8.2.3Adjusting the Voltage, Gain, and Volts/Hz

After setting the system voltage, check the output voltage and adjust, if necessary, using the following procedures. Follow the instructions in Figure 8-6 to adjust the voltage, gain, and volts/Hz while the engine is running. An x in the Display column in Figure 8-6 indicates a number from 0 to 9. Use the up arrow to increase a setting or the down arrow to decrease the setting.

Note: Save your settings before exiting the configuration mode.

Pressing the Select button when SAVE is displayed returns to the first parameter, voltage adjust (1P).

Voltage changes are lost if they are not saved before the generator set shuts down. The generator set continues to run with the new settings until it shuts down but then reverts to the previous settings at the next startup if the changes have not been saved.

Note: A digital multimeter is required for these adjustments.

8.2.4Voltage Adjustment

WARNING

Hazardous voltage. Moving rotor.

Can cause severe injury or death.

Operate the generator set only when all guards and electrical enclosures are in place.

Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.

Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.

Voltage Adjustment Procedure

Note: Refer to Figure 8-6 and Figure 8-7 for instructions to adjust the voltage using the ADC 2100.

1.With the generator set off, connect a digital multimeter to the output leads or an electrical outlet on the load side of the generator set. Set the meter to measure AC voltage.

2.Start the generator set by moving the generator set master switch to the RUN position.

3.Use the ADC controller to adjust the voltage (parameter 1P) until the output voltage reaches the desired value. See Figure 8-5 for the approximate change in voltage per step in parameter 1P.

Measured

Voltage Change per Step, VAC

Voltage, VAC

 

 

Coarse Adjust

Fine Adjust

 

 

 

 

85--132

5

0.5

180--251

7

0.7

Figure 8-5 Voltage Adjustment

4.Adjust the voltage stability (gain, parameter 2P) to minimize light flicker.

5.Readjust the voltage, if necessary.

6.Readjust the voltage stability (gain, parameter 2P), if necessary.

7.Readjust the voltage (parameter 1P), if necessary.

8.Stop the generator set.

TP-6335 9/04

Reconnection/Adjustments 29

Image 39
Contents TP-6335 9/04 ModelPage Table of Contents Page Safety Precautions and Instructions BatteryAccidental Starting Exhaust System Engine Backfire/Flash FireFuel System Hazardous NoiseHazardous Voltage/ Electrical Shock Moving Parts Hot Parts246242 VI Safety Precautions and Instructions TP-6335 9/04 Generator Set Operation Installation StandardsGenerator Set Specifications IntroductionIntroduction TP-6335 9/04 Vehicle-Floor Mounting Location and MountingGeneral Considerations LocationLocation and Mounting TP-6335 9/04 Block Heaters High Water Temperature SwitchCooling System Air RequirementsCooling System TP-6335 9/04 Exhaust System Planning Clearance RequirementsExhaust Piping, If Used Gasoline Fuel SystemFuel Filters or Strainers LP GasFuel Lines Fuel Pump Lift Capability Max., Gasoline Models Fuel Pump Lift and Fuel ConsumptionFuel System TP-6335 9/04 Electrical System Electrical ConnectionsAC Load Lead Connections Transfer Switch Connections Wire AC Circuit Circuit Breaker Considerations Circuit ProtectionElectrical Connections Circuit Breaker InstallationADC 2100 Continuous Power Mode Jumper CCA Battery and ConnectionsView B Remote ConnectionElectrical System TP-6335 9/04 Dimension Drawing, Gasoline Fuel System Installation DrawingDimension Drawing, LP Fuel System Dimension Drawing, Floor Template Installation Drawing TP-6335 9/04 Reconnection/Adjustments Four-Lead Reconnection 100--120-Volt, 2-Wire Configuration200--220--240-Volt, 2-Wire Configuration For Models with ADC Configuration Mode Time Out Advanced Digital Control ADCController Software Version Number Voltage Adjustment Adjusting the Voltage, Gain, and Volts/HzOn Figure Output Voltage Adjustment ModeFrom Figure V EController Configuration Controller Parameters N c V E 11 Save Mode after configuring generator set parameters Reconnection/Adjustments TP-6335 9/04 General Wattage Requirements Appendix a Generator Selection and Wattage RequirementsAnsi Appendix B AbbreviationsLCB Page Page By Kohler Co. All rights reserved