

 

 

en

0

Reset Temp Alert

±40-245 (±40-118)

DEG F (DEG C)

rres

 

 

 

al

245 (118)

Spare Temp 1 Enable

0-2

 

spr1

 

 

 

en

0

Spare Temp 1 Alert

±40-245 (±40-118)

DEG F (DEG C)

spr1

 

 

 

 

al

245 (118)

Spare Temp 2 Enable

0-2

 

spr2

 

 

 

en

0

Spare Temp 2 Alert

±40-245 (±40-118)

DEG F (DEG C)

spr2

 

 

 

 

al

245 (118)

Spare Temp 3 Enable

0-2

 

spr3

 

 

 

en

0

Spare Temp 3 Alert

±40-245 (±40-118)

DEG F (DEG C)

spr3

 

 

 

 

al

245 (118)

 

 

 

 

OPTIONS BOARD 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 mA POWER CONFIGURATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External = 0, Internal = 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPARE 1 20 mA Power Source

0,1

 

sp1

 

 

20 ma

0

SPARE 2 20 mA Power Source

0,1

 

sp2

 

 

20 ma

0

 

 

 

SPARE ALERT ENABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disable = 0, Low = 1, High = 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp = Alert Threshold

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Spare Temp 4 Enable

0-2

 

spr4

 

 

 

en

0

Spare Temp 4 Alert

±40-245 (±40-118)

DEG F (DEG C)

spr4

 

 

 

 

al

245 (118)

Spare Temp 5 Enable

0-2

 

spr5

 

 

 

en

0

Spare Temp 5 Alert

±40-245 (±40-118)

DEG F (DEG C)

spr5

 

 

 

 

al

245 (118)

Spare Temp 6 Enable

0-2

 

spr6

 

 

 

en

0

Spare Temp 6 Alert

±40-245 (±40-118)

DEG F (DEG C)

spr6

 

 

 

 

al

245 (118)

Spare Temp 7 Enable

0-2

 

spr7

 

 

 

en

0

Spare Temp 7 Alert

±40-245 (±40-118)

DEG F (DEG C)

spr7

 

 

 

 

al

245 (118)

Spare Temp 8 Enable

0-2

 

spr8

 

 

 

en

0

Spare Temp 8 Alert

±40-245 (±0-118)

DEG F (DEG C)

spr8

 

 

 

 

al

245 (118)

Spare Temp 9 Enable

0-2

 

spr9

 

 

 

en

0

Spare Temp 9 Alert

±40-245 (±40-118)

DEG F (DEG C)

spr9

 

 

 

 

al

245 (118)

 

 

 

 

NOTE: This screen provides the means to generate alert messages based on exceeding the ``Temp Alert'' threshold for each point listed. If the ``Enable'' is set to 1, a value above the ``Temp Alert'' threshold shall generate an alert message. If the ``Enable'' is set to 2, a value below the ``Temp Alert'' threshold shall generate an alert message. If the ``Enable'' is set to 0, alert generation is disabled.

EXAMPLE 9 Ð SERVICE3 DISPLAY SCREEN

To access this display from the LID default screen:

1.Press

2.Press

MENU

SERVICE

.

.

3. Scroll down to highlight EQUIPMENT SERVICE.

4. Press

SELECT

.

5. Scroll down to highlight SERVICE3.

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME

DEFAULT VALUE

Proportional Inc Band

2-10

 

gv

 

inc

6.5

Proportional Dec Band

2-10

 

gv

 

de

6.0

Proportional ECW Gain

1-3

 

gv

 

ecw

2.0

Guide Vane Travel Limit

30-100

%

gv

 

lim

50

 

