8.2.5Controller Configuration

The controller configuration for each generator model is set at the factory and should not normally require changes. The controller’s configuration mode allows adjustment of the system parameters listed in this section. Use the instructions in this section to check the configuration after installation and change them to match the settings shown in Figure 8-8, if necessary.

The controller will automatically exit the configuration mode without saving any changes after about 1 minute if no buttons are pressed. Start the configuration procedure over again from the beginning if the controller exits the configuration mode before the settings have been saved.

Follow the instructions in Figure 8-9 to enter the configuration mode while the engine is not running and then step through the following parameters. Use the up () and down () arrow buttons to select the appropriate setting for the application.

Voltage/frequency setting (Uu). Select the system voltage and frequency from the table in Figure 8-8. For system voltages not listed in the table, select the setting closest to the system voltage and then adjust the output voltage to the desired level using the instructions in Section 8.2.4.

Note: This parameter sets the nominal system voltage and frequency. To adjust the output (measured) voltage, see Section 8.2.4.

Unit configuration (Uc). This parameter sets the generator set type: marine, standby, or mobile. The setting for the 10/13/15ERG is Uc02, mobile.

Note: The engine type (EC) and the engine data input type (ED) are factory set and should only be changed by an authorized Kohler dealer/distributor. Incorrect settings will make your unit non-functional.

Engine configuration (Ec). The engine configuration must match the generator set engine type. The engine configuration setting for the 10/13/15ERG is Ec03.

Advanced configuration mode (Adnc). The data input types, battery voltage, and communications setting can be changed in the advanced configuration mode. Press the up arrow button when Adnc is displayed to enter the advanced configuration mode.

Engine data input types (Ed). This setting defines the type of senders used on the generator set engine. Setting the Ec parameter automatically sets the Ed parameter.

The remote digital gauge requires the optional analog oil pressure sender. Install the optional sender and change the Ed parameter to Ed02.

Battery voltage (Bt). This setting toggles between 12 and 24 VDC for the engine starting battery voltage. The 10/13/15ERG models use a 12-volt battery, Bt12.

Communications setting (Cn). This setting allows the user to set the controller for communication with optional meters. The 10/13/15ERG models are factory-set for no CAN communications, Cn00. Change this setting to Cn01 if the optional Remote Digital Gauge is used.

Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to the last saved settings when the master switch is moved to the OFF/RESET position.

32 Reconnection/Adjustments

TP-6335 9/04

Image 42
Contents Model TP-6335 9/04Page Table of Contents Page Safety Precautions and Instructions BatteryAccidental Starting Engine Backfire/Flash Fire Exhaust SystemFuel System Hazardous NoiseHazardous Voltage/ Electrical Shock Hot Parts Moving Parts246242 VI Safety Precautions and Instructions TP-6335 9/04 Introduction Installation StandardsGenerator Set Specifications Generator Set OperationIntroduction TP-6335 9/04 Location Location and MountingGeneral Considerations Vehicle-Floor MountingLocation and Mounting TP-6335 9/04 Air Requirements High Water Temperature SwitchCooling System Block HeatersCooling System TP-6335 9/04 Exhaust System Planning Clearance RequirementsExhaust Piping, If Used Fuel System GasolineFuel Filters or Strainers LP GasFuel Lines Fuel Pump Lift and Fuel Consumption Fuel Pump Lift Capability Max., Gasoline ModelsFuel System TP-6335 9/04 Electrical System Electrical ConnectionsAC Load Lead Connections Transfer Switch Connections Wire AC Circuit Circuit Protection Circuit Breaker ConsiderationsCircuit Breaker Installation Electrical ConnectionsADC 2100 Continuous Power Mode Jumper Battery and Connections CCARemote Connection View BElectrical System TP-6335 9/04 Installation Drawing Dimension Drawing, Gasoline Fuel SystemDimension Drawing, LP Fuel System Dimension Drawing, Floor Template Installation Drawing TP-6335 9/04 Reconnection/Adjustments 100--120-Volt, 2-Wire Configuration Four-Lead Reconnection200--220--240-Volt, 2-Wire Configuration For Models with ADC Configuration Mode Time Out Advanced Digital Control ADCController Software Version Number Adjusting the Voltage, Gain, and Volts/Hz Voltage AdjustmentOutput Voltage Adjustment Mode On FigureV E From FigureController Configuration Controller Parameters N c V E 11 Save Mode after configuring generator set parameters Reconnection/Adjustments TP-6335 9/04 Appendix a Generator Selection and Wattage Requirements General Wattage RequirementsAppendix B Abbreviations AnsiLCB Page Page By Kohler Co. All rights reserved