Output Voltage Adjustment Mode:
Move the generator set master switch to the RUN position. The generator set engine starts and the controller display shows the engine runtime hours.
Hold:
Wait about 5 seconds until the display changes from runtime hours to the program version number.
Press the down arrow key and then the up arrow key 3 times to enter the adjustment mode. (This is the controller “password.”)
The controller is now in the voltage coarse adjustment mode.
Press:
or | To raise or lower the voltage in large increments | |
(approximately | ||
|
To enter fine voltage adjustment mode.
Display :*
x x x x
x. x x
1 P x x
1 P x x
1 P x x
or
or
or
or
To raise or lower the voltage in smaller increments (approximately
To enter coarse voltage stability (gain) adjustment mode.
2 P x x
To raise or lower the voltage stability (gain) in large increments.
To enter fine voltage stability (gain) adjustment mode.
2 P x x
To raise or lower the voltage stability (gain) in smaller increments.
To enter volts/Hz adjustment mode.
3 P 0 x
To raise or lower the volts/Hz: 00=low; 09= high
Continued on Figure |
|
* Shaded boxes show which character in the controller display changes for each adjustment. “x” in the |
|
examples above denotes any number from 0 to 9. The actual values may vary from | TP6196 |
Figure 8-6 Output Voltage Adjustments
30 Reconnection/Adjustments |