25

Image 25
Contents Safety Considerations Start-Up, Operation, and Maintenance InstructionsContents Contents Abbreviations and Explanations IntroductionRefrigeration Cycle Chiller FamiliarizationMOTOR/OIL Refrigeration Cooling Cycle 19XL Rear View Cooler In/Out Temperature Sensors Take-Apart Rabbet Fit ConnectorCondenser In/Out Temperature Sensors Cooler Pressure Schrader FittingRefrigerant Motor Cooling and Oil Cooling Cycles Lubrication CycleLubrication System Unit-Mounted Solid-State Starter Optional Starting EquipmentControls DenitionsMajor PIC Components Panel Locations PIC Component PanelPressure Transducer, Typical 19XL Controls and Sensor LocationsControl and OIL Heater Voltage Selector S1 Power Panel with OptionsGeneral LID Operation and Menus FigSelect Override Operations − Example of Point Status Screen Status01Example of Time Schedule Operation Screen 19XL Menu Structure 19XL Service Menu Structure 19XL Service Menu Structure Example of Set Point Screen SetpointLID Screens Description Range Units Reference Point Name Alarm HistoryExample 1 Ð STATUS01 Display Screen Menu Status SelectExample 3 Ð STATUS03 Display Screen Example 2 Ð STATUS02 Display ScreenExample 4 Ð Setpoint Display Screen MenuExample 6 Ð LEAD/LAG Configuration Display Screen Example 5 Ð Configuration Config Display ScreenECW Control Option ICE Build TerminationExample 7 Ð SERVICE1 Display Screen Spare Alert Enable Example 8 Ð SERVICE2 Display ScreenExample 9 Ð SERVICE3 Display Screen Menu ServiceExample 11 Ð Maintenance MAINT02 Display Screen Example 10 Ð Maintenance MAINT01 Display ScreenDischarge Temperature Bearing TemperatureExample 13 Ð Maintenance MAINT04 Display Screen Example 12 Ð Maintenance MAINT03 Display ScreenDescription RANGE/STATUS Units Reference Point Name PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page ECW Lead/Lag ControlHgbp Hot Gas BypassPage Cent Capacity Ice Build ControlPage To LOG on Example of Attach to Network Device ScreenSequence Fig START-UP/SHUTDOWN/RECYCLERecycle Restart Delta T Before Initial START-UP Using the Optional Storage Tank and PumpoutJob Data Required Equipment Required19XL Leak Test Procedures Page Ð HCFC-22 Pressure Ð Temperature C Ð HCFC-22 Pressure Ð Temperature FÐ HFC-134a Pressure Ð Temperature C Ð HFC-134a Pressure Ð Temperature FTemperature Pressure Page Check Optional Pumpout Compressor Water Pip Inspect WiringMECHANICAL-TYPE Starters Check StarterBENSHAW, INC. SOLID-STATE Starter Benshaw, Inc. Solid-State Starter Power StackSet Up Chiller Control Conguration Power Up the Controls and Check the Oil HeaterLoad Surge Prevention Occurs TOO Soon Occurs TOO Late Volt Motor Code Amps Correction Factors For 19XL Motors19XL Chiller Equalization Without PUMP- OUT Unit Charge Refrigerant into ChillerControl Test Menu Functions Tests to be Devices Tested Performed19XL Total Refrigerant Charge Refrigerant ChargesCooler SizeDry Run to Test Start-Up Sequence Initial START-UPCheck Rotation Calibrate Motor Current Check Oil Pressure and Compressor StopOperating Instructions Operator DutiesTo Stop the Chiller Plant Operating the Optional Pumpout Compressor Pumpout and Refrigerant Transfer ProceduresTransfer Refrigerant from Storage Tank to Chiller TstatTransfer the Refrigerant from Chiller to Storage Tank Chillers with Isolation ValvesTest After Service, Repair, or Major Leak Ð If General MaintenanceReturn Refrigerant to Normal Operating Conditions Guide Vane Actuator Linkage Weekly MaintenanceCheck Safety and Operating Controls Monthly Scheduled MaintenanceTo Change the OIL Inspect the Heat Exchanger Tubes Compressor Bearing and Gear MaintenOptional Pumpout System Controls Troubleshooting Guide MAINT02 MAINT01MAINT03 MAINT04Timing OUT or Timed OUT Shutdown with ON/OFF/RESET-OFFNormal or AUTO.-RESTART Recycle ShutdownAutorestart in Progress LOW Chilled Water Compressor Jumpstart and Refrigerant Protection Normal RUN with RESET, TEMPERATURE, or DemandOUT-OF-RANGE Sensor Failures Normal RUN Overrides Active AlertsLimited Protective Limit Chiller Protect Limit FaultsSpare Sensor Alert Messages Chiller AlertsDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY Other PROBLEMS/MALFUNCTIONSTemperature Voltage Resistance Drop Ð Thermistor Temperature F vs Resistance/Voltage DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Module Address Control ModulesInput Options Module Processor Module Psio Fig Starter Management Module SMM FigOptions Module Switch Options Setting Module InstallationTypical Benshaw, Inc. Solid-State Starter internal View Page Page Problem Probable Causes Area of Correction Benshaw, Inc. Solid-State Starter Troubleshooting GuideRV1 SCRAdditional Data for Marine Waterboxes Heat Exchanger DataCooler CondenserCoolers Waterbox Cover WeightsCondensers 1034 kPaCompressor Weights Compressor/Motor WeightsOptional Pumpout System Electrical Data Compressor Fits and Clearances Description Torque Compressor Assembly TorquesFt-lb ``ZCOM CLRComm EXTPage CLR Page Chiller Power Panel, Starter Assembly Motor Wiring Schematic Chiller Power Panel, Starter Assembly Motor Wiring Schematic POT PMRGFR HPSTypical Wye-Delta Unit Mounted Starter Wiring Schematic Index Index Copyright 1996 Carrier Corporation

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.