DCA-125USJ (50 HZ)— OUTPUT TERMINAL PANEL FAMILIARIZATION
Connecting Loads
Loads can be connected to the generator by the OuputTerminal Lugs or the convienience receptacles. (See Figure 13). Make sure to read the operation manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a
Blower Fan
This unit has an intake fan located at the rear of the machine to draw outside air into the cabinet to cool the engine. The fan has a 10 amp AC fuse located beneath the Voltage Selector Switch (Figure 15).
Figure 15. Blower Fan Fuse
Figure 13. Connecting Loads
Over Current Relay
An over current relay (Figure 14) is connected to the main circuit breaker. In the event of an overload, both the circuit breaker and the over current relay may trip. If the circuit breaker can not be reset, the reset button on the over cur- rent relay must be pressed. The over current relay is lo- cated in the control box.
DANGER:
This fuse has current running through it any time the engine is operating. THIS FUSE IS NOT connected to the main circuit breaker OF the generator. Attempting to
replace the fuse with the engine and/or generator operating could result in electrocution and severe bodily harm. ALWAYS turn the unit completely off before attempting to replace or handle THIS fuse
Figure 14. Over Current Relay
PAGE 28 —