RESET BUTTON
CLOG INDICATOR

10.3 Cleaning / Changing Air Filter Element

Clean Replace

Every 200 hours Every 500 hours

Loosen the bolt that is holding the air cleaner and remove the cleaner cap Unscrew the wing nut and remove the filter element

Clean or replace the filter element, and reinstall it in reverse order

CLEANER CAP

WING NUT

 

 

 

CLEANER CAP

 

 

 

 

 

FIXING BOLT

AIR CLEANER

AIR FILTER ELEMENT

 

<Caution>

￿Always make sure that the arrow mark on the cleaner cap is pointing upward

￿Clean more frequently, if used in dusty environment

￿Air filter element:

ISUZU Part No.

9142151321

￿To clean the air filter element:

￿If the element has dried contaminants, it may be cleaned by blowing compressed air from the inside.

￿If the element has carbon or grease, it should be replaced with new element.

￿Clog Indicator

The clog indicator to display clog in the air filter element is incorporated to air filter unit.

￿Whenever RED SIGNAL appears in the indicator window, clean or change element regardless of operation hour.

￿After cleaning or changing finishes, push the reset button to release the RED SIGNAL.

WINDOW (RED SIGNAL)

- 41 -

Image 41
Contents DG1000MI Introduction Suffocation from exhaust fume Safety GuidelinesElectrical Shock InjuriesExplosion Injuries to eyes and skinFire BurnsInjuries Location of Warning labels Specification Matrix SpecificationsExternal view Use PartsAmbient Condition Control panel Monitor Display EquipmentEngine Oil Monitoring Lamp for oil pressure low Injuries Water Temperature Gauge Battery Charge Monitoring Lamp charge lampGauges Hour Meter built into the TachometerGenerator Gauges Fuel GaugeAmp Meter Frequency MeterEmergency Stop button Switch Starter SwitchPanel Light / Pilot Lamp Thermal Relay Amp Meter Changeover SwitchEarth Leakage Relay Unit Voltage Regulator and Throttle LeverFuel Line Changeover Valve 3-way valve Using fuel from built-in fuel tank< > Transportation Transport and InstallationLifting Equipment TransportationSelecting Cable InstallationConnection Electrical damages For 1-Phase Load1 Connecting CableLoad Connection Terminal Plate 3-Phase For 3-Phase Load 2 1-Phase Output Terminals & Receptacles For 1-Phase Load2Grounding Work Earth Leakage Relay and GroundingOperation Check Electrical Shock Earth leakage breaker relay has activated Initialization and pre-checkElectrical Shock Injuries Fire BurnsEngine Oil Capacity Checking Engine OilSelecting proper engine oil Checking Coolant reservoir tank / Adding coolant Checking Coolant/waterChecking Radiator / Adding water Tension Checking Fan BeltCoolant Capacity Condition Checking FuelChecking Fuel, Engine Oil, and Water leakage Checking BatteryReplacing the battery Initializing / preparation OperationFrequency Adjust Screw Damages to the property 200/400 Voltage Changeover Dual Voltage SystemDuring operation Refer to 7-2. Connecting cableStopping the Generator Protection FeaturesFeature List During Operation section Connecting to External Fuel Tank Maintenance Generator side Engine SideReplace, refer to 8-1 Checking Engine Oil 10.1 Oil ChangeCleaning / Changing Air Filter Element Draining Water from Water Separator Cleaning / Changing Fuel FilterClean gauze filter in engine feed pump Clean gauze filter in water separatorIsuzu Part No 8970631550 Draining Water from Fuel Tank Long-term Storage Storage ProceduresStacking Troubleshooting Ask our distributor to repair Page Generator Wiring Diagram Engine Wiring Diagram