Controller Configuration Mode (Use with Figure
Hold the Select button:
Move the generator set master switch to the RUN position. (The generator set engine will not start.)
Wait about 5 seconds until the display shows the program version number. (The number may be different than the one shown here.)
Press the down arrow key and then the up arrow key 3 times to enter the configuration mode. (This is the controller “password.”)
Now release the Select button.
Press:
or | To set the voltage/frequency setting for 60 Hz | |
models. | ||
| ||
| To step to the next parameter, unit configuration | |
| Uc. | |
or | To set the unit configuration setting to Uc02, if | |
necessary. | ||
| ||
| To step to the next parameter, engine type Ec. | |
or | To set the engine type, if necessary. | |
| To step to the next parameter, advanced | |
| configuration mode or save mode selection. |
Now either save your settings or enter the Advanced Configuration Mode to set the engine data inputs, battery voltage, and communications.
Press: |
|
| To enter advanced configuration mode. |
| Go to Figure |
OR: |
|
or | To proceed to the save mode without |
| entering the advanced configuration mode. |
| Go to Figure |
Display:
. 0
1 0 4
U u 0 x
U u 0 1
U c 0 2
E c 0 3
A d n c
E d 0 x
S A V E
Note: Shaded boxes show which number in the controller display changes when the up or down arrow key is pressed. “x” denotes any number from 0 to 9.
Figure 8-9 Configuration Mode (system voltage, unit configuration, and engine type parameters)
34 Reconnection/Adjustments |