4.1 Planning
Carefully plan the generator exhaust system to ensure a safe, quiet installation. Verify that the installation complies with all state and local requirements and applicable articles of the codes listed at the beginning of this manual.
4.2 Clearance Requirements
Kohler Co. recommends a minimum clearance of 38 mm (1 1/2 in.) between the exhaust system parts and the fuel system, the electrical system, and all combustible components to protect the generator set components and to avoid igniting adjacent combustible materials.
4.3 Exhaust Piping, If Used
Route the exhaust piping to maintain minimum clearances and to minimize exhaust piping bends. Use a tail pipe as short as possible with as few bends as possible to reduce back pressure. Design the exhaust piping to prevent excessive back pressure of the
For generator sets without a
| Allowable Exhaust |
Model | Back Pressure |
|
|
10/13/15ERG | < 10.2 kPa (3.0 in. Hg) |
|
|
Figure 4-1 Allowable Exhaust Back Pressure
8 Exhaust System |