Kohler 10ERG, 15ERG, 13ERG manual Fuel Filters or Strainers, LP Gas, Fuel Lines

Page 20

5.1.1Fuel Lines

Note: Keep fuel lines away from the exhaust system.

Routing fuel lines. Take care when routing the fuel line from the fuel tank to the generator set. Keep the fuel lines as short as possible but maintain adequate clearance from the exhaust system. Route the fuel lines along the frame or undercarriage—never route the fuel lines inside the habitable area of the vehicle. Locate the fuel lines with the entry point near the fuel pump. See Section 5.4 for the fuel pump lift.

Sizing fuel inlet and return lines. Size the fuel line to handle the flow of fuel and to withstand road shock and year-round climate conditions. Use steel tubing as the codes require. Use 8 mm (0.31 in.) ID tubing with a 230 mm (8 in.) (minimum) flexible section to allow free movement of the generator set.

Flexible hose sections. If a metal fuel line draws fuel from the fuel tank, install a flexible hose section to connect the metal line to the fuel pump. The flexible section allows generator set vibrational motion during operation. See Section 7 for the fuel inlet and the fuel return connection points.

Note: Gasoline-fueled engines require a type A1 hose.

5.2 Fuel Filters or Strainers

Gasoline model generator sets are shipped with a fuel filter. No additional fuel filter or strainer is required.

 

1

 

ADV-6450-E

1.

Fuel filter

Figure 5-2 Fuel Filter Location (Gasoline Models)

5.3 LP Gas

LP fuel hose. Use a flexible fuel hose designated for use with LP fuel between the generator set and the main fuel tank. See Section 7 for the fuel inlet connection point. Take care when routing the fuel line. Maintain a 51 mm (2 in. ) clearance between the fuel line and any bare exhaust component. Do not tie any electrical wiring to the fuel line. If the flexible fuel line passes through sheet metal, install grommets or clamps to prevent hose abrasion. The LP fuel system shall conform to Section 3-6.4 of NFPA58, Storage and Handling of Liquified Petroleum Gases.

For an LP gas system, use UL classified pipe joint sealing compound to prevent dangerous fuel leaks. Use a sealing compound approved for use with LP gas. Apply UL classified sealing compound at all fuel line pipe joints.

Use flexible fuel lines in areas where vibration and/or movement of connected components is likely, such as the main fuel line to the generator set. Use seamless steel tubing wherever long main fuel lines are required.

Testing the fuel system. After all of the LP connections have been completed, pressure test the entire system to 6--8 ounces (10--14 inches) water column. Test the connections for leakage with soapy water or bubble solution. Do not use solutions that contain ammonia or chlorine since the solution will not bubble for an accurate leakage test.

The gas supply pressure should not exceed 6 ounces. To check the inlet pressure, remove the plug on the fuel inlet for the gas regulator. Insert an ounce pressure gauge or manometer. Adjust the operating pressure to 4--6 ounces or 7--11 inches water column; adjust the inlet pressure on the primary regulator.

Note: Fuel leakage could cause an explosion. After making all LP gas connections, pressure test the entire system to 6--8 ounces (10--14 inches) water column.

Note: Gas pressure above 10 ounces can result in non operation of the gas valve.

10 Fuel System

TP-6335 9/04

Image 20
Contents Model TP-6335 9/04Page Table of Contents Page Accidental Starting Safety Precautions and InstructionsBattery Engine Backfire/Flash Fire Exhaust SystemHazardous Voltage/ Electrical Shock Fuel SystemHazardous Noise Hot Parts Moving Parts246242 VI Safety Precautions and Instructions TP-6335 9/04 Installation Standards Generator Set SpecificationsIntroduction Generator Set OperationIntroduction TP-6335 9/04 Location and Mounting General ConsiderationsLocation Vehicle-Floor MountingLocation and Mounting TP-6335 9/04 High Water Temperature Switch Cooling SystemAir Requirements Block HeatersCooling System TP-6335 9/04 Exhaust System Exhaust Piping, If Used PlanningClearance Requirements Fuel System GasolineFuel Lines Fuel Filters or StrainersLP Gas Fuel Pump Lift and Fuel Consumption Fuel Pump Lift Capability Max., Gasoline ModelsFuel System TP-6335 9/04 AC Load Lead Connections Electrical SystemElectrical Connections Transfer Switch Connections Wire AC Circuit Circuit Protection Circuit Breaker ConsiderationsCircuit Breaker Installation Electrical ConnectionsADC 2100 Continuous Power Mode Jumper Battery and Connections CCARemote Connection View BElectrical System TP-6335 9/04 Installation Drawing Dimension Drawing, Gasoline Fuel SystemDimension Drawing, LP Fuel System Dimension Drawing, Floor Template Installation Drawing TP-6335 9/04 Reconnection/Adjustments 100--120-Volt, 2-Wire Configuration Four-Lead Reconnection200--220--240-Volt, 2-Wire Configuration For Models with ADC Controller Software Version Number Configuration Mode Time OutAdvanced Digital Control ADC Adjusting the Voltage, Gain, and Volts/Hz Voltage AdjustmentOutput Voltage Adjustment Mode On FigureV E From FigureController Configuration Controller Parameters N c V E 11 Save Mode after configuring generator set parameters Reconnection/Adjustments TP-6335 9/04 Appendix a Generator Selection and Wattage Requirements General Wattage RequirementsAppendix B Abbreviations AnsiLCB Page Page By Kohler Co. All rights reserved