Oil Charge Ð The 19XL compressor holds approxi- mately 8 gal. (30 L) of oil. The chiller will be shipped with oil in the compressor. When the sump is full, the oil level should be no higher than the middle of the upper sight glass and minimum level is the bottom of the lower sight glass (Fig. 2A or 2B). If oil is added, it must meet Carrier's speci- ®cation for centrifugal compressor usage as described in the Oil Speci®cation section on page 63. Charge the oil through the oil charging valve, located near the bottom of the trans- mission housing (Fig. 2A or Fig. 2B). The oil must be pumped from the oil container through the charging valve due to higher refrigerant pressure. The pumping device must be able to lift from 0 to 200 psig (0 to 1380 kPa) or above unit pressure. Oil should only be charged or removed when the chiller is shut down.
Power Up the Controls and Check the Oil Heater
ÐEnsure that an oil level is visible in the compressor before energizing controls. A circuit breaker in the starter energizes the oil heater and the control circuit. When ®rst powered, the LID should display the default screen within a short period of time.
The oil heater is energized by powering the control cir- cuit. This should be done several hours before start-up to minimize oil-refrigerant migration. The oil heater is con- trolled by the PIC and is powered through a contactor in the power panel. Starters contain a separate circuit breaker to power the heater and the control circuit. This set up allows the heater to energize when the main motor circuit breaker is off for service work or extended shutdowns. The oil heater relay status can be viewed on the Status02 table on the LID. Oil sump temperature can be viewed on the LID default screen.
When the Time/Date is con®gured for the ®rst time or if power is lost for more than 3 hours, the oil heat algorithm will take effect before the compressor can start. See the Oil Sump Temperature Control section on page 32 for addi- tional information. The oil pump will then energize for 1 to 2 minutes to bring the oil temperature to normal operating temperature. A LOW OIL TEMPERATURE alert will show on the default LID screen if the operator has the controls set to start.
SOFTWARE VERSION Ð The software version will always be labeled on the PSIO module, and on the back side of the LID module. On both the Controller ID and LID ID display screens, the software version number will also appear.
Set Up Chiller Control Con®guration
Do not operate the chiller before the control con®gu- rations have been checked and a Control Test has been satisfactorily completed. Protection by safety controls cannot be assumed until all control con®gurations have been con®rmed.
As con®guration of the 19XL unit is performed, write down all con®guration settings. A log, such as the one shown on pages CL-1 to CL-2, provides a convenient list for con®gu- ration values.
Input the Design Set Points Ð Access the LID set point screen and view/modify the base demand limit set point, and either the LCW set point or the ECW set point. The PIC can control a set point to either the leaving or entering chilled water. This control method is set in the Equipment Con®gu- ration table, Con®g table.
Input the Local Occupied Schedule (OCCPC01S)
ÐAccess the schedule OCCPC01S screen on the LID and set up the occupied time schedule per the customer's requirements. If no schedule is available, the default is fac- tory set for 24 hours occupied 7 days per week including holidays.
For more information about how to set up a time sched- ule, see the Controls section, page 11.
The CCN Occupied Schedule should be con®gured if a CCN system is being installed or if a secondary time sched- ule is needed.
NOTE: The default CCN Occupied Schedule is OCCPC03S for Software Version 09 and above; the default is OCCPC02S for Software Version 08 and below.
Selecting Refrigerant Type Ð The 19XL control must be con®gured for the refrigerant being used, either HCFC-22 or HFC-134a.
TO CONFIRM REFRIGERANT TYPE Ð Con®rm that the correct refrigerant type is indicated by entering the Controls Test tables on the Service menu, Fig. 17. Select REFRIG- ERANT TYPE. The screen will display the current refrig-
erant setting. Press EXIT softkey to leave the screen with- out changes.
TO CHANGE REFRIGERANT TYPE Ð Enter the Con- trols Test tables on the Service Menu. See Fig. 17. Select
REFRIGERANT TYPE. The screen will display the current
refrigerant setting. Press YES softkey to change the cur-
rent setting. Next, move to the ATTACH TO NETWORK DEVICE screen on the Service menu and the ATTACH TO LOCAL DEVICE to upload the new refrigerant tables.
Input Service Con®gurations Ð The following con- ®gurations require the LID screen to be in the Service por- tion of the menu.
·password
·input time and date
·LID con®guration
·controller identi®cation
·service parameters
·equipment con®guration
·automated control test
PASSWORD Ð When accessing the Service tables, a pass- word must be entered. All LIDs are initially set for a pass- word of 1-1-1-1. This password may be changed in the LID con®guration screen, if desired.
INPUT TIME AND DATE Ð Access the Time and Date table on the Service menu. Input the present time of day, date, and day of the week. ``Holiday Today'' should only be con®gured to ``Yes'' if the present day is a holiday.
CHANGE LID CONFIGURATION IF NECESSARY Ð The LID Con®guration screen is used to view or modify the LID CCN address, change to English or SI units, and to change the password. If there is more than one chiller at the jobsite, change the LID address on each chiller so that each chiller has its own address. Note and record the new address. Change the screen to SI units as required, and change the password if desired.