Kohler 10ERG, 15ERG, 13ERG manual Advanced Digital Control ADC, Configuration Mode Time Out

Page 38

8.2Advanced Digital Control (ADC 2100)

The model 10/13/15ERG generator sets use the ADC 2100. The ADC 2100 uses password-protected menus for generator output adjustments and controller configuration.

This section contains instructions for using the ADC’s password-protected menus to check and adjust the generator output and controller configuration. The controller configuration and generator set output are factory-set and should not require field adjustment under normal circumstances. Check and adjust the configuration and/or output in the following cases:

DCheck and adjust the controller configuration and generator output after generator set reconnection to a different voltage.

DCheck the controller configuration when troubleshooting generator set problems.

DCheck and adjust the generator set output after installation if the voltage requires adjustment for a particular application.

8.2.1Configuration Mode Time Out

The controller will automatically exit the configuration mode without saving any changes after about 1 minute if no buttons are pressed. Start the configuration procedure over again from the beginning if the controller exits the configuration mode before the settings have been saved.

8.2.2Controller Software Version Number

The application software for controller operation is factory-loaded onto the Advanced Digital Control. At times, it may be necessary to check the software version number for troubleshooting purposes.

The controller’s application software version number is displayed on the LED screen during the key sequence to enter the configuration mode, after the Select button has been pressed and held for about five seconds. For example, 01.00 will be displayed for software version 1.00.

28 Reconnection/Adjustments

TP-6335 9/04

Image 38
Contents Model TP-6335 9/04Page Table of Contents Page Accidental Starting Safety Precautions and InstructionsBattery Engine Backfire/Flash Fire Exhaust SystemHazardous Voltage/ Electrical Shock Fuel SystemHazardous Noise Hot Parts Moving Parts246242 VI Safety Precautions and Instructions TP-6335 9/04 Introduction Installation StandardsGenerator Set Specifications Generator Set OperationIntroduction TP-6335 9/04 Location Location and MountingGeneral Considerations Vehicle-Floor MountingLocation and Mounting TP-6335 9/04 Air Requirements High Water Temperature SwitchCooling System Block HeatersCooling System TP-6335 9/04 Exhaust System Exhaust Piping, If Used PlanningClearance Requirements Fuel System GasolineFuel Lines Fuel Filters or StrainersLP Gas Fuel Pump Lift and Fuel Consumption Fuel Pump Lift Capability Max., Gasoline ModelsFuel System TP-6335 9/04 AC Load Lead Connections Electrical SystemElectrical Connections Transfer Switch Connections Wire AC Circuit Circuit Protection Circuit Breaker ConsiderationsCircuit Breaker Installation Electrical ConnectionsADC 2100 Continuous Power Mode Jumper Battery and Connections CCARemote Connection View BElectrical System TP-6335 9/04 Installation Drawing Dimension Drawing, Gasoline Fuel SystemDimension Drawing, LP Fuel System Dimension Drawing, Floor Template Installation Drawing TP-6335 9/04 Reconnection/Adjustments 100--120-Volt, 2-Wire Configuration Four-Lead Reconnection200--220--240-Volt, 2-Wire Configuration For Models with ADC Controller Software Version Number Configuration Mode Time OutAdvanced Digital Control ADC Adjusting the Voltage, Gain, and Volts/Hz Voltage AdjustmentOutput Voltage Adjustment Mode On FigureV E From FigureController Configuration Controller Parameters N c V E 11 Save Mode after configuring generator set parameters Reconnection/Adjustments TP-6335 9/04 Appendix a Generator Selection and Wattage Requirements General Wattage RequirementsAppendix B Abbreviations AnsiLCB Page Page By Kohler Co. All rights reserved